ABB S402M-C8 is an 8 A Type C 2-pole miniature circuit breaker with 10 kA rated short-circuit breaking capacity and SMISSLINE TP plug-in mounting for commercial and industrial electrical distribution systems.
£62.41
The ABB S402M-C8 is a compact, current-limiting miniature circuit breaker (MCB) designed to provide reliable overload and short-circuit protection in commercial and industrial electrical distribution systems. As part of the ABB SMISSLINE TP S400M series, it combines dependable two-pole protection with the modular plug-in installation advantages of the SMISSLINE system.
This circuit breaker uses thermal and electromagnetic tripping to protect wiring and connected equipment against overcurrents. Its Type C tripping characteristic is suitable for general-purpose circuits and compatible electrical loads with moderate starting or inrush currents.
With a rated current of 8 A, a rated operational voltage of 415 V AC and a 10 kA rated short-circuit breaking capacity, the S402M-C8 provides dependable two-pole circuit protection. Its SMISSLINE TP plug-in design enables straightforward integration into compatible ABB modular distribution systems.
Miniature circuit breakers such as the ABB S402M-C8 protect electrical wiring and connected equipment against excessive current. Thermal tripping responds to sustained overload conditions, while electromagnetic tripping provides rapid disconnection during short-circuit faults.
The Type C characteristic makes the S402M-C8 suitable for general-purpose circuits and compatible equipment with moderate inrush currents. Combined with ABB’s SMISSLINE TP plug-in architecture and two protected poles, it provides a practical protection solution for commercial and industrial electrical distribution applications.
| Series | SMISSLINE TP S400M |
|---|---|
| ABB order code | 2CCS572001R0084 |
| EAN | 7612270102167 |
| Product type | Miniature circuit breaker (MCB) |
| Rated current | 8 A |
| Rated operational voltage | 415 V AC |
| Trip characteristic | Type C |
| Pole configuration | 2P |
| Number of protected poles | 2 |
| Rated short-circuit breaking capacity | 10 kA |
| Ultimate short-circuit breaking capacity Icu | 25 kA at 415 V AC |
| Protection rating | IP20 |
| Applicable standards | IEC/EN 60898-1 and IEC/EN 60947-2 |
| Mounting type | Plug-in SMISSLINE TP |
| Module width | 2 modules |
| Conductor connection capacity | 0.75–35 mm² |
| Electrical endurance | 10,000 cycles |
| Operating ambient temperature | -25 to +60 °C |
| Dimensions (W × H × D) | 36 × 91 × 75 mm |
| Weight | approx. 221 g |
The S402M-C8 provides overload and short-circuit protection for compatible two-pole electrical circuits in ABB SMISSLINE TP commercial and industrial distribution systems.
The S402M-C8 has a rated current of 8 A.
The breaker uses a Type C tripping characteristic, making it suitable for general-purpose circuits and compatible loads with moderate starting or inrush currents.
The S402M-C8 has a rated short-circuit breaking capacity of 10 kA and an ultimate short-circuit breaking capacity of 25 kA at 415 V AC.
The breaker uses ABB’s SMISSLINE TP plug-in system, allowing it to be integrated into compatible modular SMISSLINE electrical distribution assemblies.
ABB SMISSLINE TP miniature circuit breakers provide dependable overload and short-circuit protection while supporting modular plug-in installation for commercial and industrial electrical distribution applications.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.