Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB FS401MK-B10/0.03 is a 10 A 1P+N Type B RCBO with Type F 30 mA short-time delayed residual-current protection and 10 kA breaking capacity for ABB SMISSLINE TP plug-in distribution systems.
£139.97
The ABB FS401MK-B10/0.03 is a high-performance residual current circuit breaker with overcurrent protection (RCBO) designed to protect single-phase circuits against overloads, short circuits and earth leakage faults. As part of the ABB SMISSLINE TP plug-in system, it combines overcurrent and residual-current protection in a compact 1P+N protective device for residential, commercial and industrial electrical installations.
This RCBO has a rated current of 10 A, a Type B overcurrent tripping characteristic and 30 mA residual-current sensitivity. Its Type F residual-current protection is designed for mixed-frequency residual currents and incorporates short-time delayed, high-immunity characteristics that improve resistance to unwanted tripping while maintaining dependable earth fault protection.
With a 10 kA rated short-circuit breaking capacity according to IEC/EN 61009-1, the FS401MK-B10/0.03 provides robust circuit protection in a compact two-module format. Its plug-in construction enables straightforward integration with compatible ABB SMISSLINE TP distribution systems, while DTI functionality assists with identification of residual-current tripping during inspection and fault finding.
The ABB FS401MK-B10/0.03 combines overload, short-circuit and residual-current protection in one compact device. Its Type F residual-current characteristic extends protection to mixed-frequency residual currents and is particularly useful where connected electronic equipment or variable-frequency loads can produce residual-current components beyond conventional mains-frequency fault currents.
The FS401MK range also incorporates short-time delayed, high-immunity residual-current operation to improve continuity of service by increasing resistance to unwanted tripping. Combined with 30 mA residual-current sensitivity and ABB's SMISSLINE TP plug-in architecture, this makes the RCBO suitable for demanding residential, commercial and industrial distribution applications.
| Series | FS401MK / SMISSLINE TP |
|---|---|
| ABB order code | 2CCG001691R0001 |
| EAN / GTIN | 7612271521608 |
| Product type | Residual current circuit breaker with overcurrent protection (RCBO) |
| Rated current | 10 A |
| Number of poles | 1P+N / 2 poles total |
| Protected poles | 1 |
| Neutral position | Right |
| Overcurrent tripping characteristic | Type B |
| Residual-current type | Type F |
| Rated residual current | 30 mA |
| Operating characteristic | High immunity / short-time delayed |
| Rated short-circuit breaking capacity | 10 kA according to IEC/EN 61009-1 |
| Rated ultimate short-circuit breaking capacity | 10 kA |
| Rated service short-circuit breaking capacity at 240 V AC | 7.5 kA |
| Rated conditional short-circuit current | 10 kA |
| Maximum surge current | 3 kA |
| Rated impulse withstand voltage | 4 kV |
| Frequency | 50/60 Hz |
| Energy limiting class | 3 |
| Overvoltage category | III |
| Pollution degree | 2 |
| Protection rating | IP20 |
| Operating temperature | -25 to 40 °C |
| Solid conductor capacity | up to 35 mm² |
| Multi-wired conductor capacity | up to 35 mm² |
| Width | 2 modules / 36 mm |
| Height | 91 mm |
| Weight | approx. 0.2 kg |
| Standard | IEC/EN 61009-1 |
| System | SMISSLINE TP plug-in system |
The FS401MK-B10/0.03 protects single-phase circuits against overloads, short circuits and residual earth fault currents, with Type F high-immunity protection suited to circuits containing electronic, resistive or inductive loads.
The ABB FS401MK-B10/0.03 has a rated current of 10 A and a Type B overcurrent tripping characteristic.
The FS401MK-B10/0.03 provides Type F residual-current protection with a rated residual operating current of 30 mA and short-time delayed, high-immunity operation.
The FS401MK-B10/0.03 has a rated short-circuit breaking capacity of 10 kA according to IEC/EN 61009-1.
The ABB order code for the FS401MK-B10/0.03 is 2CCG001691R0001.
ABB SMISSLINE TP RCBOs combine residual-current and overcurrent protection with a flexible plug-in architecture, while Type F high-immunity variants provide enhanced continuity of service for circuits with modern electronic and mixed-frequency loads.