2CCG000413R0001 ABB S401P-K4 MCB 40kA 1P Type K 4A

2CCG000413R0001 ABB S401P-K4 MCB 40kA 1P Type K 4A

ABB S401P-K4 is a 4 A Type K 1-pole miniature circuit breaker with 40 kA ultimate short-circuit breaking capacity, designed for overload and short-circuit protection in SMISSLINE TP plug-in distribution systems.

SKU: 2CCG000413R0001Alt SKU: S401PK4MPN: 2CCG000413R0001
Price
List Price £50.36 ex VAT
Your Price (ex VAT) Save 35%
£32.73 35% OFF
You save £17.63 per unit
Manufacturer Lead Time Estimated Delivery 7 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £32.73
Trade pricing is personalised to your account

Manufacturer Lead Time

£32.73

Why Choose the ABB S401P-K4 Miniature Circuit Breaker?

The ABB S401P-K4 is a high-performance 1-pole miniature circuit breaker (MCB) designed to provide reliable overload and short-circuit protection in commercial and industrial electrical distribution systems. Part of the ABB S400P range for the SMISSLINE TP plug-in system, it combines current-limiting circuit protection with a compact plug-in format for compatible distribution assemblies.

The S401P-K4 uses thermal overload protection together with electromagnetic short-circuit protection to safeguard cables, conductors and connected equipment. Its Type K tripping characteristic, specified according to IEC/EN 60947-2, is particularly useful for circuits where higher starting or inrush currents may occur without requiring premature magnetic tripping.

With a rated current of 4 A, a 1-pole configuration and a rated ultimate short-circuit breaking capacity of 40 kA, the S401P-K4 provides robust protection in a compact format. ABB order code 2CCG000413R0001 and GTIN 7612271509835 identify this specific 4 A Type K version.

Key Advantages

  • High-performance 1-pole miniature circuit breaker for overload and short-circuit protection.
  • 4 A rated current for lower-current distribution, control and auxiliary circuits.
  • Type K tripping characteristic suitable for applications where higher starting or inrush currents can occur.
  • 40 kA ultimate short-circuit breaking capacity for demanding electrical installations.
  • Thermal overload and electromagnetic short-circuit protection mechanisms.
  • Compact 1-module construction helps minimise panel space requirements.
  • Plug-in construction designed specifically for the ABB SMISSLINE TP system.

Key Features

  • ABB S400P / SMISSLINE TP series.
  • 4 A rated current.
  • 1-pole configuration.
  • Type K tripping characteristic.
  • 40 kA rated ultimate short-circuit breaking capacity.
  • Type K characteristic according to IEC/EN 60947-2.
  • Current-limiting miniature circuit breaker design.
  • Direct plug-in installation within compatible SMISSLINE TP distribution assemblies.
  • Compact 18 mm width.
  • Approximate device weight of 115 g.

Reliable Type K Circuit Protection

The ABB S401P-K4 protects cables, conductors and connected equipment against damaging overload and short-circuit currents. Its thermal trip responds to sustained overload conditions, while the electromagnetic trip provides rapid disconnection during short-circuit faults. The Type K characteristic accommodates higher transient starting currents than characteristics intended primarily for low-inrush loads.

The ABB SMISSLINE TP plug-in architecture allows compatible protective devices to connect directly to the socket system, supporting efficient assembly, servicing and modification of electrical distribution installations. With its compact single-pole design, 4 A rating and 40 kA breaking capacity, the S401P-K4 is suited to professional control, auxiliary and distribution applications requiring Type K protection.

Typical Applications

  • Industrial electrical distribution systems.
  • Machine and automation control panels.
  • SMISSLINE TP plug-in distribution assemblies.
  • Commercial electrical distribution boards.
  • Control and auxiliary circuits.
  • Circuits with elevated starting or inrush currents.
  • Single-pole branch circuit overload and short-circuit protection.

Technical Specifications

Series S400P / SMISSLINE TP
ABB order code 2CCG000413R0001
EAN / GTIN 7612271509835
Product type Miniature circuit breaker (MCB)
Rated current 4 A
Number of poles 1
Tripping characteristic Type K
Rated ultimate short-circuit breaking capacity 40 kA
Standard IEC/EN 60947-2
Mounting system SMISSLINE TP plug-in system
Module width 1 module
Width 18 mm
Height 85 mm
Depth 91 mm
Weight approx. 115 g
Pack unit 10 pieces

Frequently Asked Questions

What is the ABB S401P-K4 used for?

The ABB S401P-K4 is a 1-pole miniature circuit breaker designed to protect compatible electrical circuits against overload and short-circuit currents in ABB SMISSLINE TP distribution systems.

What is the rated current of the S401P-K4?

The ABB S401P-K4 has a rated current of 4 A.

What tripping characteristic does the S401P-K4 use?

The S401P-K4 uses a Type K tripping characteristic according to IEC/EN 60947-2, making it suitable for applications where higher starting or inrush currents can occur.

What is the breaking capacity of the ABB S401P-K4?

The S401P-K4 has a rated ultimate short-circuit breaking capacity of 40 kA.

Which mounting system is the S401P-K4 designed for?

The S401P-K4 is designed for the ABB SMISSLINE TP plug-in system, enabling direct installation within compatible SMISSLINE TP electrical distribution assemblies.

Trusted Circuit Protection from ABB

ABB SMISSLINE TP S400P miniature circuit breakers combine dependable overload and short-circuit protection with a practical plug-in architecture for professional commercial and industrial electrical distribution systems.