2CCG001708R0001 ABB FS401MK-C20/0.3 RCBO 1P+N Type F 20 A 300 mA

2CCG001708R0001 ABB FS401MK-C20/0.3 RCBO 1P+N Type F 20 A 300 mA

ABB FS401MK-C20/0.3 is a SMISSLINE TP 1P+N Type F short-time-delayed RCBO with a 20 A C-curve rating, 300 mA residual-current sensitivity and 10 kA breaking capacity for single-phase circuit protection.

SKU: 2CCG001708R0001Alt SKU: FS401MKC200.3MPN: 2CCG001708R0001
Price
List Price £260.24 ex VAT
Your Price (ex VAT) Save 35%
£169.16 35% OFF
You save £91.08 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £169.16
Trade pricing is personalised to your account

Manufacturer Lead Time

£169.16

Why Choose the ABB FS401MK-C20/0.3 RCBO?

The ABB FS401MK-C20/0.3 is a compact and dependable 1P+N residual current circuit breaker with overcurrent protection (RCBO) designed for the ABB SMISSLINE TP plug-in distribution system. Combining overload, short-circuit and residual-current protection in a single device, it provides comprehensive protection for single-phase circuits in residential, commercial and industrial electrical installations.

As part of the ABB FS401M-K series, this RCBO provides protection against the effects of sinusoidal alternating and pulsating DC earth-fault currents. Its Type F short-time-delayed characteristic provides increased resistance to unwanted tripping, helping achieve an effective balance between electrical safety and continuity of service with resistive, inductive and modern electronically controlled loads.

With a rated current of 20 A, a C tripping characteristic and a rated residual operating current of 300 mA, the FS401MK-C20/0.3 provides combined circuit and residual-current protection in a compact two-module format. It has a rated short-circuit breaking capacity of 10 kA according to IEC/EN 61009-1 and connects directly to the SMISSLINE TP plug-in system for efficient installation and maintenance.

Key Advantages

  • Combines residual-current, overload and short-circuit protection in one compact device.
  • 20 A rated current with C-curve overcurrent characteristic.
  • 300 mA residual-current sensitivity for earth-fault and preventive fire protection applications.
  • Type F short-time-delayed protection with increased resistance to unwanted tripping.
  • 10 kA rated breaking capacity according to IEC/EN 61009-1.
  • Suitable for the protection and isolation of resistive and inductive loads.
  • Direct plug-in installation into the ABB SMISSLINE TP system.

Key Features

  • ABB FS401M-K RCBO series.
  • 1P+N configuration for single-phase circuits.
  • 20 A rated current.
  • C tripping characteristic.
  • 300 mA rated residual operating current.
  • Type F residual-current characteristic.
  • Short-time-delayed operation for improved continuity of service.
  • 10 kA rated short-circuit breaking capacity according to IEC/EN 61009-1.
  • Protection against overload, short circuit and residual earth-fault currents.
  • Two-module format for compact distribution-board installation.
  • Plug-in connection for rapid installation and replacement within SMISSLINE TP assemblies.

Reliable Circuit Protection for SMISSLINE TP

An RCBO combines the functions of a miniature circuit breaker and residual-current protective device in a single unit. The ABB FS401MK-C20/0.3 therefore protects single-phase circuits against overload and short-circuit currents while detecting residual currents caused by insulation faults and earth leakage.

The FS401M-K series is engineered to provide an effective balance between safety and continuity of service. Its Type F short-time-delayed residual-current protection offers enhanced resistance to unwanted tripping, while the SMISSLINE TP plug-in architecture enables compatible protective devices to be installed quickly and efficiently in modular electrical distribution systems.

Typical Applications

  • ABB SMISSLINE TP electrical distribution systems.
  • Single-phase final circuit protection.
  • Commercial and industrial distribution boards.
  • Residential electrical distribution installations.
  • Protection and isolation of resistive and inductive loads.
  • Circuits containing modern electronic and frequency-controlled equipment.
  • Applications requiring combined overload, short-circuit, residual-current and preventive fire protection.

Technical Specifications

Product group SMISSLINE Plug-in System
Series FS401M-K
ABB order code 2CCG001708R0001
EAN / GTIN 7612271521776
Product type Residual current circuit breaker with overcurrent protection (RCBO)
Poles 1P+N
Total number of poles 2
Rated current 20 A
Tripping characteristic C
Residual-current type Type F, short-time delayed
Rated residual operating current 300 mA
Rated breaking capacity Icn 10 kA according to IEC/EN 61009-1
Number of modules 2
Mounting type SMISSLINE TP plug-in
Installation depth 78 mm
Dimensions (H × W × D) approx. 91 × 36 × 68 mm
Protection rating IP20
Pollution degree 2
Product standard IEC/EN 61009-1
Weight approx. 0.2 kg

Frequently Asked Questions

What is the ABB FS401MK-C20/0.3 used for?

It is a 1P+N RCBO designed to protect single-phase circuits against overloads, short circuits and residual earth-fault currents within ABB SMISSLINE TP distribution systems.

What is the rated current of the FS401MK-C20/0.3?

The RCBO has a rated current of 20 A and uses a C tripping characteristic.

What residual-current sensitivity does this RCBO provide?

The FS401MK-C20/0.3 has a rated residual operating current of 300 mA and uses a Type F short-time-delayed residual-current characteristic.

What is the breaking capacity of the ABB FS401MK-C20/0.3?

The device has a rated short-circuit breaking capacity of 10 kA according to IEC/EN 61009-1.

How is the FS401MK-C20/0.3 installed?

The RCBO is designed for direct plug-in installation in the ABB SMISSLINE TP system, simplifying installation, circuit configuration and maintenance in compatible electrical distribution assemblies.

Trusted ABB Circuit Protection

ABB SMISSLINE TP protective devices combine modular plug-in installation with dependable circuit protection, helping electrical designers and installers create flexible and efficient distribution systems for residential, commercial and industrial applications.