ABB FS403M-C16/0.03 is a 3P+N Type A 16 A C-curve RCBO with 30 mA residual-current protection, 10 kA breaking capacity and DTI earth-fault indication for the SMISSLINE TP plug-in system.
£271.14
The ABB FS403M-C16/0.03 is a 3P+N Type A residual current circuit breaker with overcurrent protection (RCBO) designed for the ABB SMISSLINE TP plug-in system. It combines overload, short-circuit and residual-current protection in a single four-pole device, providing comprehensive protection for three-phase final circuits with neutral in residential, commercial and industrial electrical installations.
This FS403M model has a 16 A rated current, C tripping characteristic and 30 mA rated residual operating current. Its Type A residual-current characteristic provides protection against the effects of sinusoidal alternating and pulsating DC earth-fault currents, while the 30 mA sensitivity provides additional protection against direct contact in appropriate installations.
With a rated voltage of 415 V AC and a 10 kA rated short-circuit breaking capacity according to EN 61009-1, the FS403M-C16/0.03 is suited to demanding distribution applications. Integrated DTI earth-fault indication assists fault identification, while direct connection to the SMISSLINE TP plug-in system supports efficient installation, servicing and circuit replacement.
The ABB FS403M-C16/0.03 combines miniature circuit-breaker and residual-current functions within one device. It protects three-phase final circuits with neutral against overload and short-circuit currents while monitoring for residual currents caused by insulation faults or unintended current flow to earth.
Its Type A characteristic provides protection against sinusoidal alternating and pulsating DC residual currents, while the 30 mA sensitivity provides additional protection against direct contact in appropriate installations. Integration with ABB's SMISSLINE TP plug-in architecture also supports efficient distribution-board assembly, servicing and circuit replacement.
| Series | FS403M / SMISSLINE TP |
|---|---|
| ABB order code | 2CCG001728R0001 |
| EAN / GTIN | 7612271521974 |
| Product type | Residual current circuit breaker with overcurrent protection (RCBO) |
| Poles | 3P+N / 4 poles |
| Protected poles | 3 |
| Rated current | 16 A |
| Tripping characteristic | C |
| Residual-current type | Type A |
| Rated residual operating current | 30 mA |
| Rated operational voltage | 415 V AC |
| Rated insulation voltage | 500 V |
| Rated impulse withstand voltage | 4 kV |
| Frequency | 50 / 60 Hz |
| Rated short-circuit breaking capacity (Icn) | 10 kA according to EN 61009-1 |
| Breaking capacity according to IEC 60947-2 | 25 kA |
| Current-limiting class | 3 |
| Surge-current withstand | 3 kA |
| Disconnection characteristic | Undelayed |
| Product standard | IEC/EN 61009-1 |
| Trip indication | DTI earth-fault indication |
| Mounting system | SMISSLINE TP plug-in system |
| Protection rating | IP20 |
| Module width | 4 modules |
| Installation depth | 78 mm |
| Connectable stranded conductor cross-section | 0.75–25 mm² |
| Overvoltage category | III |
| Pollution degree | 2 |
| Power loss | 6.6 W |
| Operating temperature | −25 to +60 °C |
| Weight | approx. 0.42 kg |
It is a 3P+N RCBO designed to protect three-phase final circuits with neutral against overload, short-circuit and residual-current faults within ABB SMISSLINE TP distribution systems.
The FS403M-C16/0.03 has a rated current of 16 A with a C tripping characteristic.
The device provides Type A residual-current protection with a rated residual operating current of 30 mA, providing protection against the effects of sinusoidal AC and pulsating DC earth-fault currents.
The FS403M-C16/0.03 has a rated short-circuit breaking capacity of 10 kA according to EN 61009-1 and a breaking capacity of 25 kA according to IEC 60947-2.
The integrated DTI earth-fault indication helps identify residual-current operation, supporting faster fault diagnosis and maintenance.
ABB FS403M RCBOs combine three-phase overcurrent and Type A residual-current protection with fault indication and SMISSLINE TP plug-in installation for dependable protection of residential, commercial and industrial electrical circuits.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.