2CCS572001R0537 ABB S402M-K32 MCB 10kA 2P Type K 32A

2CCS572001R0537 ABB S402M-K32 MCB 10kA 2P Type K 32A

ABB S402M-K32 is a 32 A Type K 2-pole miniature circuit breaker with 10 kA short-circuit breaking capacity, designed for reliable overload and short-circuit protection in SMISSLINE TP plug-in electrical distribution systems.

SKU: 2CCS572001R0537Alt SKU: S402MK32MPN: 2CCS572001R0537
Price
List Price £98.05 ex VAT
Your Price (ex VAT) Save 35%
£63.73 35% OFF
You save £34.32 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £63.73
Trade pricing is personalised to your account

Manufacturer Lead Time

£63.73

Why Choose the ABB S402M-K32 Miniature Circuit Breaker?

The ABB S402M-K32 is a high-performance 2-pole miniature circuit breaker (MCB) designed to provide reliable overload and short-circuit protection in industrial and commercial electrical distribution systems. Part of the ABB S400M range for the SMISSLINE TP plug-in system, it combines a 32 A rated current, Type K tripping characteristic and 10 kA rated short-circuit breaking capacity.

The S402M-K32 is a current-limiting circuit breaker with two complementary tripping mechanisms: a delayed thermal release for overload protection and an electromagnetic release for short-circuit protection. Its Type K characteristic is particularly suitable for circuits supplying motors and other inductive loads where elevated starting currents can occur during normal operation.

Designed specifically for ABB's SMISSLINE TP distribution platform, the S402M-K32 provides convenient plug-in installation within compatible assemblies. With 2 protected poles, a 240 V AC rated voltage, IP20 protection and compact 36 × 91 × 75 mm dimensions, it provides dependable circuit protection for machinery, control panels and industrial distribution applications.

Key Advantages

  • 32 A rated current for dependable protection of compatible electrical circuits.
  • 2-pole configuration with both poles protected.
  • Type K tripping characteristic suited to motors and other inductive loads with elevated starting currents.
  • 10 kA rated short-circuit breaking capacity.
  • Purpose-designed for the ABB SMISSLINE TP plug-in system.
  • Separate thermal and electromagnetic tripping mechanisms provide overload and short-circuit protection.

Key Features

  • ABB S400M series miniature circuit breaker.
  • 32 A nominal current rating.
  • Type K tripping characteristic.
  • 2 protected poles.
  • 240 V AC rated voltage.
  • 10 kA short-circuit breaking capacity.
  • 15 kA Icu breaking capacity to IEC 60947-2 at 230/400 V AC.
  • 440 V rated insulation voltage.
  • 4 kV rated impulse withstand voltage.
  • IP20 protection rating.
  • SMISSLINE plug-in mounting for compatible distribution systems.

Reliable Protection for Motors and Inductive Loads

Miniature circuit breakers such as the ABB S402M-K32 protect electrical circuits against excessive current caused by overloads and short circuits. The delayed thermal tripping mechanism responds to sustained overload conditions, while the electromagnetic mechanism provides rapid disconnection when a short-circuit fault occurs.

The Type K characteristic is particularly useful for circuits supplying motors and other inductive equipment where starting current can be substantially higher than normal operating current. Combined with ABB SMISSLINE TP plug-in technology, the S402M-K32 provides dependable protection while supporting efficient installation and maintenance within compatible modular distribution systems.

Typical Applications

  • ABB SMISSLINE TP electrical distribution systems.
  • Motor and inductive-load circuit protection.
  • Industrial control panels and switchboards.
  • Transformers and electromagnetic equipment.
  • Machine-building and automation power distribution.
  • Commercial, industrial and critical-power installations.

Technical Specifications

Series S400M / SMISSLINE TP
ABB order code 2CCS572001R0537
EAN 7612270102501
Product type Miniature circuit breaker (MCB)
Number of poles 2
Number of protected poles 2
Rated current 32 A
Tripping characteristic Type K
Rated voltage 240 V AC
Rated short-circuit breaking capacity 10 kA
Ultimate short-circuit breaking capacity (Icu) 15 kA at 230/400 V AC
Frequency 50–60 Hz
Rated insulation voltage (Ui) 440 V
Rated impulse withstand voltage (Uimp) 4 kV
Energy limiting class 3
Overvoltage category III
Pollution degree 3
Protection rating IP20
Power loss 6.2 W
Electrical endurance 10,000 cycles
Mounting type SMISSLINE plug-in
Width 2 modules / 36 mm
Dimensions (W × H × D) 36 × 91 × 75 mm
Weight approx. 221 g
Operating temperature −25 to +60 °C
Connectable stranded conductor 0.75–25 mm²
Connectable solid conductor 0.75–35 mm²
Standard IEC/EN 60947-2

Frequently Asked Questions

What is the ABB S402M-K32 used for?

The ABB S402M-K32 is a 2-pole miniature circuit breaker designed to protect electrical circuits against overload and short-circuit currents in compatible ABB SMISSLINE TP distribution systems.

What is the current rating of the S402M-K32?

The S402M-K32 has a rated current of 32 A.

What does the Type K characteristic mean?

The Type K tripping characteristic accommodates elevated starting currents, making it particularly suitable for appropriate motor and other inductive-load circuits.

What is the breaking capacity of the ABB S402M-K32?

The S402M-K32 has a rated short-circuit breaking capacity of 10 kA and an ultimate short-circuit breaking capacity of 15 kA at 230/400 V AC to IEC 60947-2.

How is the S402M-K32 installed?

The circuit breaker is designed for plug-in installation in compatible ABB SMISSLINE TP systems, allowing efficient integration into modular electrical distribution assemblies.

Trusted ABB Circuit Protection