Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB S802P-K100 high-performance two-pole miniature circuit breaker with a 100 A rated current, Type K tripping characteristic and 50 kA rated ultimate short-circuit breaking capacity at 415 V AC for demanding commercial and industrial circuit protection.
£173.60
The ABB S802P-K100 is a high-performance two-pole miniature circuit breaker (MCB) designed to protect electrical circuits against overload and short-circuit conditions. As part of the ABB S800P high-performance circuit breaker series, it is engineered for demanding commercial and industrial installations where high short-circuit breaking capacity and dependable circuit protection are required.
The S802P-K100 combines thermal overload protection with electromagnetic short-circuit protection. Its Type K tripping characteristic is particularly suited to circuits such as motors, transformers and auxiliary circuits, offering resistance to unwanted tripping from functional peak currents while providing sensitive protection in the overcurrent range.
With a rated current of 100 A, two protected poles and a rated ultimate short-circuit breaking capacity (Icu) of 50 kA at 415 V AC, the S802P-K100 provides robust protection for demanding distribution systems. The S800P range is also suitable where selectivity with an upstream MCCB or back-up protection for downstream MCBs is required.
High-performance miniature circuit breakers such as the ABB S802P-K100 automatically disconnect electrical circuits when excessive current occurs. Thermal protection responds to sustained overload conditions, while electromagnetic protection provides rapid operation during short-circuit conditions, helping protect cables, conductors and connected equipment from damaging fault currents.
The Type K characteristic is designed for applications such as motors, transformers and auxiliary circuits where functional current peaks can occur during normal operation. Combined with a 100 A rated current and 50 kA ultimate breaking capacity at 415 V AC, the S802P-K100 provides high-performance protection while helping reduce nuisance tripping in demanding commercial and industrial systems.
Tick the specs you need, then view products that match.
| Certification | UL 1077 | |
|---|---|---|
| Series | S800P | |
| SKU | S802PK100 | |
| ABB order code | 2CCG001254R0001 | |
| GTIN / EAN | 7612271517236 | |
| ABB product group | S800 / S800P / S750 MCB | |
| Product type | High-performance miniature circuit breaker (MCB) | |
| Rated current | 100 A | |
| Number of poles | 2 | |
| Number of protected poles | 2 | |
| Tripping characteristic | K | |
| Rated operational voltage | 690 V AC according to IEC 60947-2 | |
| Rated ultimate short-circuit breaking capacity (Icu) | 50 kA at 415 V AC | |
| Icu at 440 V AC | 30 kA | |
| Icu at 500 V AC | 10 kA | |
| Icu at 690 V AC | 4.5 kA | |
| Icu at 250 V DC | 30 kA | |
| Rated service short-circuit breaking capacity (Ics) | 40 kA at 240 / 415 V AC | |
| Rated insulation voltage (Ui) | 690 V | |
| Rated impulse withstand voltage (Uimp) | 6 kV | |
| Rated frequency | 50/60 Hz | |
| Pollution degree | 3 | |
| Protection rating | IP20 | |
| Operating temperature | −25 to +60 °C | |
| Power loss | 16 W total, 8 W per pole at rated operating conditions | |
| Tightening torque | 3.5 N·m | |
| Contact position indication | ON / OFF / TRIP | |
| Standards | IEC/EN 60947-2, UL 1077 | |
| Dimensions (H × W × D) | 95 × 54 × 82.5 mm | |
| Weight | 0.49 kg |
The ABB S802P-K100 is a high-performance two-pole miniature circuit breaker designed to protect commercial and industrial circuits against overload and short-circuit conditions, with its Type K characteristic making it particularly suitable for motors, transformers and auxiliary circuits.
The S802P-K100 has a rated current of 100 A and features two protected poles.
The Type K tripping characteristic is designed for circuits that can experience functional peak currents, such as motors and transformers. ABB specifies resistance to nuisance tripping from functional current peaks up to 10 × In, while the sensitive thermal trip provides effective overcurrent protection.
The S802P-K100 has a rated ultimate short-circuit breaking capacity (Icu) of 50 kA at 415 V AC. Its Icu is also 30 kA at 440 V AC, 10 kA at 500 V AC, 4.5 kA at 690 V AC and 30 kA at 250 V DC.
The ABB S802P-K100 is designed in accordance with IEC/EN 60947-2 and is also specified to UL 1077.
ABB S800P high-performance miniature circuit breakers provide dependable overload and short-circuit protection for demanding commercial and industrial installations, combining high breaking capacity with protection characteristics engineered for a wide range of electrical loads.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.