Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB FS401MKB160.03 (FS401MK-B16/0.03) is a 16 A 1P+N B characteristic Type F RCBO with 30 mA residual current sensitivity, 240 V AC rating and 10 kA breaking capacity for ABB SMISSLINE TP systems.
£152.26
The ABB FS401MKB160.03, type code FS401MK-B16/0.03, is a compact 1P+N Type F residual current circuit breaker with overcurrent protection (RCBO) designed for the ABB SMISSLINE TP plug-in system. It combines protection against overloads, short circuits and residual earth fault currents in one modular protective device for single-phase circuits in residential, commercial and industrial installations.
This RCBO has a 16 A rated current, B tripping characteristic and 30 mA Type F residual current sensitivity. ABB specifies the FS401MK range for protection against sinusoidal AC, pulsating DC and mixed-frequency residual currents, making it suitable for modern single-phase electronic loads and equipment incorporating frequency-controlled electronics. The 30 mA sensitivity also provides additional protection against direct contact.
With a rated operational voltage of 240 V AC and a 10 kA rated short-circuit breaking capacity according to EN 61009-1, the FS401MK-B16/0.03 provides robust combined protection in a compact two-module format. Its direct SMISSLINE TP plug-in connection supports efficient installation, replacement and flexible circuit configuration within compatible ABB distribution assemblies.
The ABB FS401MK-B16/0.03 combines miniature circuit breaker and Type F residual current protective functions in a single device. It protects single-phase circuits against overload and short-circuit currents while monitoring for earth leakage, with its 30 mA residual current sensitivity providing protection against indirect contact and additional protection against direct contact.
Type F residual current detection extends protection to mixed-frequency residual currents that can arise from modern single-phase electronic equipment. Combined with its B characteristic, 10 kA Icn rating, 3 kA surge current capability and SMISSLINE TP plug-in architecture, the FS401MK-B16/0.03 provides dependable protection with efficient system integration and maintenance.
| Product group | SMISSLINE Plug-in System |
|---|---|
| Series | FS401MK |
| Model / type code | FS401MK-B16/0.03 |
| SKU | FS401MKB160.03 |
| ABB order code | 2CCG001693R0001 |
| Product type | Residual current circuit breaker with overcurrent protection (RCBO) |
| Application | Single-phase circuit protection |
| Pole configuration | 1P+N |
| Number of poles | 2 |
| Number of protected poles | 1 |
| Rated current | 16 A |
| Overcurrent tripping characteristic | B |
| Residual current type | Type F |
| Rated residual current | 30 mA |
| Rated operational voltage | 240 V AC |
| Rated insulation voltage | 500 V |
| Rated impulse withstand voltage | 4 kV |
| Dielectric test voltage | 2500 V |
| Frequency | 50/60 Hz |
| Rated short-circuit breaking capacity (Icn) | 10 kA according to EN 61009-1 |
| Breaking capacity according to IEC 60947-2 | 25 kA |
| Rated residual breaking capacity | 10 kA |
| Rated service short-circuit breaking capacity | 15 kA at 240 V AC |
| Standards | IEC/EN 61009-1, IEC/EN 61009-2-1 and IEC/EN 62423 |
| Energy limiting class | 3 |
| Maximum surge current | 3 kA |
| Power loss | 2.7 W |
| Electrical endurance | 10,000 cycles |
| Overvoltage category | III |
| Pollution degree | 2 |
| Protection rating | IP20 |
| Operating ambient temperature | −25 to +60 °C |
| Width | 2 modules / 36 mm |
| Height | 91 mm |
| Depth | 78 mm |
| Flexible conductor capacity | 0.75–25 mm² |
| Multi-wired conductor capacity | 0.75–35 mm² |
| Tightening torque | 2.8 N·m |
| Neutral terminal position | Right |
| Installation position | Any |
| Installation system | ABB SMISSLINE TP plug-in system |
| EAN / GTIN | 7612271521622 |
| Product net weight | 0.2 kg |
| Pack unit | 1 piece |
The ABB FS401MKB160.03 is a 16 A 1P+N Type F RCBO for protecting single-phase circuits against overloads, short circuits and residual earth fault currents, including applications with modern electronic loads that can produce mixed-frequency residual currents.
The FS401MK-B16/0.03 has a rated current of 16 A and a B tripping characteristic.
Type F residual current protection is designed to respond to sinusoidal AC, pulsating DC and mixed-frequency residual currents associated with modern single-phase electronic equipment.
The FS401MK-B16/0.03 has a rated short-circuit breaking capacity (Icn) of 10 kA according to EN 61009-1 and a 25 kA breaking capacity according to IEC 60947-2 short-circuit testing.
It is designed for the ABB SMISSLINE TP plug-in system, allowing direct integration into compatible modular electrical distribution assemblies.
ABB FS401MK Type F RCBOs combine residual current and overcurrent protection with SMISSLINE TP plug-in technology, providing dependable protection for single-phase circuits including applications with modern electronic loads and mixed-frequency residual currents.
We use cookies