ABB S402M-UCC16 is a 16 A 2-pole Type C DC miniature circuit breaker rated at 440 V DC with 10 kA short-circuit breaking capacity for overload and short-circuit protection in SMISSLINE TP plug-in distribution systems.
£91.10
The ABB S402M-UCC16 is a specialised 2-pole miniature circuit breaker (MCB) designed to provide reliable overload and short-circuit protection in DC electrical distribution systems. As part of the ABB S400M UC / SMISSLINE TP series, it combines a 16 A rated current, Type C tripping characteristic and convenient plug-in installation.
Designed for industrial and commercial circuit protection, the S402M-UCC16 uses a Type C / UC-C characteristic suitable for general-purpose loads and circuits where moderate starting or inrush currents may occur. Its two protected poles and SMISSLINE plug-in construction support efficient integration into compatible modular distribution assemblies.
With a 16 A rated current, 2-pole configuration and rated operating voltage of 440 V DC, the S402M-UCC16 is suitable for control, automation and DC power distribution circuits. It provides a 10 kA short-circuit breaking capacity and an ultimate short-circuit breaking capacity of 25 kA at 440 V DC for robust protection in demanding installations.
DC miniature circuit breakers such as the ABB S402M-UCC16 protect electrical conductors and connected equipment by automatically interrupting current when overload or short-circuit conditions occur. Correctly specified DC switching capability is particularly important because direct current behaves differently from alternating current when a circuit is interrupted.
The ABB S400M UC range extends the SMISSLINE TP platform to DC circuit protection applications. The S402M-UCC16 combines a Type C characteristic, two protected poles and robust short-circuit performance with ABB's modular plug-in installation concept.
| Series | S400M UC / SMISSLINE TP |
|---|---|
| ABB order code | 2CCS572001R1164 |
| EAN | 7612270110018 |
| Product type | DC miniature circuit breaker (MCB) |
| Rated current | 16 A |
| Number of poles | 2 |
| Number of protected poles | 2 |
| Tripping characteristic | Type C / UC-C |
| Rated operating voltage | 440 V DC |
| Short-circuit breaking capacity | 10 kA |
| Rated ultimate short-circuit breaking capacity (Icu) | 25 kA at 440 V DC |
| Rated impulse withstand voltage | 4 kV |
| Protection rating | IP20 |
| Operating temperature | -25 to +55 °C |
| Mounting type | SMISSLINE TP plug-in system |
| Width | 36 mm |
| Height | 91 mm |
| Depth | 75 mm |
| Width in modules | 2 |
| Weight | approx. 221 g |
| Standard | IEC/EN 60947-2 |
The S402M-UCC16 is a 2-pole miniature circuit breaker designed to protect compatible DC electrical circuits against overloads and short circuits.
The ABB S402M-UCC16 has a rated current of 16 A.
The breaker uses a Type C / UC-C tripping characteristic, making it suitable for general-purpose circuits and appropriate loads with moderate starting or inrush currents.
The S402M-UCC16 has a rated operating voltage of 440 V DC in its specified two-pole configuration.
The breaker is designed for plug-in installation within the ABB SMISSLINE TP system, enabling efficient integration into compatible modular electrical distribution assemblies.
ABB S400M UC miniature circuit breakers provide dependable overload and short-circuit protection for DC applications while combining robust electrical performance with the modular advantages of the SMISSLINE TP plug-in distribution system.