2CCG001744R0001 ABB FS403MK-B25/0.03 RCBO 3P+N Type F 25 A 30 mA

2CCG001744R0001 ABB FS403MK-B25/0.03 RCBO 3P+N Type F 25 A 30 mA

ABB FS403MK-B25/0.03 is a 3P+N short-time-delayed Type F 25 A B-curve RCBO with 30 mA residual-current sensitivity, 10 kA breaking capacity and DTI earth-fault indication for the SMISSLINE TP plug-in system.

SKU: 2CCG001744R0001Alt SKU: FS403MKB250.03MPN: 2CCG001744R0001
Price
List Price £457.84 ex VAT
Your Price (ex VAT) Save 35%
£297.60 35% OFF
You save £160.24 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £297.60
Trade pricing is personalised to your account

Manufacturer Lead Time

£297.60

Why Choose the ABB FS403MK-B25/0.03 RCBO?

The ABB FS403MK-B25/0.03 is a 3P+N Type F residual current circuit breaker with overcurrent protection (RCBO) designed for the ABB SMISSLINE TP plug-in system. It combines overload, short-circuit and residual-current protection in one four-pole device, simplifying circuit protection within compatible three-phase distribution assemblies.

This FS403MK model has a 25 A rated current, B tripping characteristic and 30 mA rated residual operating current. Its short-time-delayed APR Type F characteristic is intended for modern loads incorporating electronic and frequency-dependent equipment, while increased resistance to transient disturbances helps reduce unwanted tripping.

The FS403MK-B25/0.03 provides a 10 kA rated short-circuit breaking capacity according to IEC/EN 61009-1 and a 15 kA ultimate breaking capacity according to IEC/EN 60947-2. Integrated DTI earth-fault indication assists fault identification, while direct connection to the SMISSLINE TP plug-in system supports efficient installation, servicing and circuit replacement.

Key Advantages

  • Combines overload, short-circuit and residual-current protection in one RCBO.
  • 3P+N configuration for three-phase circuits with neutral.
  • 25 A B-curve rating for suitable final and distribution circuits.
  • Type F residual-current protection for modern loads incorporating electronic and frequency-dependent equipment.
  • 30 mA residual-current sensitivity provides additional protection against direct contact in appropriate installations.
  • Short-time-delayed APR characteristic provides increased resistance to unwanted tripping.
  • 10 kA rated short-circuit breaking capacity according to IEC/EN 61009-1.
  • Integrated DTI earth-fault indication supports efficient fault identification.
  • Direct integration with the ABB SMISSLINE TP plug-in system supports efficient installation and maintenance.

Key Features

  • ABB FS403MK RCBO series.
  • 3P+N / four-pole configuration.
  • Three protected poles.
  • 25 A rated current.
  • B tripping characteristic.
  • 30 mA rated residual operating current.
  • Short-time-delayed APR Type F residual-current detection.
  • 240/415 V AC rated operational voltage.
  • 10 kA rated short-circuit breaking capacity according to IEC/EN 61009-1.
  • 15 kA ultimate breaking capacity according to IEC/EN 60947-2.
  • 500 V rated insulation voltage.
  • 4 kV rated impulse withstand voltage.
  • 50/60 Hz rated frequency.
  • Current-limiting class 3.
  • 3 kA surge-current withstand.
  • Integrated DTI differential-trip indication.
  • Direct plug-in connection to the SMISSLINE TP system.

Reliable Type F Protection with Increased Immunity

The ABB FS403MK-B25/0.03 combines circuit-breaker and residual-current functions within one device, protecting connected circuits against overload, short-circuit and earth-fault conditions. Its 30 mA residual-current sensitivity also provides additional protection against direct contact in appropriate installations.

The short-time-delayed APR Type F characteristic provides an effective balance between electrical safety and continuity of service. Type F protection is suited to modern loads incorporating electronic and frequency-dependent components, while increased resistance to transient disturbances helps reduce unwanted residual-current tripping.

Typical Applications

  • Three-phase circuits with neutral in SMISSLINE TP distribution systems.
  • Residential and commercial distribution boards.
  • Industrial electrical distribution systems.
  • Circuits supplying loads incorporating electronic or frequency-dependent components.
  • Applications where increased resistance to unwanted residual-current tripping is beneficial.
  • Circuits requiring combined 25 A B-curve overcurrent and 30 mA Type F residual-current protection.

Technical Specifications

Series FS403MK / SMISSLINE TP
ABB order code 2CCG001744R0001
EAN / GTIN 7612271522131
Product type Residual current circuit breaker with overcurrent protection (RCBO)
Poles 3P+N / 4 poles
Protected poles 3
Rated current 25 A
Tripping characteristic B
Residual-current type APR Type F
Rated residual operating current 30 mA
Rated operational voltage 240/415 V AC
Rated insulation voltage 500 V
Rated impulse withstand voltage 4 kV
Rated frequency 50/60 Hz
Rated short-circuit breaking capacity (Icn) 10 kA according to IEC/EN 61009-1
Ultimate breaking capacity (Icu) 15 kA according to IEC/EN 60947-2
Current-limiting class 3
Surge-current withstand 3 kA
Residual-current characteristic Short-time-delayed APR Type F
Product standards IEC/EN 61009-1, IEC/EN 61009-2-1 and IEC/EN 62423
Trip indication DTI earth-fault indication
Mounting system SMISSLINE TP plug-in system
Protection rating IP20
Module width 4 modules
Installation depth 78 mm
Connectable multi-wired conductor cross-section 0.75–25 mm²
Overvoltage category III
Pollution degree 2
Power loss 10.1 W
Operating temperature −25 to +60 °C
Weight approx. 0.420 kg

Frequently Asked Questions

What is the ABB FS403MK-B25/0.03 used for?

It is a 3P+N RCBO for ABB SMISSLINE TP systems that combines overload, short-circuit and Type F residual-current protection in one device.

What are the current and residual-current ratings?

The FS403MK-B25/0.03 has a rated current of 25 A, a B tripping characteristic and a rated residual operating current of 30 mA.

What does Type F residual-current protection provide?

Type F residual-current protection is designed for modern loads incorporating electronic and frequency-dependent components, providing residual-current detection capabilities beyond conventional Type A applications.

What is the breaking capacity of the FS403MK-B25/0.03?

The FS403MK-B25/0.03 has a rated short-circuit breaking capacity of 10 kA according to IEC/EN 61009-1 and an ultimate breaking capacity of 15 kA according to IEC/EN 60947-2.

What is the benefit of the APR characteristic?

The short-time-delayed APR characteristic provides increased resistance to unwanted tripping from transient disturbances, helping maintain continuity of service while retaining residual-current protection.

Advanced ABB Protection for SMISSLINE TP Systems

ABB FS403MK RCBOs combine overcurrent protection, short-time-delayed Type F residual-current protection and SMISSLINE TP plug-in installation for reliable circuit protection where safety, fault identification and continuity of service are important.