Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB FS401MK-C13/0.03 is a 13 A 1P+N Type C RCBO with Type F 30 mA short-time delayed residual-current protection and 10 kA breaking capacity for ABB SMISSLINE TP plug-in distribution systems.
£169.16
The ABB FS401MK-C13/0.03 is a high-performance residual current circuit breaker with overcurrent protection (RCBO) designed to protect single-phase final circuits against overloads, short circuits and earth leakage faults. As part of the ABB SMISSLINE TP plug-in system, it combines overcurrent and residual-current protection in a compact 1P+N protective device for residential, commercial and industrial electrical installations.
This RCBO has a rated current of 13 A, a Type C overcurrent tripping characteristic and 30 mA residual-current sensitivity. Its Type F residual-current characteristic provides protection against sinusoidal AC and pulsating DC residual currents and is designed to handle mixed-frequency residual currents associated with modern electronic loads, while its short-time delayed characteristic provides increased resistance to unwanted tripping.
With a rated operational voltage of 240 V AC and a 10 kA rated short-circuit breaking capacity according to IEC/EN 61009-1, the FS401MK-C13/0.03 provides robust protection in a compact two-module format. Its plug-in construction enables direct integration with compatible ABB SMISSLINE TP socket systems, while DTI functionality assists with identification of residual-current tripping during inspection and fault finding.
The ABB FS401MK-C13/0.03 combines overload, short-circuit and residual-current protection in one compact device. Its Type F residual-current characteristic is suitable for circuits where modern electronic equipment can generate residual-current waveforms containing frequency components beyond conventional mains-frequency fault currents, while also providing protection against sinusoidal alternating and pulsating direct residual currents.
The FS401MK range incorporates short-time delayed operation and resistance to unwanted tripping to provide an effective compromise between safety and continuity of service. Combined with 30 mA residual-current sensitivity and ABB's SMISSLINE TP plug-in architecture, the FS401MK-C13/0.03 is well suited to residential, commercial and industrial circuits supplying resistive, inductive and electronically controlled loads.
| Series | FS401MK / SMISSLINE TP |
|---|---|
| ABB order code | 2CCG001699R0001 |
| EAN / GTIN | 7612271521684 |
| Product type | Residual current circuit breaker with overcurrent protection (RCBO) |
| Rated current | 13 A |
| Number of poles | 1P+N / 2 poles total |
| Protected poles | 1 |
| Overcurrent tripping characteristic | Type C |
| Residual-current type | Type F |
| Rated residual current | 30 mA |
| Operating characteristic | Short-time delayed / high immunity |
| Rated operational voltage | 240 V AC |
| Rated insulation voltage | 500 V |
| Rated short-circuit breaking capacity | 10 kA according to IEC/EN 61009-1 |
| Protection rating | IP20 |
| Dimensions (H × W × D) | 91 × 36 × 78 mm |
| Width | 2 modules / 36 mm |
| Weight | approx. 0.2 kg |
| Standard | IEC/EN 61009-1 |
| System | SMISSLINE TP plug-in system |
The FS401MK-C13/0.03 protects single-phase final circuits against overloads, short circuits and residual earth fault currents, with Type F protection and short-time delayed operation providing increased resistance to unwanted tripping.
The ABB FS401MK-C13/0.03 has a rated current of 13 A and a Type C overcurrent tripping characteristic.
The FS401MK-C13/0.03 provides Type F residual-current protection with a rated residual operating current of 30 mA and short-time delayed, high-immunity operation.
The FS401MK-C13/0.03 has a rated short-circuit breaking capacity of 10 kA according to IEC/EN 61009-1.
The ABB order code for the FS401MK-C13/0.03 is 2CCG001699R0001.
ABB SMISSLINE TP RCBOs combine residual-current and overcurrent protection with a flexible plug-in architecture, while FS401MK Type F variants provide enhanced continuity of service for circuits incorporating modern electronic, resistive and inductive loads.
We use cookies