ABB DS802P-C125/0.3AS is a 2-pole 125 A C-curve selective Type AS RCBO with 300 mA residual current sensitivity and 50 kA breaking capacity for industrial circuit protection.
£669.86
The ABB DS802P-C125/0.3AS is a high-performance 2-pole residual current circuit breaker with overcurrent protection (RCBO) designed to provide combined protection against overloads, short circuits and earth leakage faults in demanding industrial electrical installations. As part of the ABB DS800P series, it combines a rated current of 125 A, C tripping characteristic and selective Type AS residual current protection in a single protective device.
This RCBO provides protection against overload and short-circuit currents together with residual current protection for AC and pulsating DC earth fault currents. Its selective residual current operation incorporates an intentional time delay, supporting discrimination with suitable downstream residual current protective devices and helping improve continuity of supply in coordinated installations.
With a rated residual operating current of 300 mA and an ultimate short-circuit breaking capacity of 50 kA to IEC/EN 60947-2, the DS802P-C125/0.3AS is engineered for industrial distribution systems requiring high fault-current performance and dependable selective protection.
RCBOs combine residual current protection with overload and short-circuit protection in a single device. This integrated approach simplifies electrical protection arrangements while helping protect circuits, equipment and installations against multiple common fault conditions.
The selective Type AS functionality of the DS802P-C125/0.3AS introduces a defined operating delay for residual current faults. In correctly coordinated installations, this allows suitable downstream residual current devices to clear local faults first, helping reduce unnecessary interruption to upstream circuits.
| Series | DS800P |
|---|---|
| ABB order code | 2CCG001334R0001 |
| Product type | Residual current circuit breaker with overcurrent protection (RCBO) |
| Number of poles | 2 |
| Rated current | 125 A |
| Tripping characteristic | C |
| Residual current type | Type AS, selective |
| Rated residual operating current (IΔn) | 300 mA |
| Ultimate short-circuit breaking capacity (Icu) | 50 kA |
| Rated voltage | 240 / 415 V AC |
| Standard | IEC/EN 60947-2 |
| Application | Industrial electrical distribution |
The DS802P-C125/0.3AS provides combined protection against overload, short-circuit and residual earth fault currents in industrial electrical installations.
The RCBO has a rated current of 125 A with a C tripping characteristic.
The DS802P-C125/0.3AS has a rated residual operating current of 300 mA and provides selective Type AS residual current protection.
The device has an ultimate short-circuit breaking capacity (Icu) of 50 kA according to IEC/EN 60947-2.
Selective Type AS operation incorporates an intentional time delay, supporting discrimination with suitable downstream residual current devices and helping minimise unnecessary interruption of upstream circuits.
ABB DS800P residual current circuit breakers with overcurrent protection are engineered for demanding industrial installations, combining high short-circuit performance with dependable overload, earth fault and selective circuit protection.