2CCS571001R1068 ABB S401M-UCZ6 AC/DC Miniature Circuit Breaker 6 A Type Z 1P

2CCS571001R1068 ABB S401M-UCZ6 AC/DC Miniature Circuit Breaker 6 A Type Z 1P

ABB S401M-UCZ6 is a 6 A single-pole Type Z AC/DC miniature circuit breaker for the SMISSLINE TP plug-in system, providing sensitive overload and short-circuit protection with an Icu of 20 kA at 220 V DC.

SKU: 2CCS571001R1068Alt SKU: S401MUCZ6MPN: 2CCS571001R1068
Price
List Price £73.35 ex VAT
Your Price (ex VAT) Save 35%
£47.68 35% OFF
You save £25.67 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £47.68
Trade pricing is personalised to your account

Manufacturer Lead Time

£47.68

Why Choose the ABB S401M-UCZ6 Miniature Circuit Breaker?

The ABB S401M-UCZ6 is a high-performance single-pole miniature circuit breaker (MCB) designed for reliable overload and short-circuit protection in AC and DC electrical circuits. As part of the ABB S400M UC range for the SMISSLINE TP plug-in system, it combines flexible AC/DC operation with a compact, pluggable design for commercial, industrial and critical-power applications.

Featuring a 6 A rated current and Type Z tripping characteristic, the S401M-UCZ6 provides sensitive overcurrent protection for circuits and equipment requiring a lower magnetic trip threshold than conventional Type B or Type C breakers. This makes it particularly useful for control, electronic, instrumentation and automation circuits where precise protection is important.

The S401M-UCZ6 is suitable for single-pole applications up to 220 V DC and provides a rated ultimate short-circuit breaking capacity of 20 kA at 220 V DC. Its compact one-module construction and SMISSLINE TP plug-in architecture enable efficient installation and replacement within compatible ABB distribution systems.

Key Advantages

  • Compact AC/DC miniature circuit breaker for overload and short-circuit protection.
  • 6 A rated current suitable for control, electronic and auxiliary circuits.
  • Type Z tripping characteristic for sensitive overcurrent protection.
  • Suitable for single-pole DC applications up to 220 V DC.
  • Rated ultimate short-circuit breaking capacity of 20 kA at 220 V DC.
  • Plug-in construction for direct integration with the ABB SMISSLINE TP system.

Key Features

  • ABB S400M UC / SMISSLINE TP series.
  • 6 A rated current.
  • Type Z tripping characteristic.
  • 1-pole protected configuration.
  • Designed for AC and DC circuit protection.
  • 220 V DC single-pole application voltage.
  • 20 kA Icu at 220 V DC.
  • IP20 degree of protection.
  • Compliant with IEC/EN 60947-2.
  • Compact one-module SMISSLINE TP plug-in construction.

Sensitive AC/DC Circuit Protection for SMISSLINE TP Systems

Miniature circuit breakers such as the ABB S401M-UCZ6 automatically interrupt the electrical supply when excessive current results from an overload or short circuit. This helps protect wiring, electronic equipment and connected devices against damaging fault currents.

The Type Z characteristic is designed for sensitive circuits requiring rapid magnetic response to comparatively low levels of overcurrent. Combined with the flexible AC/DC capabilities and plug-in architecture of the S400M UC range, the S401M-UCZ6 is well suited to modern control, automation, electronic and critical-power installations.

Typical Applications

  • DC control and auxiliary circuits.
  • Industrial automation and machine control systems.
  • Electronic equipment protection.
  • Instrumentation and measurement circuits.
  • SMISSLINE TP distribution systems.
  • Commercial, industrial and critical-power installations.

Technical Specifications

Series S400M UC / SMISSLINE TP
ABB order code 2CCS571001R1068
Product type AC/DC miniature circuit breaker (MCB)
Number of poles 1
Number of protected poles 1
Rated current 6 A
Tripping characteristic Type Z
Single-pole DC application voltage 220 V DC
Ultimate short-circuit breaking capacity (Icu) 20 kA at 220 V DC
Protection rating IP20
Operating temperature -25 to +55 °C
Mounting system SMISSLINE TP plug-in system
Width 1 module / 18 mm
Dimensions (H × W × D) approx. 91 × 18 × 75 mm
Weight approx. 110 g
Standard IEC/EN 60947-2

Frequently Asked Questions

What is the ABB S401M-UCZ6 used for?

The S401M-UCZ6 is a single-pole AC/DC miniature circuit breaker designed to protect electrical circuits against overload and short-circuit conditions within ABB SMISSLINE TP systems.

What is the current rating of the S401M-UCZ6?

The ABB S401M-UCZ6 has a rated current of 6 A.

What tripping characteristic does the S401M-UCZ6 use?

The S401M-UCZ6 uses a Type Z tripping characteristic, providing sensitive protection for electronic, control and other circuits requiring a relatively low magnetic trip threshold.

Can the ABB S401M-UCZ6 be used on DC circuits?

Yes. The S401M-UCZ6 is suitable for AC and DC applications, including single-pole operation up to 220 V DC.

What is the DC breaking capacity of the ABB S401M-UCZ6?

The S401M-UCZ6 has a rated ultimate short-circuit breaking capacity of 20 kA at 220 V DC.

Trusted ABB AC/DC Circuit Protection

ABB S400M UC miniature circuit breakers extend the SMISSLINE TP platform with flexible AC and DC circuit protection, combining high short-circuit performance with sensitive tripping characteristics and a modular plug-in architecture.