2CCG001723R0001 ABB FS403E-C25/0.03 RCBO 3P+N Type A 25 A 30 mA

2CCG001723R0001 ABB FS403E-C25/0.03 RCBO 3P+N Type A 25 A 30 mA

ABB FS403E-C25/0.03 is a 3P+N Type A 25 A C-curve RCBO with 30 mA residual-current sensitivity, 6 kA breaking capacity and DTI earth-fault indication for the SMISSLINE TP plug-in system.

SKU: 2CCG001723R0001Alt SKU: FS403EC250.03MPN: 2CCG001723R0001
Price
List Price £286.82 ex VAT
Your Price (ex VAT) Save 35%
£186.43 35% OFF
You save £100.39 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £186.43
Trade pricing is personalised to your account

Manufacturer Lead Time

£186.43

Why Choose the ABB FS403E-C25/0.03 RCBO?

The ABB FS403E-C25/0.03 is a compact 3P+N Type A residual current circuit breaker with overcurrent protection (RCBO) designed for the ABB SMISSLINE TP plug-in system. It combines overload, short-circuit and residual-current protection in a single four-pole device, providing coordinated protection for three-phase circuits with neutral in residential, commercial and industrial electrical distribution systems.

This FS403E model has a 25 A rated current, C tripping characteristic and 30 mA rated residual operating current. Its Type A residual-current detection provides protection against the effects of sinusoidal alternating and pulsating DC earth-fault currents, while the 30 mA sensitivity provides additional protection against direct contact in appropriate installations.

With a rated operational voltage of 415 V AC and a 6 kA rated short-circuit breaking capacity according to IEC/EN 61009-1, the FS403E-C25/0.03 provides dependable circuit protection in a four-module format. Integrated DTI earth-fault indication assists fault identification, while direct connection to the SMISSLINE TP plug-in system supports efficient installation and maintenance.

Key Advantages

  • Combines overload, short-circuit and residual-current protection in one RCBO.
  • 3P+N configuration for three-phase circuits with neutral.
  • 25 A C-curve rating for suitable three-phase circuits and loads.
  • Type A residual-current protection for sinusoidal AC and pulsating DC residual currents.
  • 30 mA sensitivity provides additional protection against direct contact in appropriate installations.
  • 6 kA rated short-circuit breaking capacity according to IEC/EN 61009-1.
  • Integrated DTI earth-fault indication supports faster fault identification.
  • Direct integration with the ABB SMISSLINE TP plug-in system supports efficient installation and maintenance.

Key Features

  • ABB FS403E RCBO series.
  • 3P+N / four-pole configuration.
  • Three protected poles.
  • 25 A rated current.
  • C tripping characteristic.
  • 30 mA rated residual operating current.
  • Type A residual-current detection.
  • 415 V AC rated operational voltage.
  • 6 kA rated short-circuit breaking capacity according to IEC/EN 61009-1.
  • Current-limiting class 3.
  • 3 kA surge-current capacity.
  • Integrated DTI differential-trip indication.
  • Direct plug-in connection to the SMISSLINE TP system.
  • Compact four-module format.

Reliable Three-Phase Circuit and Residual-Current Protection

The ABB FS403E-C25/0.03 combines miniature circuit-breaker and residual-current functions within one device. It protects three-phase circuits with neutral against overload and short-circuit currents while monitoring for residual currents resulting from insulation faults or unintended current flow to earth.

Its Type A characteristic provides protection against sinusoidal alternating and pulsating DC residual currents, while the 30 mA sensitivity provides additional protection against direct contact in appropriate installations. Integration with ABB's SMISSLINE TP plug-in architecture also supports efficient distribution-board assembly, servicing and circuit replacement.

Typical Applications

  • Three-phase final circuits with neutral in SMISSLINE TP distribution systems.
  • Residential electrical distribution.
  • Commercial building distribution boards.
  • Industrial electrical distribution and auxiliary circuits.
  • Three-phase circuits requiring combined overcurrent and residual-current protection.
  • Installations requiring 30 mA Type A residual-current protection.

Technical Specifications

Series FS403E / SMISSLINE TP
ABB order code 2CCG001723R0001
EAN / GTIN 7612271521929
Product type Residual current circuit breaker with overcurrent protection (RCBO)
Poles 3P+N / 4 poles
Protected poles 3
Rated current 25 A
Tripping characteristic C
Residual-current type Type A
Rated residual operating current 30 mA
Rated operational voltage 415 V AC
Rated insulation voltage 500 V
Rated impulse withstand voltage 4 kV
Frequency 50 / 60 Hz
Rated short-circuit breaking capacity (Icn) 6 kA
Current-limiting class 3
Surge-current capacity 3 kA
Operating characteristic Undelayed
Product standard IEC/EN 61009-1
Trip indication DTI earth-fault indication
Mounting system SMISSLINE TP plug-in system
Protection rating IP20
Module width 4 modules
Installation depth 78 mm
Connectable stranded conductor cross-section 0.75–25 mm²
Overvoltage category III
Pollution degree 2
Power loss 10.1 W
Operating temperature −25 to +60 °C
Weight approx. 0.42 kg

Frequently Asked Questions

What is the ABB FS403E-C25/0.03 used for?

It is a 3P+N RCBO designed to protect three-phase circuits with neutral against overload, short-circuit and residual-current faults within ABB SMISSLINE TP distribution systems.

What is the current rating of the FS403E-C25/0.03?

The FS403E-C25/0.03 has a rated current of 25 A with a C tripping characteristic.

What residual-current protection does this RCBO provide?

The device provides Type A residual-current protection with a rated residual operating current of 30 mA, protecting against the effects of sinusoidal AC and pulsating DC earth-fault currents.

What is the breaking capacity of the FS403E-C25/0.03?

The FS403E-C25/0.03 has a rated short-circuit breaking capacity of 6 kA according to IEC/EN 61009-1.

What does the DTI feature do?

The integrated DTI earth-fault indication helps identify residual-current operation, supporting faster fault diagnosis and maintenance.

Trusted ABB Protection for SMISSLINE TP Systems

ABB FS403E RCBOs combine three-phase overcurrent and Type A residual-current protection with clear fault indication and SMISSLINE TP plug-in installation for dependable protection of residential, commercial and industrial electrical circuits.