Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB S402M-UCC4 is a 4 A 2-pole Type C miniature circuit breaker rated up to 440 V DC and designed for overload and short-circuit protection in SMISSLINE TP plug-in distribution systems.
£111.12
The ABB S402M-UCC4 is a specialised 2-pole miniature circuit breaker (MCB) designed to provide reliable overload and short-circuit protection in DC and AC electrical distribution systems. As part of the ABB S400M UC / SMISSLINE TP series, it combines a 4 A rated current, Type C tripping characteristic and plug-in installation for commercial, industrial and critical-power applications.
Designed for circuits requiring dependable overcurrent protection, the S402M-UCC4 uses a Type C characteristic suitable for general-purpose loads with moderate starting or inrush currents. Its two protected poles and SMISSLINE TP plug-in construction provide efficient integration into compatible modular distribution assemblies.
With a 4 A rated current, 2-pole configuration and rated operating voltage up to 440 V DC, the S402M-UCC4 is suitable for control, automation and DC distribution circuits. Its DC ultimate short-circuit breaking capacity reaches 25 kA at 440 V DC, providing robust fault protection in demanding installations.
Miniature circuit breakers such as the ABB S402M-UCC4 protect conductors and connected equipment by automatically interrupting current when overload or short-circuit conditions occur. Correct DC switching capability is particularly important because direct current does not naturally pass through a zero-current point during each cycle in the same way as alternating current.
The S400M UC range extends ABB's SMISSLINE TP platform with miniature circuit breakers engineered for flexible AC and DC applications. The S402M-UCC4 combines a Type C characteristic, two-pole configuration and high DC short-circuit capability with the convenience of ABB's modular plug-in distribution system.
| Series | S400M UC / SMISSLINE TP |
|---|---|
| ABB order code | 2CCS572001R1044 |
| Product type | Miniature circuit breaker (MCB) |
| Rated current | 4 A |
| Number of poles | 2 |
| Number of protected poles | 2 |
| Tripping characteristic | Type C / UC-C |
| Rated operating voltage | 440 V DC |
| Rated ultimate short-circuit breaking capacity (Icu) | 25 kA at 440 V DC |
| Rated impulse withstand voltage | 4 kV |
| Protection rating | IP20 |
| Operating temperature | -25 to +55 °C |
| Mounting type | SMISSLINE TP plug-in system |
| Width | 36 mm |
| Height | 91 mm |
| Depth | 75 mm |
| Width in modules | 2 |
| Weight | approx. 290 g |
| Standard | IEC/EN 60947-2 |
The S402M-UCC4 is a 2-pole miniature circuit breaker designed to protect compatible DC and AC electrical circuits against overloads and short circuits.
The ABB S402M-UCC4 has a rated current of 4 A.
The breaker uses a Type C / UC-C tripping characteristic, making it suitable for general-purpose circuits and appropriate loads with moderate starting or inrush currents.
The S402M-UCC4 is rated for operation up to 440 V DC when used in its specified two-pole configuration.
The breaker is designed for plug-in installation within the ABB SMISSLINE TP system, allowing efficient integration into compatible modular electrical distribution assemblies.
ABB S400M UC miniature circuit breakers provide dependable overload and short-circuit protection for AC and DC applications while combining high breaking performance with the modular advantages of the SMISSLINE TP plug-in distribution system.