ABB S401M-C3 is a single-pole 3 A Type C miniature circuit breaker with 10 kA Icn and 25 kA Icu for the SMISSLINE TP plug-in system.

SKU: 2CCS571001R0034Alt SKU: S401MC3MPN: 2CCS571001R0034
Price
List Price £46.03 ex VAT
Your Price (ex VAT) Save 35%
£29.92 35% OFF
You save £16.11 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £29.92
Trade pricing is personalised to your account

Manufacturer Lead Time

£29.92

Why Choose the ABB S401M-C3 Miniature Circuit Breaker?

The ABB S401M-C3 is a compact single-pole miniature circuit breaker (MCB) designed for overload and short-circuit protection within the ABB SMISSLINE TP plug-in distribution system. With a rated current of 3 A and a Type C tripping characteristic, it is well suited to lower-current control, auxiliary and distribution circuits.

As part of the ABB S400 M-C series, the S401M-C3 provides a rated short-circuit capacity of 10 kA according to EN 60898-1 and a rated ultimate short-circuit breaking capacity of 25 kA according to IEC/EN 60947-2. This combination provides robust fault protection for demanding commercial and industrial electrical installations.

The S401M-C3 occupies only one 18 mm module and uses ABB's SMISSLINE TP plug-in architecture for efficient installation within compatible distribution assemblies. ABB identifies this exact model under order code 2CCS571001R0034 and EAN / GTIN 7612270101368.

Key Advantages

  • 3 A rated current for lower-current electrical circuits.
  • Type C tripping characteristic accommodates moderate inrush currents.
  • 10 kA rated short-circuit capacity according to EN 60898-1.
  • 25 kA rated ultimate short-circuit breaking capacity according to IEC/EN 60947-2.
  • Single-pole configuration for compact circuit protection.
  • Compact 18 mm / one-module construction.
  • IP20 degree of protection at the device.
  • Plug-in construction supports efficient integration with the ABB SMISSLINE TP system.

Key Features

  • ABB SMISSLINE TP S400 M-C series.
  • Single-pole miniature circuit breaker.
  • 3 A rated current.
  • Type C tripping characteristic.
  • 10 kA Icn according to EN 60898-1.
  • 25 kA Icu according to IEC/EN 60947-2.
  • 240 V AC rated voltage.
  • IP20 degree of protection.
  • 18 mm width.
  • Compact one-module SMISSLINE TP plug-in format.

Reliable Type C Circuit Protection for SMISSLINE TP

A Type C miniature circuit breaker combines thermal overload protection with magnetic short-circuit protection and is designed to tolerate moderate transient or inrush currents without unnecessary operation. This makes Type C breakers suitable for many commercial and industrial circuits containing equipment with normal starting-current peaks.

The ABB S401M-C3 combines this characteristic with a 3 A rating and strong short-circuit performance. Its SMISSLINE TP plug-in format enables compact integration into compatible ABB distribution assemblies while maintaining dependable protection against overloads and short circuits.

Typical Applications

  • ABB SMISSLINE TP electrical distribution systems.
  • Industrial control and auxiliary circuits.
  • Automation and PLC supply circuits.
  • Control-panel power distribution.
  • Signalling and monitoring circuits.
  • Building automation systems.
  • Commercial electrical distribution boards.
  • Industrial low-voltage installations.

Technical Specifications

Product group SMISSLINE Plug-in System
Series S400 M-C
ABB order code 2CCS571001R0034
EAN / GTIN 7612270101368
Product type Miniature circuit breaker (MCB)
Number of poles 1
Rated current 3 A
Tripping characteristic C
Rated voltage 240 V AC
Rated short-circuit capacity Icn 10 kA according to EN 60898-1
Rated ultimate short-circuit capacity Icu 25 kA according to IEC/EN 60947-2
Degree of protection IP20
Width 18 mm
Height approx. 91 mm
Depth approx. 75 mm
Module width 1 module
Weight approx. 110 g
Operating ambient temperature -25 to +55 °C
Packaging unit 10 pieces
Mounting system ABB SMISSLINE TP plug-in system
Standards EN 60898-1 and IEC/EN 60947-2

Frequently Asked Questions

What is the ABB S401M-C3 used for?

The ABB S401M-C3 is a single-pole miniature circuit breaker designed to protect compatible SMISSLINE TP circuits against overloads and short circuits.

What is the rated current of the ABB S401M-C3?

The S401M-C3 has a rated current of 3 A and uses a Type C tripping characteristic.

What is the breaking capacity of the S401M-C3?

The S401M-C3 has a rated short-circuit capacity of 10 kA according to EN 60898-1 and a rated ultimate short-circuit breaking capacity of 25 kA according to IEC/EN 60947-2.

How wide is the ABB S401M-C3?

The S401M-C3 is 18 mm wide and occupies one module within a compatible ABB SMISSLINE TP assembly.

What is the ABB order code for the S401M-C3?

The ABB order code is 2CCS571001R0034, and the EAN / GTIN is 7612270101368.

Trusted ABB SMISSLINE Circuit Protection

ABB SMISSLINE TP S400 M-C miniature circuit breakers combine high-performance overload and short-circuit protection with a modular plug-in architecture, supporting compact, dependable and service-friendly electrical distribution in commercial and industrial applications.