ABB DS803P-C125/0.3A is a 125 A three-pole Type A RCBO with C-characteristic overcurrent protection and a 300 mA rated residual operating current for combined residual-current, overload and short-circuit protection.
£669.86
The ABB DS803P-C125/0.3A is a high-performance 3-pole residual current circuit breaker with overcurrent protection (RCBO) designed to combine overload, short-circuit and residual-current protection in a single device. It features a 125 A rated current, C-characteristic overcurrent protection and a 300 mA rated residual operating current.
As a Type A RCBO, the DS803P-C125/0.3A is designed to detect residual sinusoidal AC currents as well as pulsating DC residual currents. This makes it suitable for demanding electrical installations where combined overcurrent and earth-leakage protection is required.
The three-pole construction makes the DS803P-C125/0.3A particularly suitable for industrial and commercial three-phase circuits. Its C tripping characteristic provides tolerance of moderate starting and inrush currents, making it appropriate for many machinery, equipment and distribution applications.
The ABB DS803P-C125/0.3A combines residual-current protection and overcurrent circuit protection within one device. Its C-characteristic overcurrent protection safeguards the circuit against overload and short-circuit conditions while accommodating moderate temporary starting currents, and the residual-current function detects earth-leakage fault currents.
With a 300 mA residual operating current and Type A detection characteristic, the device can respond to sinusoidal AC and pulsating DC residual currents. Its 125 A rating and three-pole configuration make it suitable for demanding three-phase distribution and equipment circuits where integrated protection is required.
| Series | DS800P |
|---|---|
| ABB order code | 2CCG001315R0001 |
| Product type | Residual current circuit breaker with overcurrent protection (RCBO) |
| Number of poles | 3 |
| Rated current | 125 A |
| Overcurrent tripping characteristic | C |
| Residual-current type | A |
| Rated residual operating current | 300 mA |
| Protection functions | Residual current, overload and short-circuit protection |
| Mounting type | DIN rail |
The DS803P-C125/0.3A is a three-pole RCBO that combines residual-current protection with overload and short-circuit protection in a single device.
The DS803P-C125/0.3A has a rated current of 125 A.
The device uses a Type C overcurrent tripping characteristic, making it suitable for circuits where moderate starting or inrush currents can occur.
It is a Type A RCBO with a rated residual operating current of 300 mA, designed to detect sinusoidal AC and pulsating DC residual currents.
The ABB order code is 2CCG001315R0001.
ABB high-performance circuit protection devices are designed for demanding electrical installations where dependable protection against overcurrent and residual-current faults is required.