Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB S402M-B16 is a 16 A Type B 2-pole miniature circuit breaker with 10 kA breaking capacity, designed for reliable overload and short-circuit protection in SMISSLINE plug-in distribution systems.
£44.11
The ABB S402M-B16 is a high-performance 2-pole miniature circuit breaker (MCB) designed to provide reliable overload and short-circuit protection in electrical distribution systems. Part of the ABB S400M range for the SMISSLINE TP plug-in system, this circuit breaker combines a 16 A rated current, Type B tripping characteristic and 10 kA rated short-circuit breaking capacity.
Designed for ABB's SMISSLINE plug-in distribution platform, the S402M-B16 enables efficient installation and replacement within compatible SMISSLINE assemblies. Its thermal and electromagnetic tripping mechanisms provide protection against sustained overloads and short-circuit faults, helping safeguard cables, equipment and downstream circuits.
With two protected poles, a rated voltage of 400 V AC and compliance with IEC/EN 60898-1, the S402M-B16 is suitable for commercial, industrial and infrastructure distribution applications where dependable circuit protection and convenient plug-in installation are required.
Miniature circuit breakers such as the ABB S402M-B16 protect electrical circuits against excessive current caused by overloads and short circuits. The thermal trip responds to sustained overload conditions, while the electromagnetic trip provides rapid operation when high fault currents occur.
The ABB SMISSLINE system is designed around plug-in distribution technology, allowing compatible protective devices to be integrated efficiently into modular electrical distribution assemblies. The S402M-B16 combines this installation concept with Type B protection, two-pole switching and a 10 kA breaking capacity for dependable protection in demanding electrical installations.
| Series | S400M / SMISSLINE TP |
|---|---|
| ABB order code | 2CCS572001R0165 |
| Product type | Miniature circuit breaker (MCB) |
| Number of poles | 2 |
| Rated current | 16 A |
| Tripping characteristic | Type B |
| Rated voltage | 400 V AC |
| Rated short-circuit breaking capacity | 10 kA |
| Frequency | 50–60 Hz |
| Rated insulation voltage (Ui) | 440 V |
| Rated impulse withstand voltage (Uimp) | 4 kV |
| Protection rating | IP20 |
| Energy limiting class | 3 |
| Mounting type | SMISSLINE plug-in |
| Width | 2 modules / 36 mm |
| Dimensions (W × H × D) | 36 × 91 × 75 mm |
| Operating temperature | −25 to +60 °C |
| Standard | IEC/EN 60898-1 |
| EAN | 7612270102020 |
The ABB S402M-B16 is a 2-pole miniature circuit breaker used to protect electrical circuits against overload and short-circuit currents in compatible ABB SMISSLINE distribution systems.
The S402M-B16 has a rated current of 16 A.
The Type B tripping characteristic is intended for circuits with relatively low inrush currents, providing rapid magnetic operation when sufficiently high short-circuit current is detected.
The S402M-B16 has a rated short-circuit breaking capacity of 10 kA to IEC/EN 60898-1.
The circuit breaker is designed for plug-in installation in compatible ABB SMISSLINE systems, providing convenient integration into modular electrical distribution assemblies.
ABB SMISSLINE protective devices combine modular plug-in distribution technology with dependable circuit protection, supporting efficient and reliable electrical distribution in commercial and industrial installations.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.