2CCG001738R0001 ABB FS403M-C32/0.1 RCBO 3P+N Type A 32 A 100 mA

2CCG001738R0001 ABB FS403M-C32/0.1 RCBO 3P+N Type A 32 A 100 mA

ABB FS403M-C32/0.1 is a SMISSLINE TP 3P+N Type A RCBO with a 32 A C-curve rating, 100 mA residual-current sensitivity, 415 V AC rated voltage and 10 kA breaking capacity for three-phase circuit and earth-fault protection.

SKU: 2CCG001738R0001Alt SKU: FS403MC320.1MPN: 2CCG001738R0001
Price
List Price £375.00 ex VAT
Your Price (ex VAT) Save 35%
£243.75 35% OFF
You save £131.25 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £243.75
Trade pricing is personalised to your account

Manufacturer Lead Time

£243.75

Why Choose the ABB FS403M-C32/0.1 RCBO?

The ABB FS403M-C32/0.1 is a pluggable 3P+N residual current circuit breaker with overcurrent protection (RCBO) designed for the ABB SMISSLINE TP distribution system. Combining overload, short-circuit and residual-current protection in a single four-pole device, it provides integrated protection for three-phase circuits with neutral in residential, commercial and industrial electrical installations.

As part of the ABB FS403M series, this RCBO uses a Type A residual-current characteristic for detection of sinusoidal alternating and pulsating DC earth-fault currents. Its 100 mA residual-current sensitivity supports earth-fault protection, while DTI functionality provides an indication when operation has been caused by a residual-current fault.

With a rated current of 32 A, a C tripping characteristic and a rated residual operating current of 100 mA, the FS403M-C32/0.1 is suitable for circuits where moderate starting currents may occur. It provides a rated short-circuit breaking capacity of 10 kA according to EN 61009-1 and connects directly to the SMISSLINE TP plug-in system for efficient installation, replacement and maintenance.

Key Advantages

  • Combines residual-current, overload and short-circuit protection in one device.
  • 3P+N four-pole configuration for three-phase circuits with neutral.
  • 32 A rated current with C-curve overcurrent characteristic.
  • 100 mA residual-current sensitivity for earth-fault protection.
  • Type A residual-current protection for sinusoidal AC and pulsating DC earth-fault currents.
  • 10 kA rated breaking capacity according to EN 61009-1.
  • Direct plug-in installation into the ABB SMISSLINE TP system.

Key Features

  • ABB FS403M RCBO series.
  • 3P+N configuration with four poles and three protected poles.
  • 32 A rated current.
  • C tripping characteristic.
  • 100 mA rated residual operating current.
  • Type A residual-current characteristic.
  • 415 V AC rated voltage.
  • 10 kA rated short-circuit breaking capacity according to EN 61009-1.
  • 15 kA breaking capacity according to IEC 60947-2.
  • Integrated DTI residual-current trip indication.
  • 3 kA surge-current resistance and current limiting class 3.
  • Four-module SMISSLINE TP plug-in format with 78 mm installation depth.

Integrated Three-Phase Circuit Protection for SMISSLINE TP

An RCBO combines the protective functions of a miniature circuit breaker and a residual-current protective device in one unit. The ABB FS403M-C32/0.1 therefore protects three-phase circuits against overload and short-circuit currents while detecting residual currents caused by insulation faults, earth leakage and other electrical faults.

The Type A residual-current characteristic enables detection of sinusoidal alternating and pulsating DC earth-fault currents. Combined with 100 mA sensitivity, a 10 kA rated breaking capacity and the SMISSLINE TP plug-in architecture, the FS403M-C32/0.1 provides coordinated circuit and earth-fault protection while supporting efficient installation and maintenance in compatible distribution systems.

Typical Applications

  • ABB SMISSLINE TP electrical distribution systems.
  • Three-phase circuits with neutral.
  • Commercial building electrical distribution.
  • Industrial control and electrical distribution systems.
  • Circuits requiring C-curve protection for moderate starting currents.
  • Installations requiring 100 mA Type A residual-current protection.
  • Applications requiring combined overload, short-circuit and earth-fault protection.

Technical Specifications

Product group SMISSLINE Plug-in System
Series FS403M
ABB order code 2CCG001738R0001
EAN / GTIN 7612271522070
Product type Residual current circuit breaker with overcurrent protection (RCBO)
Poles 3P+N
Total number of poles 4
Number of protected poles 3
Rated current 32 A
Tripping characteristic C
Residual-current type Type A
Rated residual operating current 100 mA
Rated voltage 415 V AC
Rated insulation voltage 500 V
Rated impulse withstand voltage 4 kV
Rated frequency 50/60 Hz
Rated breaking capacity Icn 10 kA according to EN 61009-1
Breaking capacity 15 kA according to IEC 60947-2
Surge-current resistance 3 kA
Current limiting class 3
Overvoltage category III
Pollution degree 2
Number of modules 4
Installation depth 78 mm
Power loss 12.6 W
Connectable conductor cross-section, multi-wired 0.75–25 mm²
Mounting type SMISSLINE TP plug-in
Protection rating IP20
Operating ambient temperature -25 to +60 °C
Product standard IEC/EN 61009-1
Weight approx. 0.42 kg

Frequently Asked Questions

What is the ABB FS403M-C32/0.1 used for?

It is a 3P+N RCBO designed to provide overload, short-circuit and 100 mA Type A residual-current protection for three-phase circuits with neutral in ABB SMISSLINE TP distribution systems.

What is the rated current of the FS403M-C32/0.1?

The RCBO has a rated current of 32 A and uses a C tripping characteristic, making it suitable for circuits where moderate starting currents may occur.

What residual-current protection does this RCBO provide?

The FS403M-C32/0.1 provides Type A residual-current protection with 100 mA sensitivity for sinusoidal AC and pulsating DC earth-fault currents.

What is the breaking capacity of the ABB FS403M-C32/0.1?

The device has a rated short-circuit breaking capacity of 10 kA according to EN 61009-1 and a breaking capacity of 15 kA according to IEC 60947-2.

How is the FS403M-C32/0.1 installed?

The RCBO is designed for plug-in installation in the ABB SMISSLINE TP system, enabling efficient integration, replacement and maintenance within compatible electrical distribution assemblies.

Trusted ABB Circuit Protection

ABB SMISSLINE TP protective devices combine modular plug-in installation with dependable circuit protection, helping electrical designers and installers create flexible distribution systems for residential, commercial and industrial applications.