Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB DS804P-B125/0.3AS is a 125 A four-pole B-characteristic Type AS selective RCBO with 300 mA residual-current sensitivity and 50 kA ultimate short-circuit breaking capacity for industrial circuit protection.
£970.00
The ABB DS804P-B125/0.3AS is a high-performance four-pole residual current circuit breaker with overcurrent protection (RCBO) designed for demanding industrial electrical installations. Part of the ABB DS800P high-performance protection range, it combines overload, short-circuit and residual-current protection in one device, with a 125 A rated current, B tripping characteristic and 300 mA rated residual operating current.
This model uses ABB's Type AS selective residual-current characteristic. It is pulse-current sensitive and incorporates an intentional tripping delay, allowing residual-current selectivity with suitable downstream instantaneous protective devices. This makes it particularly useful in industrial distribution systems where coordinated protection and continuity of supply are important.
With four protected poles, a rated operational voltage up to 690 V AC and an ultimate short-circuit breaking capacity of 50 kA at 415 V AC, the DS804P-B125/0.3AS provides robust protection for demanding three-phase distribution circuits. It is designed to IEC/EN 60947-2 for industrial applications.
The ABB DS804P-B125/0.3AS combines thermal and magnetic overcurrent protection with residual-current monitoring, allowing one device to protect against overload currents, short circuits and earth-fault currents. Its high short-circuit breaking capacity supports use in industrial systems with substantial prospective fault levels.
The Type AS characteristic incorporates intentional residual-current tripping delay. This enables selective coordination with suitable downstream instantaneous residual-current devices so that a downstream fault can be cleared locally without unnecessarily disconnecting a larger upstream section of the installation.
| Series | DS800P |
|---|---|
| SKU | DS804PB1250.3AS |
| ABB order code | 2CCG001326R0001 |
| Product group | S800 / S800P / S750 MCB |
| Product type | Residual current circuit breaker with overcurrent protection (RCBO) |
| Number of poles | 4 |
| Protected poles | 4 |
| Rated current | 125 A |
| Tripping characteristic | B |
| Residual-current characteristic | Type AS, selective |
| Rated residual operating current | 300 mA |
| Rated operational voltage | Up to 690 V AC |
| Rated frequency | 50–60 Hz |
| Ultimate short-circuit breaking capacity (Icu) | 50 kA at 415 V AC |
| Service short-circuit breaking capacity (Ics) | 40 kA at 240 / 415 V AC |
| Standard | IEC/EN 60947-2 |
| Application | Industrial |
| Dimensions (H × W × D) | approx. 108.2 × 227.5 × 82.3 mm |
The ABB DS804P-B125/0.3AS provides combined overload, short-circuit and residual-current protection for demanding industrial electrical circuits.
The DS804P-B125/0.3AS has a rated current of 125 A.
The device has a rated residual operating current of 300 mA.
Type AS denotes pulse-current-sensitive selective residual-current protection with an intentional tripping delay, allowing coordination with suitable downstream instantaneous residual-current devices.
The DS804P-B125/0.3AS has an ultimate short-circuit breaking capacity Icu of 50 kA at 415 V AC.
The DS804P-B125/0.3AS is a four-pole RCBO with four protected poles.
The ABB order code is 2CCG001326R0001.
ABB DS800P high-performance RCBOs are designed for demanding industrial power distribution systems where dependable overcurrent protection, residual-current protection, high breaking capacity and selective coordination are required.