2CCS572001R1164 ABB S402M-UCC16 DC Miniature Circuit Breaker 16 A 2P Type C

2CCS572001R1164 ABB S402M-UCC16 DC Miniature Circuit Breaker 16 A 2P Type C

ABB S402M-UCC16 is a 16 A 2-pole Type C DC miniature circuit breaker rated at 440 V DC with 10 kA short-circuit breaking capacity for overload and short-circuit protection in SMISSLINE TP plug-in distribution systems.

SKU: 2CCS572001R1164Alt SKU: S402MUCC16MPN: 2CCS572001R1164
Price
List Price £140.16 ex VAT
Your Price (ex VAT) Save 35%
£91.10 35% OFF
You save £49.06 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £91.10
Trade pricing is personalised to your account

Manufacturer Lead Time

£91.10

Why Choose the ABB S402M-UCC16 DC Miniature Circuit Breaker?

The ABB S402M-UCC16 is a specialised 2-pole miniature circuit breaker (MCB) designed to provide reliable overload and short-circuit protection in DC electrical distribution systems. As part of the ABB S400M UC / SMISSLINE TP series, it combines a 16 A rated current, Type C tripping characteristic and convenient plug-in installation.

Designed for industrial and commercial circuit protection, the S402M-UCC16 uses a Type C / UC-C characteristic suitable for general-purpose loads and circuits where moderate starting or inrush currents may occur. Its two protected poles and SMISSLINE plug-in construction support efficient integration into compatible modular distribution assemblies.

With a 16 A rated current, 2-pole configuration and rated operating voltage of 440 V DC, the S402M-UCC16 is suitable for control, automation and DC power distribution circuits. It provides a 10 kA short-circuit breaking capacity and an ultimate short-circuit breaking capacity of 25 kA at 440 V DC for robust protection in demanding installations.

Key Advantages

  • Reliable 2-pole miniature circuit breaker for DC circuit protection.
  • 16 A rated current for control, auxiliary and distribution circuits.
  • Type C / UC-C tripping characteristic suitable for loads with moderate inrush currents.
  • Rated operating voltage of 440 V DC.
  • 10 kA short-circuit breaking capacity.
  • 25 kA ultimate short-circuit breaking capacity at 440 V DC.
  • Plug-in construction designed for the ABB SMISSLINE TP system.

Key Features

  • ABB S400M UC / SMISSLINE TP series.
  • 16 A rated current.
  • 2 protected poles.
  • Type C / UC-C tripping characteristic.
  • 440 V DC rated operating voltage.
  • 10 kA rated short-circuit breaking capacity.
  • 4 kV rated impulse withstand voltage.
  • IP20 degree of protection.
  • Compact two-module construction for compatible SMISSLINE TP distribution systems.

Reliable Protection for DC Circuits

DC miniature circuit breakers such as the ABB S402M-UCC16 protect electrical conductors and connected equipment by automatically interrupting current when overload or short-circuit conditions occur. Correctly specified DC switching capability is particularly important because direct current behaves differently from alternating current when a circuit is interrupted.

The ABB S400M UC range extends the SMISSLINE TP platform to DC circuit protection applications. The S402M-UCC16 combines a Type C characteristic, two protected poles and robust short-circuit performance with ABB's modular plug-in installation concept.

Typical Applications

  • Industrial DC distribution systems.
  • Automation and machine control circuits.
  • DC control and auxiliary power circuits.
  • Industrial electrical distribution cabinets.
  • Equipment with moderate starting or inrush currents.
  • Critical-power DC distribution systems.
  • ABB SMISSLINE TP modular distribution assemblies.

Technical Specifications

Series S400M UC / SMISSLINE TP
ABB order code 2CCS572001R1164
EAN 7612270110018
Product type DC miniature circuit breaker (MCB)
Rated current 16 A
Number of poles 2
Number of protected poles 2
Tripping characteristic Type C / UC-C
Rated operating voltage 440 V DC
Short-circuit breaking capacity 10 kA
Rated ultimate short-circuit breaking capacity (Icu) 25 kA at 440 V DC
Rated impulse withstand voltage 4 kV
Protection rating IP20
Operating temperature -25 to +55 °C
Mounting type SMISSLINE TP plug-in system
Width 36 mm
Height 91 mm
Depth 75 mm
Width in modules 2
Weight approx. 221 g
Standard IEC/EN 60947-2

Frequently Asked Questions

What is the ABB S402M-UCC16 used for?

The S402M-UCC16 is a 2-pole miniature circuit breaker designed to protect compatible DC electrical circuits against overloads and short circuits.

What is the current rating of the S402M-UCC16?

The ABB S402M-UCC16 has a rated current of 16 A.

What tripping characteristic does the S402M-UCC16 use?

The breaker uses a Type C / UC-C tripping characteristic, making it suitable for general-purpose circuits and appropriate loads with moderate starting or inrush currents.

What DC voltage is the ABB S402M-UCC16 rated for?

The S402M-UCC16 has a rated operating voltage of 440 V DC in its specified two-pole configuration.

How is the ABB S402M-UCC16 installed?

The breaker is designed for plug-in installation within the ABB SMISSLINE TP system, enabling efficient integration into compatible modular electrical distribution assemblies.

Trusted ABB DC Circuit Protection

ABB S400M UC miniature circuit breakers provide dependable overload and short-circuit protection for DC applications while combining robust electrical performance with the modular advantages of the SMISSLINE TP plug-in distribution system.