2CCS572001R1328 ABB S402M-UCZ32 32 A 2-Pole Type Z DC Miniature Circuit Breaker

2CCS572001R1328 ABB S402M-UCZ32 32 A 2-Pole Type Z DC Miniature Circuit Breaker

ABB S402M-UCZ32 is a 32 A 2-pole UC-Z Type Z DC miniature circuit breaker for the SMISSLINE TP plug-in system, providing sensitive overload and short-circuit protection for DC circuits with two-pole operation up to 440 V.

SKU: 2CCS572001R1328Alt SKU: S402MUCZ32MPN: 2CCS572001R1328
Price
List Price £205.11 ex VAT
Your Price (ex VAT) Save 35%
£133.32 35% OFF
You save £71.79 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £133.32
Trade pricing is personalised to your account

Manufacturer Lead Time

£133.32

Why Choose the ABB S402M-UCZ32 DC Miniature Circuit Breaker?

The ABB S402M-UCZ32 is a specialised 2-pole DC miniature circuit breaker (MCB) designed to provide reliable overload and short-circuit protection in direct-current electrical systems. Part of the ABB S400M-UC / SMISSLINE TP plug-in system, it combines dedicated DC circuit protection with convenient plug-in installation for compatible industrial and commercial distribution assemblies.

This circuit breaker has a rated current of 32 A and a UC-Z / Type Z tripping characteristic. The sensitive Type Z characteristic is particularly suited to appropriate electronic, control and instrumentation circuits where rapid magnetic tripping is required to protect connected equipment against excessive fault currents.

The S402M-UCZ32 supports two-pole operation up to 440 V DC and provides a rated ultimate short-circuit breaking capacity of 20 kA at 220 V DC. Its compact 36 × 91 × 75 mm enclosure, IP20 protection and SMISSLINE TP plug-in construction make it a practical protection device for professional DC control, automation and distribution systems.

Key Advantages

  • Specialised 2-pole miniature circuit breaker for DC applications.
  • 32 A rated current for DC control, auxiliary and distribution circuits.
  • UC-Z / Type Z tripping characteristic for sensitive circuit protection.
  • Supports two-pole operation up to 440 V DC.
  • High short-circuit interruption capability for demanding DC installations.
  • Designed for the ABB SMISSLINE TP plug-in system.
  • Two-pole construction provides coordinated protection for DC circuits.
  • Compact 2-module design helps optimise distribution-board space.

Key Features

  • ABB S400M-UC / SMISSLINE TP series.
  • 32 A rated current.
  • 2-pole configuration.
  • UC-Z / Type Z tripping characteristic.
  • 440 V DC maximum two-pole operating voltage.
  • 20 kA rated ultimate short-circuit breaking capacity Icu at 220 V DC.
  • IP20 degree of protection.
  • Plug-in SMISSLINE TP mounting for modular distribution systems.
  • Screw terminals for conductor connection.
  • Connection capacity up to 35 mm².
  • Electrical endurance of up to 10,000 operating cycles.
  • Compliant with IEC/EN 60947-2.

Sensitive Protection for DC Electrical Systems

DC miniature circuit breakers such as the ABB S402M-UCZ32 automatically disconnect a circuit when excessive current occurs because of an overload or short circuit. Dedicated DC switching capability is important because direct-current arcs do not naturally pass through the regular zero-current points present in AC systems, requiring suitable protective-device construction and connection arrangements for dependable fault interruption.

The Type Z characteristic provides sensitive magnetic protection and is particularly useful for appropriate electronic, control and instrumentation circuits. Combined with ABB's SMISSLINE TP plug-in architecture, the S402M-UCZ32 provides dependable DC circuit protection while supporting efficient installation, replacement and maintenance within compatible modular distribution systems.

Typical Applications

  • Industrial DC distribution systems.
  • DC control and auxiliary circuits.
  • Sensitive electronic equipment circuits.
  • Industrial instrumentation and monitoring systems.
  • Machine control panels and automation equipment.
  • Battery-backed control and distribution circuits.
  • DC power-supply output circuits.
  • OEM machinery incorporating DC electrical systems.
  • ABB SMISSLINE TP modular distribution assemblies.

Technical Specifications

Product group SMISSLINE Plug-in System
Range SMISSLINE TP
Series S400M-UC
ABB order code 2CCS572001R1328
Product type DC miniature circuit breaker (MCB)
Rated current 32 A
Number of poles 2
Tripping characteristic UC-Z / Type Z
Maximum two-pole DC operating voltage 440 V DC
Rated ultimate short-circuit breaking capacity Icu 20 kA at 220 V DC
Short-circuit breaking capacity 10 kA
Protection rating IP20
Terminal type Screw
Mounting type Plug-in SMISSLINE TP
Module width 2 modules
Connection conductor cross-section 0.75–35 mm²
Electrical endurance 10,000 cycles
Operating ambient temperature -25 to +55 °C
Width 36 mm
Height 91 mm
Depth 75 mm
Dimensions (W × H × D) 36 × 91 × 75 mm
Weight approx. 221 g
EAN 7612270110384
Standard IEC/EN 60947-2

Frequently Asked Questions

What is the ABB S402M-UCZ32 used for?

The ABB S402M-UCZ32 is a 2-pole DC miniature circuit breaker designed to protect direct-current circuits against overload and short-circuit currents in industrial control, automation, instrumentation and distribution applications.

What is the current rating of the S402M-UCZ32?

The S402M-UCZ32 has a rated current of 32 A.

What does the Type Z tripping characteristic mean?

The UC-Z / Type Z characteristic provides sensitive magnetic tripping and is suited to appropriate circuits where electronic, control or instrumentation equipment requires rapid protection against excessive fault currents.

What DC voltage can the ABB S402M-UCZ32 handle?

The two-pole S402M-UCZ32 supports operation up to 440 V DC when connected in accordance with ABB's specified two-pole DC connection arrangement.

What is the breaking capacity of the ABB S402M-UCZ32?

The S402M-UCZ32 has a rated ultimate short-circuit breaking capacity Icu of 20 kA at 220 V DC, with the applicable breaking capacity depending on the operating voltage and connection arrangement.

Trusted ABB DC Circuit Protection

ABB S400M-UC miniature circuit breakers provide dedicated protection for DC electrical systems, combining sensitive overcurrent protection with the flexibility and convenience of the SMISSLINE TP modular plug-in distribution platform.