2CCS572001R1068 ABB S402M-UCZ6 6 A 2-Pole Type Z DC Miniature Circuit Breaker

2CCS572001R1068 ABB S402M-UCZ6 6 A 2-Pole Type Z DC Miniature Circuit Breaker

ABB S402M-UCZ6 is a 6 A 2-pole UC-Z Type Z DC miniature circuit breaker for the SMISSLINE TP plug-in system, designed for sensitive overload and short-circuit protection in DC circuits up to 440 V.

SKU: 2CCS572001R1068Alt SKU: S402MUCZ6MPN: 2CCS572001R1068
Price
List Price £160.07 ex VAT
Your Price (ex VAT) Save 35%
£104.05 35% OFF
You save £56.02 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £104.05
Trade pricing is personalised to your account

Manufacturer Lead Time

£104.05

Why Choose the ABB S402M-UCZ6 DC Miniature Circuit Breaker?

The ABB S402M-UCZ6 is a specialised 2-pole DC miniature circuit breaker (MCB) designed to protect cables and electrical circuits against overload and short-circuit currents. As part of the ABB S400M UC / SMISSLINE TP plug-in system, it combines dedicated DC circuit protection with convenient plug-in installation for industrial and commercial distribution systems.

This circuit breaker has a rated current of 6 A and a UC-Z / Type Z tripping characteristic. The sensitive Type Z characteristic is suited to applications where rapid magnetic tripping is required to protect sensitive equipment, control circuits and electronic loads against excessive fault currents.

The S402M-UCZ6 is designed for two-pole operation at up to 440 V DC and provides a rated ultimate short-circuit breaking capacity of 25 kA at 440 V DC. Its compact 36 × 91 × 75 mm enclosure, IP20 terminals and SMISSLINE plug-in connection make it a practical protection device for professional DC control and distribution installations.

Key Advantages

  • Specialised 2-pole miniature circuit breaker for DC applications.
  • 6 A rated current for control, auxiliary and distribution circuits.
  • UC-Z / Type Z tripping characteristic for sensitive circuit protection.
  • Suitable for two-pole operation up to 440 V DC.
  • 25 kA ultimate short-circuit breaking capacity at 440 V DC.
  • Designed for the ABB SMISSLINE TP plug-in system.
  • Two protected poles provide coordinated protection of DC conductors.
  • Compact 2-module design helps optimise distribution-board space.

Key Features

  • ABB S400M UC / SMISSLINE TP series.
  • 6 A rated current.
  • 2-pole configuration with two protected poles.
  • UC-Z / Type Z tripping characteristic.
  • 440 V DC rated operational voltage in two-pole configuration.
  • 25 kA rated ultimate short-circuit breaking capacity Icu at 440 V DC.
  • 440 V rated insulation voltage.
  • 4 kV rated impulse withstand voltage.
  • IP20 degree of protection.
  • Plug-in SMISSLINE TP mounting for modular distribution systems.
  • Compliant with IEC/EN 60947-2.
  • Compact 36 × 91 × 75 mm enclosure.

Sensitive Protection for DC Electrical Systems

DC miniature circuit breakers such as the ABB S402M-UCZ6 automatically disconnect a circuit when excessive current occurs because of an overload or short circuit. Dedicated DC switching capability is particularly important because direct-current arcs do not naturally pass through the regular zero-current points present in AC systems, requiring suitable circuit-breaker design for dependable interruption.

The Type Z characteristic provides sensitive magnetic protection and is particularly useful for appropriate electronic, control and instrumentation circuits. Combined with ABB's SMISSLINE TP plug-in architecture, the S402M-UCZ6 provides high-performance DC protection while supporting efficient installation, replacement and maintenance in compatible modular distribution systems.

Typical Applications

  • Industrial DC distribution systems.
  • DC control and auxiliary circuits.
  • Sensitive electronic equipment circuits.
  • Industrial instrumentation and monitoring systems.
  • Machine control panels and automation equipment.
  • Battery-backed control and distribution circuits.
  • DC power-supply output circuits.
  • OEM machinery with DC electrical systems.
  • ABB SMISSLINE TP modular distribution assemblies.

Technical Specifications

Product group SMISSLINE Plug-in System
Range SMISSLINE TP
Series S400M UC
ABB order code 2CCS572001R1068
Product type DC miniature circuit breaker (MCB)
Rated current 6 A
Number of poles 2
Number of protected poles 2
Tripping characteristic UC-Z / Type Z
Rated operational voltage 440 V DC
Rated insulation voltage 440 V
Rated impulse withstand voltage 4 kV
Rated ultimate short-circuit breaking capacity Icu 25 kA at 440 V DC
Short-circuit breaking capacity 10 kA
Protection rating IP20
Energy limiting class 3
Overvoltage category III
Mounting type Plug-in SMISSLINE TP
Module width 2 modules
Connectable conductor cross-section up to 35 mm²
Operating ambient temperature -25 to +55 °C
Dimensions (W × H × D) 36 × 91 × 75 mm
Weight approx. 221 g
EAN 7612270110315
Standard IEC/EN 60947-2

Frequently Asked Questions

What is the ABB S402M-UCZ6 used for?

The ABB S402M-UCZ6 is a 2-pole DC miniature circuit breaker designed to protect direct-current circuits against overload and short-circuit currents, including control, automation, instrumentation and sensitive equipment applications.

What is the current rating of the S402M-UCZ6?

The S402M-UCZ6 has a rated current of 6 A.

What does the Type Z tripping characteristic mean?

The UC-Z / Type Z characteristic provides sensitive magnetic tripping and is suited to appropriate circuits where connected electronic or control equipment requires rapid protection against excessive fault currents.

What DC voltage can the ABB S402M-UCZ6 handle?

The two-pole S402M-UCZ6 is designed for operation up to 440 V DC when connected in accordance with ABB's specified DC connection arrangement.

What is the breaking capacity of the ABB S402M-UCZ6?

The S402M-UCZ6 has a rated ultimate short-circuit breaking capacity Icu of 25 kA at 440 V DC to IEC/EN 60947-2.

Trusted ABB DC Circuit Protection

ABB S400M UC miniature circuit breakers provide dedicated protection for DC electrical systems, combining sensitive overcurrent protection with the flexibility and convenience of the SMISSLINE TP modular plug-in distribution platform.