2CCS573103R8164 ABB S403M-C16NP 16A 3P+N Type C Miniature Circuit Breaker

2CCS573103R8164 ABB S403M-C16NP 16A 3P+N Type C Miniature Circuit Breaker

ABB S403M-C16NP is a 16 A 3P+N Type C SMISSLINE TP miniature circuit breaker with protected neutral, providing overload and short-circuit protection with a 10 kA rated short-circuit capacity.

SKU: 2CCS573103R8164Alt SKU: S403MC16NPMPN: 2CCS573103R8164
Price
List Price £176.69 ex VAT
Your Price (ex VAT) Save 35%
£114.85 35% OFF
You save £61.84 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £114.85
Trade pricing is personalised to your account

Manufacturer Lead Time

£114.85

Why Choose the ABB S403M-C16NP Miniature Circuit Breaker?

The ABB S403M-C16NP is a current-limiting 3P+N miniature circuit breaker (MCB) with protected neutral, designed to provide reliable overload and short-circuit protection for three-phase circuits with neutral. Part of the ABB SMISSLINE TP S400M series, it combines four-pole circuit protection with the installation efficiency of ABB's modular plug-in distribution architecture.

Rated at 16 A with a Type C tripping characteristic, the S403M-C16NP is suitable for commercial and industrial circuits where moderate transient inrush currents may occur. Its thermal overload and electromechanical short-circuit tripping functions provide dependable protection for connected conductors while accommodating normal starting currents from appropriately selected equipment.

The S403M-C16NP provides a rated short-circuit capacity (Icn) of 10 kA and an ultimate short-circuit breaking capacity (Icu) of 25 kA at 230 / 400 V AC. Its neutral is protected at 100% of the nominal pole-conductor value, while the four-module SMISSLINE TP plug-in construction enables efficient integration into compatible ABB distribution assemblies.

Key Advantages

  • 3P+N configuration with protected neutral for comprehensive three-phase-plus-neutral circuit protection.
  • 16 A rated current for appropriately designed commercial and industrial circuits.
  • Type C tripping characteristic suitable for loads with moderate transient inrush currents.
  • 10 kA rated short-circuit capacity (Icn) to EN 60898-1.
  • 25 kA ultimate short-circuit breaking capacity (Icu) at 230 / 400 V AC to IEC/EN 60947-2.
  • Neutral protected at 100% of the nominal pole-conductor value.
  • Energy-limiting class 3 helps reduce fault energy during short-circuit conditions.
  • Plug-in construction for efficient integration with the ABB SMISSLINE TP system.

Key Features

  • ABB SMISSLINE TP S400M series.
  • 16 A rated current.
  • 3P+N / four-pole configuration.
  • Four protected poles.
  • Type C tripping characteristic.
  • 10 kA Icn at 230 / 400 V AC.
  • 25 kA Icu at 230 / 400 V AC.
  • 415 V AC rated voltage.
  • 440 V rated insulation voltage.
  • 4 kV rated impulse withstand voltage.
  • 50–60 Hz frequency.
  • IP20 protection rating.

Reliable Protection for Three-Phase and Neutral Circuits

The ABB S403M-C16NP protects electrical conductors and connected circuits by automatically interrupting excessive current caused by overload or short-circuit conditions. Its thermal overload protection responds to sustained overcurrent, while the short-circuit release provides rapid disconnection when a high fault current occurs.

The Type C characteristic accommodates moderate transient inrush currents encountered during normal operation of many commercial and industrial loads. Combined with four protected poles, 100% neutral protection and ABB's SMISSLINE TP plug-in architecture, the S403M-C16NP provides an effective solution for three-phase-plus-neutral distribution, control and equipment circuits.

Typical Applications

  • Three-phase-plus-neutral commercial and industrial circuits.
  • Electrical distribution and control panels.
  • Industrial machinery and automation systems.
  • Equipment circuits with moderate starting currents.
  • Manufacturing and production equipment.
  • Building-services electrical distribution.
  • ABB SMISSLINE TP distribution assemblies.

Technical Specifications

Series SMISSLINE TP S400M
ABB order code 2CCS573103R8164
EAN 7612270103928
Product type Miniature circuit breaker (MCB)
Pole configuration 3P+N
Total poles 4
Protected poles 4
Neutral Protected at 100% of nominal pole-conductor value
Rated current 16 A
Tripping characteristic Type C
Rated voltage 415 V AC
Rated insulation voltage 440 V
Rated impulse withstand voltage 4 kV
Frequency 50–60 Hz
Rated short-circuit capacity (Icn) 10 kA at 230 / 400 V AC
Rated ultimate short-circuit breaking capacity (Icu) 25 kA at 230 / 400 V AC
Energy-limiting class 3
Protection rating IP20
Flexible conductor cross-section 0.75–25 mm²
Rigid conductor cross-section 0.75–35 mm²
Operating temperature −25 to +60 °C
Power loss 8.8 W
Installation system ABB SMISSLINE TP plug-in system
Standards EN 60898-1, IEC/EN 60947-2
Module width 4 modules
Width 72 mm
Height 91 mm
Installation depth 75 mm
Weight approx. 428 g

Frequently Asked Questions

What is the ABB S403M-C16NP used for?

The ABB S403M-C16NP is a 3P+N miniature circuit breaker with protected neutral designed to protect three-phase-plus-neutral electrical circuits against overload and short-circuit currents.

What is the current rating of the S403M-C16NP?

The S403M-C16NP has a rated current of 16 A.

What does the Type C tripping characteristic mean?

The Type C characteristic is suitable for appropriately designed circuits that can experience moderate transient inrush currents during normal operation while still requiring dependable overload and short-circuit protection.

What is the breaking capacity of the ABB S403M-C16NP?

The S403M-C16NP has a rated short-circuit capacity (Icn) of 10 kA at 230 / 400 V AC and a rated ultimate short-circuit breaking capacity (Icu) of 25 kA at 230 / 400 V AC.

Does the ABB S403M-C16NP have a protected neutral?

Yes. The S403M-C16NP has four protected poles, with the neutral protected at 100% of the nominal pole-conductor value. It is designed for integration with compatible ABB SMISSLINE TP assemblies.

Trusted Circuit Protection from ABB

ABB SMISSLINE TP miniature circuit breakers combine dependable overload and short-circuit protection with a modular plug-in architecture designed for efficient commercial and industrial electrical distribution.