ABB FS402MKC200.03 FS402MK-C20/0.03 is a 1P+N Type F AP-R high-immunity 20 A C-curve 30 mA RCBO with protected neutral and 10 kA breaking capacity for the SMISSLINE TP plug-in system.
£188.32
The ABB FS402MKC200.03, type designation FS402MK-C20/0.03, is a 1P+N residual current circuit breaker with overcurrent protection (RCBO) designed for the ABB SMISSLINE TP plug-in system. It combines overload, short-circuit and residual-current protection in one compact device, with a protected neutral for dependable single-phase circuit protection.
This FS402MK series RCBO has a 20 A rated current, C tripping characteristic and 30 mA rated residual operating current. Its Type F AP-R high-immunity characteristic provides increased resistance to unwanted tripping and is suitable for circuits containing modern electronic, resistive and inductive loads.
With a 240/415 V AC rated operational voltage and 10 kA rated short-circuit breaking capacity according to IEC/EN 61009-1, the FS402MK-C20/0.03 provides robust combined circuit protection. ABB's integrated DTI earth-fault indicator helps identify differential trips, while the SMISSLINE TP plug-in format supports efficient installation, replacement and maintenance.
The ABB FS402MK-C20/0.03 combines miniature circuit-breaker and residual-current protective functions within one device. It protects connected circuits against overload and short-circuit currents while detecting residual currents, providing fault protection and 30 mA additional protection against electric shock.
Its Type F AP-R high-immunity characteristic is particularly suitable for circuits containing electronic equipment and provides increased resistance to transient disturbances that can otherwise cause unwanted operation. The SMISSLINE TP plug-in architecture simplifies installation and maintenance, while the DTI indicator provides a separate visual indication when the RCBO has operated because of a residual-current fault.
| Product group | SMISSLINE Plug-in System |
|---|---|
| Series | FS402MK |
| SKU | FS402MKC200.03 |
| ABB order code | 2CCG001770R0001 |
| EAN / GTIN | 7612271522391 |
| Product type | Residual current circuit breaker with overcurrent protection (RCBO) |
| Configuration | 1P+N, protected neutral |
| Number of protected poles | 2 |
| Rated current | 20 A |
| Tripping characteristic | C |
| Residual-current type | Type F, AP-R high immunity |
| Rated residual operating current | 30 mA |
| Rated operational voltage | 240/415 V AC |
| Rated insulation voltage | 500 V |
| Rated impulse withstand voltage | 4 kV |
| Rated frequency | 50/60 Hz |
| Rated breaking capacity Icn | 10 kA according to IEC/EN 61009-1 |
| Ultimate short-circuit breaking capacity Icu | 15 kA according to IEC/EN 60947-2 |
| Service short-circuit breaking capacity Ics | 7.5 kA |
| Energy limiting class | 3 |
| Power loss | 4.4 W |
| Protection rating | IP20 |
| Pollution degree | 2 |
| Overvoltage category | III |
| Operating ambient temperature | -25 to +60 °C |
| Width | 3 modular spacings |
| Built-in depth | 78 mm |
| Flexible conductor capacity | 0.75–25 mm² |
| Weight | 0.312 kg |
| Trip indication | DTI earth-fault indicator |
| Contact indication | Contact Position Indicator (CPI) |
| Mounting system | SMISSLINE TP plug-in system |
The ABB FS402MKC200.03 is a 1P+N RCBO with protected neutral designed to provide combined overload, short-circuit and residual-current protection in compatible ABB SMISSLINE TP electrical distribution systems.
The FS402MK-C20/0.03 has a rated current of 20 A and uses a C tripping characteristic.
The FS402MK-C20/0.03 has a rated residual operating current of 30 mA and uses a Type F AP-R high-immunity residual-current characteristic.
The FS402MK-C20/0.03 has a rated short-circuit breaking capacity Icn of 10 kA according to IEC/EN 61009-1, with an Icu of 15 kA and Ics of 7.5 kA according to IEC/EN 60947-2.
The DTI earth-fault indicator provides a separate visual indication when the RCBO has operated because of a residual-current fault, helping maintenance personnel distinguish differential trips during troubleshooting.
ABB SMISSLINE RCBOs combine comprehensive circuit protection, high-immunity residual-current performance, clear fault indication and efficient plug-in installation for reliable modern electrical distribution systems.