2CCS571001R1064 ABB S401M-UCC6 DC Miniature Circuit Breaker 1P Type C 6A 10kA

2CCS571001R1064 ABB S401M-UCC6 DC Miniature Circuit Breaker 1P Type C 6A 10kA

ABB S401M-UCC6 is a 6 A single-pole UC-C Type C miniature circuit breaker with 10 kA short-circuit capacity, designed for overload and short-circuit protection in DC and universal-current SMISSLINE TP plug-in distribution systems.

SKU: 2CCS571001R1064Alt SKU: S401MUCC6MPN: 2CCS571001R1064
Price
List Price £73.35 ex VAT
Your Price (ex VAT) Save 35%
£47.68 35% OFF
You save £25.67 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £47.68
Trade pricing is personalised to your account

Manufacturer Lead Time

£47.68

Why Choose the ABB S401M-UCC6 Miniature Circuit Breaker?

The ABB S401M-UCC6 is a pluggable single-pole miniature circuit breaker (MCB) designed for reliable overload and short-circuit protection in DC and universal-current applications within ABB SMISSLINE TP electrical distribution systems. Part of the ABB S400 M-UC series, it combines dependable circuit protection with the flexible plug-in architecture of the SMISSLINE TP system.

Rated at 6 A, the S401M-UCC6 features a UC-C / Type C tripping characteristic according to IEC/EN 60947-2. Its thermal and electromagnetic protection mechanisms provide automatic disconnection during sustained overloads and short-circuit faults, while the Type C characteristic accommodates moderate starting and inrush currents in appropriately designed circuits.

The single-pole S401M-UCC6 supports DC applications up to 220 V DC and has a rated short-circuit capacity of 10 kA. Its compact 18 mm one-module construction and SMISSLINE TP plug-in connection make it well suited to space-conscious industrial control and distribution assemblies.

Key Advantages

  • Reliable overload and short-circuit protection for DC and universal-current circuits.
  • 6 A rated current for control, auxiliary and distribution applications.
  • UC-C / Type C characteristic suitable for circuits with moderate starting or inrush currents.
  • 10 kA rated short-circuit capacity.
  • Single-pole configuration supports applications up to 220 V DC.
  • IP20 degree of protection.
  • Compact 18 mm, one-module construction conserves distribution-board space.
  • Plug-in design developed specifically for the ABB SMISSLINE TP system.

Key Features

  • ABB SMISSLINE TP S400 M-UC series.
  • 6 A rated current.
  • UC-C / Type C tripping characteristic.
  • 1 pole / 1 protected pole.
  • Suitable for DC circuit protection.
  • Single-pole DC operation up to 220 V DC.
  • 10 kA rated short-circuit capacity.
  • Thermal overload and electromagnetic short-circuit protection.
  • 10,000-cycle electrical endurance.
  • Compact 18 mm modular width.
  • Manufactured in accordance with IEC/EN 60947-2.

Reliable Type C Protection for DC Circuits

The ABB S401M-UCC6 protects conductors and connected equipment by automatically disconnecting the circuit when damaging overcurrent conditions occur. Its thermal protection responds to sustained overloads, while electromagnetic operation provides rapid interruption during short-circuit faults.

The UC-C characteristic makes the S401M-UCC6 suitable for appropriately engineered circuits where moderate transient currents can occur during normal equipment operation. Combined with single-pole operation up to 220 V DC and the SMISSLINE TP plug-in architecture, it provides a compact protection solution for DC control, automation and auxiliary distribution circuits.

Typical Applications

  • ABB SMISSLINE TP distribution assemblies.
  • Industrial DC control circuits.
  • Automation and control equipment.
  • DC auxiliary power circuits.
  • Instrumentation and monitoring systems.
  • Machinery and industrial electrical distribution.

Technical Specifications

Series SMISSLINE TP S400 M-UC
ABB order code 2CCS571001R1064
Product group SMISSLINE Plug-in System
Product type Miniature circuit breaker (MCB)
Rated current 6 A
Tripping characteristic UC-C / Type C
Number of poles 1
Number of protected poles 1
Maximum DC voltage, single-pole configuration 220 V DC
Rated short-circuit capacity 10 kA
Rated service short-circuit breaking capacity (Ics) at 220 V DC 10 kA
Rated service short-circuit breaking capacity (Ics) at 110 V DC 10 kA
Energy limiting class 3
Protection rating IP20
Flexible conductor capacity 0.75–25 mm²
Rigid conductor capacity 0.75–35 mm²
Tightening torque 2.8 N·m
Electrical endurance 10,000 cycles
Mechanical endurance 10,000 cycles
Width 18 mm
Height 91 mm
Depth 75 mm
Built-in depth 75 mm
Modular width 1 module
Weight 110 g
Packaging unit 10 pieces
Standard IEC/EN 60947-2
Mounting system SMISSLINE TP plug-in system

Frequently Asked Questions

What is the ABB S401M-UCC6 used for?

The ABB S401M-UCC6 provides overload and short-circuit protection for DC and universal-current circuits within compatible ABB SMISSLINE TP distribution systems.

What is the rated current of the S401M-UCC6?

The S401M-UCC6 has a rated current of 6 A.

What tripping characteristic does the S401M-UCC6 use?

The S401M-UCC6 uses a UC-C / Type C tripping characteristic, making it suitable for appropriately designed circuits that can experience moderate starting or inrush currents.

What DC voltage can the single-pole S401M-UCC6 be used with?

The single-pole S401M-UCC6 is designed for DC applications up to 220 V DC. The specified connection arrangement and polarity requirements for DC operation must be observed.

Which distribution system is the S401M-UCC6 designed for?

The S401M-UCC6 is a pluggable miniature circuit breaker designed for the ABB SMISSLINE TP system.

Trusted ABB DC Circuit Protection

ABB SMISSLINE TP S400 M-UC miniature circuit breakers combine dependable overcurrent protection, flexible DC application capability and compact plug-in construction for industrial control and distribution systems.