2CCG001757R0001 ABB FS403MKC200.3 FS403MK-C20/0.3 RCBO 3P+N Type F 20 A 300 mA

2CCG001757R0001 ABB FS403MKC200.3 FS403MK-C20/0.3 RCBO 3P+N Type F 20 A 300 mA

ABB FS403MKC200.3 FS403MK-C20/0.3 is a 3P+N Type F 20 A C-curve 300 mA short-time delayed RCBO with 10 kA breaking capacity for the SMISSLINE TP plug-in system.

SKU: 2CCG001757R0001Alt SKU: FS403MKC200.3MPN: 2CCG001757R0001
Price
List Price £473.30 ex VAT
Your Price (ex VAT) Save 35%
£307.65 35% OFF
You save £165.66 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £307.65
Trade pricing is personalised to your account

Manufacturer Lead Time

£307.65

Why Choose the ABB FS403MKC200.3 RCBO?

The ABB FS403MKC200.3, type designation FS403MK-C20/0.3, is a 3P+N residual current circuit breaker with overcurrent protection (RCBO) designed for the ABB SMISSLINE TP plug-in system. It combines overload, short-circuit and residual-current protection in a single four-pole protective device for industrial and commercial electrical distribution.

This FS403MK series RCBO has a 20 A rated current, C tripping characteristic and 300 mA rated residual operating current. Its Type F residual-current characteristic is designed for circuits incorporating modern electronic equipment, while its short-time delayed characteristic provides increased resistance to unwanted tripping and supports continuity of service.

With a 10 kA rated short-circuit breaking capacity according to EN 61009-1, the FS403MK-C20/0.3 provides dependable protection for three-phase circuits. Its plug-in construction enables direct connection to the SMISSLINE TP socket system, supporting efficient installation, replacement and maintenance in compatible electrical distribution assemblies.

Key Advantages

  • Combines residual-current, overload and short-circuit protection in one device.
  • 20 A rated current with C tripping characteristic.
  • 300 mA rated residual operating current.
  • Type F residual-current protection suitable for circuits incorporating electronic loads.
  • Short-time delayed operation provides increased resistance to unwanted tripping.
  • 10 kA breaking capacity according to EN 61009-1.
  • 3P+N configuration with three protected poles.
  • Direct plug-in connection to the ABB SMISSLINE TP system.

Key Features

  • ABB FS403MK series RCBO.
  • 20 A rated current.
  • C tripping characteristic.
  • 300 mA residual-current sensitivity.
  • Type F residual-current characteristic.
  • Short-time delayed operation.
  • 10 kA Icn rated breaking capacity according to EN 61009-1.
  • 15 kA ultimate short-circuit breaking capacity for the 20–32 A FS403MK range.
  • 7.5 kA service short-circuit breaking capacity for the 20–32 A FS403MK range.
  • 500 V rated insulation voltage.
  • 4 kV rated impulse withstand voltage.
  • 3 kA surge current withstand.
  • 50 / 60 Hz rated frequency.
  • Four-module plug-in format for the SMISSLINE TP system.

Reliable Circuit Protection for SMISSLINE Distribution Systems

RCBOs combine the protective functions of a miniature circuit breaker and a residual-current protective device. The ABB FS403MK-C20/0.3 therefore protects connected circuits against overload and short-circuit currents while also detecting residual currents, providing coordinated circuit and earth-fault protection within one compact device.

The SMISSLINE TP plug-in architecture allows compatible protective devices to connect directly to the socket system, supporting efficient installation and servicing. The Type F characteristic provides protection against residual currents associated with modern electronic loads, while the 300 mA sensitivity and short-time delayed operation make this model suitable for installations requiring dependable residual-current protection with improved continuity of service.

Typical Applications

  • ABB SMISSLINE TP electrical distribution boards.
  • Industrial control and power distribution panels.
  • Commercial building electrical distribution.
  • Three-phase circuits requiring combined overcurrent and residual-current protection.
  • Circuits incorporating electronic equipment suitable for Type F protection.
  • Electrical installations requiring 300 mA residual-current protection.

Technical Specifications

Product group SMISSLINE Plug-in System
Series FS403MK
SKU FS403MKC200.3
ABB order code 2CCG001757R0001
EAN / GTIN 7612271522261
Product type Residual current circuit breaker with overcurrent protection (RCBO)
Poles 3P+N (4 poles total)
Protected poles 3
Rated current 20 A
Tripping characteristic C
Residual-current type Type F
Rated residual operating current 300 mA
Operating characteristic Short-time delayed
Rated operational voltage 415 V AC
Rated insulation voltage 500 V
Rated impulse withstand voltage 4 kV
Rated breaking capacity Icn 10 kA according to EN 61009-1
Ultimate short-circuit breaking capacity Icu 15 kA
Service short-circuit breaking capacity Ics 7.5 kA
Frequency 50 / 60 Hz
Energy limiting class 3
Surge current withstand 3 kA
Power loss 7.5 W
Pollution degree 2
Overvoltage category III
Width 4 modular spacings
Built-in depth 78 mm
Weight 0.420 kg
Mounting system SMISSLINE TP plug-in system

Frequently Asked Questions

What is the ABB FS403MKC200.3 used for?

The ABB FS403MKC200.3 is a 3P+N RCBO designed to provide combined overload, short-circuit and residual-current protection in compatible ABB SMISSLINE TP distribution systems.

What is the current rating of the FS403MK-C20/0.3?

The RCBO has a rated current of 20 A and uses a C tripping characteristic.

What residual-current sensitivity does this RCBO provide?

The FS403MK-C20/0.3 has a rated residual operating current of 300 mA and uses a Type F residual-current characteristic with short-time delayed operation.

What is the breaking capacity of the ABB FS403MK-C20/0.3?

The FS403MK-C20/0.3 has a rated short-circuit breaking capacity Icn of 10 kA according to EN 61009-1.

Which distribution system is the FS403MK-C20/0.3 designed for?

It is a plug-in protective device designed for the ABB SMISSLINE TP system, enabling direct connection to the compatible SMISSLINE socket system.

Trusted ABB Protection for Electrical Distribution

ABB SMISSLINE protective devices combine modular plug-in installation with dependable circuit protection, helping panel builders and electrical engineers create efficient, serviceable and robust power distribution systems.