Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB FS401MKB60.03 (FS401MK-B6/0.03) is a 6 A 1P+N B characteristic Type F high-immunity RCBO with 30 mA residual current sensitivity, 240 V AC rating and 10 kA breaking capacity for ABB SMISSLINE TP systems.
£139.97
The ABB FS401MKB60.03, type code FS401MK-B6/0.03, is a compact 1P+N Type F residual current circuit breaker with overcurrent protection (RCBO) for the ABB SMISSLINE TP plug-in system. It combines protection against overloads, short circuits and residual earth fault currents in one modular protective device for single-phase circuits in residential, commercial and industrial installations.
This RCBO has a 6 A rated current, B tripping characteristic and 30 mA Type F residual current sensitivity. Type F protection is designed for mixed-frequency residual currents associated with modern single-phase electronic loads and inverters, while also detecting sinusoidal AC and pulsating DC residual currents. Its short-time-delayed, high-immunity characteristic provides increased resistance to unwanted tripping while maintaining 30 mA additional protection.
With a rated operational voltage of 240 V AC and a 10 kA rated short-circuit breaking capacity according to EN 61009-1, the FS401MK-B6/0.03 provides robust combined protection in a compact two-module format. Direct connection to the SMISSLINE TP plug-in system supports efficient installation, replacement and flexible circuit configuration within compatible ABB distribution assemblies.
The ABB FS401MK-B6/0.03 combines miniature circuit breaker and Type F residual current protective functions in one device. It protects single-phase circuits against overload and short-circuit currents while monitoring for earth leakage, and its 30 mA sensitivity provides additional protection against direct contact as well as protection against indirect contact.
Type F technology makes the RCBO particularly suitable for modern single-phase electronic equipment and circuits supplying inverters where mixed-frequency residual currents can occur. The short-time-delayed high-immunity characteristic helps resist unwanted tripping, while the B characteristic, 10 kA Icn rating and SMISSLINE TP plug-in architecture provide dependable protection and efficient system integration.
| Product group | SMISSLINE Plug-in System |
|---|---|
| Series | FS401MK |
| Model / type code | FS401MK-B6/0.03 |
| SKU | FS401MKB60.03 |
| ABB order code | 2CCG001690R0001 |
| Product type | Residual current circuit breaker with overcurrent protection (RCBO) |
| Application | Single-phase circuit protection |
| Pole configuration | 1P+N |
| Number of poles | 2 |
| Number of protected poles | 1 |
| Rated current | 6 A |
| Overcurrent tripping characteristic | B |
| Residual current type | Type F |
| Rated residual current | 30 mA |
| Residual current characteristic | Short-time delayed / high immunity |
| Rated operational voltage | 240 V AC |
| Rated insulation voltage | 500 V |
| Rated impulse withstand voltage | 4 kV |
| Frequency | 50/60 Hz |
| Rated short-circuit breaking capacity (Icn) | 10 kA according to EN 61009-1 |
| Rated ultimate short-circuit breaking capacity (Icu) | 25 kA according to IEC 60947-2 |
| Rated service short-circuit breaking capacity (Ics) | 7.5 kA at 240 V AC |
| Rated residual breaking capacity | 10 kA |
| Standards | IEC/EN 61009-1, IEC/EN 61009-2-1 and IEC/EN 62423 |
| Energy limiting class | 3 |
| Maximum surge current | 3 kA |
| Power loss | 1.9 W |
| Overvoltage category | III |
| Pollution degree | 2 |
| Protection rating | IP20 |
| Operating ambient temperature | −25 to +40 °C |
| Width | 2 modules / 36 mm |
| Neutral terminal position | Right |
| Installation system | ABB SMISSLINE TP plug-in system |
| EAN / GTIN | 7612271521592 |
| Product weight | 0.2 kg |
| Pack unit | 1 piece |
The ABB FS401MKB60.03 is a 6 A 1P+N Type F RCBO for protecting single-phase circuits against overloads, short circuits and residual earth fault currents, with particular suitability for circuits supplying modern electronic loads and single-phase inverters.
The FS401MK-B6/0.03 has a rated current of 6 A and a B tripping characteristic.
Type F residual current protection is designed to detect residual currents associated with single-phase electronic loads and frequency-controlled equipment, including mixed-frequency residual currents, while also responding to conventional AC and pulsating DC residual currents.
The FS401MK-B6/0.03 has a rated short-circuit breaking capacity (Icn) of 10 kA according to EN 61009-1.
It is designed for the ABB SMISSLINE TP plug-in system, allowing direct integration into compatible modular electrical distribution assemblies.
ABB FS401MK Type F RCBOs combine residual current and overcurrent protection with high-immunity operation and SMISSLINE TP plug-in technology, providing dependable protection for single-phase circuits including applications with electronic loads, inverters and mixed-frequency residual currents.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.