2CCS562001R1988 ABB S402M-UCZ0.5 DC MCB 2P Type Z 0.5 A

2CCS562001R1988 ABB S402M-UCZ0.5 DC MCB 2P Type Z 0.5 A

ABB S402M-UCZ0.5 is a two-pole 0.5 A Type Z DC miniature circuit breaker with up to 440 V DC operation and 25 kA ultimate breaking capacity for the SMISSLINE TP plug-in system.

SKU: 2CCS562001R1988Alt SKU: S402MUCZ0.5MPN: 2CCS562001R1988
Price
List Price £170.96 ex VAT
Your Price (ex VAT) Save 35%
£111.12 35% OFF
You save £59.84 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £111.12
Trade pricing is personalised to your account

Manufacturer Lead Time

£111.12

Why Choose the ABB S402M-UCZ0.5 DC Miniature Circuit Breaker?

The ABB S402M-UCZ0.5 is a high-performance two-pole miniature circuit breaker (MCB) designed for reliable protection of DC circuits within the ABB SMISSLINE TP plug-in distribution system. With a low 0.5 A rated current and sensitive Type Z tripping characteristic, it provides dependable overload and short-circuit protection for electronic, control, instrumentation and auxiliary circuits.

As part of the ABB S400M-UC series, the S402M-UCZ0.5 combines thermal-magnetic circuit protection with the flexibility of the SMISSLINE TP architecture. Its two-pole configuration enables simultaneous switching and protection of two conductors, while the plug-in design supports efficient installation, maintenance and modification of compatible electrical distribution assemblies.

The S402M-UCZ0.5 supports two-pole operation up to 440 V DC and has a rated ultimate short-circuit breaking capacity of 25 kA at 440 V DC. Its sensitive Type Z characteristic makes it particularly suitable for protecting low-current electronic and control equipment where rapid magnetic operation at relatively low fault-current multiples is required.

Key Advantages

  • Compact two-pole miniature circuit breaker for DC circuit protection.
  • 0.5 A rated current for sensitive low-current circuits.
  • Type Z tripping characteristic suited to electronic and control equipment.
  • Supports two-pole operation up to 440 V DC.
  • 25 kA ultimate short-circuit breaking capacity at 440 V DC.
  • SMISSLINE TP plug-in construction supports efficient installation, replacement and system expansion.

Key Features

  • ABB S400M-UC SMISSLINE TP series.
  • 0.5 A rated current.
  • Type Z tripping characteristic.
  • 2-pole configuration.
  • Designed for DC circuit protection.
  • Maximum 440 V DC two-pole operation.
  • Thermal-magnetic overload and short-circuit protection.
  • 25 kA ultimate breaking capacity at 440 V DC.
  • IP20 protection rating.
  • SMISSLINE TP plug-in mounting for modular distribution assemblies.

Sensitive Protection for Low-Current DC Circuits

Miniature circuit breakers automatically disconnect electrical circuits when overload or short-circuit currents exceed safe operating limits. The ABB S402M-UCZ0.5 uses thermal-magnetic protection to provide dependable interruption of sustained overloads and high fault currents in sensitive low-current DC circuits.

The Type Z characteristic provides sensitive magnetic tripping, making this breaker particularly suitable for electronic equipment, control systems, instrumentation and other circuits requiring rapid fault protection. Its two-pole configuration and SMISSLINE TP plug-in mounting also support flexible and service-friendly DC distribution designs.

Typical Applications

  • Industrial DC control circuits.
  • Electronic equipment protection.
  • PLC and automation auxiliary circuits.
  • Instrumentation and measurement systems.
  • Low-current DC signalling and monitoring circuits.
  • ABB SMISSLINE TP plug-in distribution assemblies.

Technical Specifications

Series S400M-UC / SMISSLINE TP
Order code 2CCS562001R1988
EAN / GTIN 7612270110254
Product type DC miniature circuit breaker (MCB)
Number of poles 2
Rated current 0.5 A
Tripping characteristic Type Z
Current type DC
Maximum DC voltage 440 V DC, 2-pole connection
Ultimate short-circuit breaking capacity 25 kA at 440 V DC
Protection rating IP20
Connection capacity 0.75–35 mm²
Dimensions (W × H × D) approx. 36 × 91 × 75 mm
Weight approx. 0.221 kg
Operating temperature -25 to +55 °C
Standard IEC/EN 60947-2
Mounting system ABB SMISSLINE TP plug-in system

Frequently Asked Questions

What is the ABB S402M-UCZ0.5 used for?

The S402M-UCZ0.5 is a two-pole DC miniature circuit breaker designed to protect sensitive low-current circuits against overload and short-circuit conditions.

What is the rated current of the S402M-UCZ0.5?

The ABB S402M-UCZ0.5 has a rated current of 0.5 A.

What tripping characteristic does the S402M-UCZ0.5 have?

The breaker has a Type Z tripping characteristic, making it particularly suitable for sensitive electronic, control and instrumentation circuits.

What DC voltage can the ABB S402M-UCZ0.5 handle?

The S402M-UCZ0.5 supports operation up to 440 V DC when used in the specified two-pole configuration.

What is the breaking capacity of the S402M-UCZ0.5?

The breaker has a rated ultimate short-circuit breaking capacity of 25 kA at 440 V DC, providing robust fault-current protection for compatible DC installations.

Trusted ABB DC Circuit Protection