Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB S402M-UCC3 is a 3 A 2-pole UC-C Type C DC miniature circuit breaker for the SMISSLINE TP plug-in system, designed for reliable overload and short-circuit protection in DC circuits up to 440 V.
£111.12
The ABB S402M-UCC3 is a specialised 2-pole DC miniature circuit breaker (MCB) designed to provide reliable overload and short-circuit protection in direct-current electrical systems. As part of the ABB S400M / SMISSLINE TP plug-in system, it combines dedicated DC circuit protection with convenient plug-in installation for compatible modular distribution assemblies.
This circuit breaker has a rated current of 3 A and a UC-C / Type C tripping characteristic, making it suitable for low-current DC control, auxiliary and distribution circuits. Its two protected poles enable both conductors to be switched and protected, while the SMISSLINE plug-in architecture helps simplify installation, replacement and maintenance in professional electrical systems.
The S402M-UCC3 is rated for operation up to 440 V DC when connected as a two-pole device and provides a rated ultimate short-circuit breaking capacity of up to 25 kA at 440 V DC to IEC/EN 60947-2. With IP20 protection, a compact two-module format and robust ABB construction, it is well suited to industrial DC distribution and control applications.
DC miniature circuit breakers such as the ABB S402M-UCC3 are specifically designed to interrupt direct-current faults safely. Because a DC arc does not naturally pass through a zero-current point in the same way as an AC waveform, dedicated DC circuit-breaker construction and correct polarity and series connection of the poles are important for dependable fault interruption.
The two-pole S402M-UCC3 supports applications up to 440 V DC when connected according to ABB's specified DC connection arrangement. Combined with the SMISSLINE TP plug-in platform, it provides a compact and maintainable protection solution for DC control, automation and distribution systems.
| Product group | SMISSLINE Plug-in System |
|---|---|
| Range | SMISSLINE TP |
| Series | S400M |
| ABB order code | 2CCS572001R1034 |
| Product type | DC miniature circuit breaker (MCB) |
| Rated current | 3 A |
| Number of poles | 2 |
| Number of protected poles | 2 |
| Tripping characteristic | UC-C / Type C |
| Rated operational voltage | 440 V DC |
| Rated insulation voltage | 440 V |
| Rated impulse withstand voltage | 4 kV |
| Rated ultimate short-circuit breaking capacity Icu | 25 kA at 440 V DC |
| Short-circuit breaking capacity | 10 kA |
| Protection rating | IP20 |
| Energy limiting class | 3 |
| Overvoltage category | III |
| Mounting type | Plug-in SMISSLINE TP |
| Module width | 2 modules |
| Width | 36 mm |
| Height | 91 mm |
| Depth | 75 mm |
| Dimensions (W × H × D) | 36 × 91 × 75 mm |
| Operating ambient temperature | -25 to +55 °C |
| Weight | approx. 0.221 kg |
| EAN | 7612270109951 |
| Standard | IEC/EN 60947-2 |
The ABB S402M-UCC3 is a 2-pole DC miniature circuit breaker designed to protect direct-current electrical circuits against overload and short-circuit currents in industrial control, automation and distribution applications.
The S402M-UCC3 has a rated current of 3 A.
The two-pole S402M-UCC3 is designed for operation up to 440 V DC when its poles are connected in accordance with ABB's specified DC connection arrangement.
The S402M-UCC3 has a rated ultimate short-circuit breaking capacity Icu of up to 25 kA at 440 V DC to IEC/EN 60947-2.
The breaker is designed for plug-in installation within compatible ABB SMISSLINE TP distribution systems, helping simplify protective-device installation, replacement and maintenance.
ABB SMISSLINE TP S400M-UC miniature circuit breakers provide dedicated protection for DC electrical systems, combining high-performance fault interruption with the flexibility and convenience of ABB's modular plug-in distribution platform.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.