ABB FS402MK-B6/0.03 SMISSLINE TP 1P+N Type F AP-R RCBO with 6 A rated current, B characteristic, 30 mA residual current sensitivity and 10 kA breaking capacity.
£197.73
The ABB FS402MK-B6/0.03 is a compact and highly reliable 1P+N residual current circuit breaker with overcurrent protection (RCBO) designed for the ABB SMISSLINE TP plug-in distribution system. Combining overload, short-circuit and residual current protection in a single device, it provides comprehensive protection for single-phase final circuits in commercial, industrial and building electrical installations.
As part of the ABB FS402 Type F RCBO series, this device features AP-R high-immunity residual current protection for improved resistance to unwanted tripping. Its Type F characteristic is suitable for modern loads containing electronic components and variable-frequency circuitry, while the protected neutral and SMISSLINE TP plug-in connection support dependable and efficient electrical distribution.
The FS402MK-B6/0.03 features a 6 A rated current, B tripping characteristic, 30 mA rated residual operating current and 10 kA rated breaking capacity according to IEC/EN 61009-1. Its two-pole 1P+N configuration occupies three modules and is designed for direct integration with compatible ABB SMISSLINE TP systems.
RCBOs combine miniature circuit breaker and residual current protection functions within a single device. The ABB FS402MK-B6/0.03 therefore protects its connected circuit against overload and short-circuit currents while also detecting potentially hazardous earth leakage currents, helping provide both equipment and personnel protection.
The FS402 series is designed specifically for single-phase circuits in the ABB SMISSLINE TP system. Type F AP-R high-immunity technology makes the range well suited to modern electronic loads while reducing susceptibility to unwanted residual-current trips, and the plug-in architecture supports efficient installation and maintenance within compatible distribution assemblies.
| Product group | SMISSLINE Plug-in System |
|---|---|
| Series | FS402 |
| ABB order code | 2CCG001760R0001 |
| EAN / GTIN | 7612271522292 |
| Product type | Residual current circuit breaker with overcurrent protection (RCBO) |
| Number of poles | 1P+N (2-pole) |
| Neutral | Protected |
| Rated current | 6 A |
| Tripping characteristic | B |
| Residual current type | Type F, AP-R high immunity |
| Rated residual operating current | 30 mA |
| Rated voltage | 240 / 415 V AC |
| Rated insulation voltage | 500 V |
| Rated frequency | 50 / 60 Hz |
| Rated breaking capacity Icn | 10 kA according to IEC/EN 61009-1 |
| Rated ultimate short-circuit capacity Icu | 25 kA according to IEC/EN 60947-2 |
| Rated service short-circuit capacity Ics | 15 kA according to IEC/EN 60947-2 |
| Overvoltage category | III |
| Pollution degree | 2 |
| Protection rating | IP20 |
| Width | 3 modules |
| Weight | approx. 0.312 kg |
| Mounting system | ABB SMISSLINE TP plug-in system |
| Standards | IEC/EN 61009-1, IEC/EN 61009-2-1 and IEC/EN 62423 |
The ABB FS402MK-B6/0.03 provides combined overload, short-circuit and residual current protection for single-phase circuits installed within compatible ABB SMISSLINE TP distribution systems.
The RCBO has a rated current of 6 A and uses a B tripping characteristic.
The FS402MK-B6/0.03 has a rated residual operating current of 30 mA and uses Type F AP-R high-immunity residual current protection.
The device has a rated breaking capacity of 10 kA according to IEC/EN 61009-1, with a 25 kA ultimate short-circuit capacity for the 6 A rating according to IEC/EN 60947-2.
The RCBO is designed for the ABB SMISSLINE TP plug-in distribution system, providing direct plug-in integration with compatible SMISSLINE TP assemblies.
ABB SMISSLINE TP protective devices provide integrated circuit protection in a modular plug-in platform designed for efficient installation, dependable operation and flexible electrical distribution in commercial and industrial applications.