Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB F404A-LF63/0.03 is a 63 A four-pole Type A 30 mA RCCB designed for 16⅔ Hz low-frequency residual-current protection in SMISSLINE TP electrical distribution systems.
£595.39
The ABB F404A-LF63/0.03 is a specialised four-pole Type A residual current circuit breaker (RCCB) developed for the ABB SMISSLINE TP plug-in distribution system. Rated at 63 A with a residual operating current of 30 mA, it provides residual-current protection for three-phase circuits and is specifically designed for 16⅔ Hz low-frequency applications.
As a Type A RCCB, the F404A-LF63/0.03 provides detection of sinusoidal AC and pulsating DC residual currents. Its specialised low-frequency design makes it suitable for electrical systems operating at 16⅔ Hz, while the four-pole configuration enables switching and residual-current monitoring across three phases and neutral.
Designed as a directly pluggable device for the ABB SMISSLINE TP system, the F404A-LF63/0.03 combines specialised low-frequency residual-current protection with modular installation. Its 400 V AC rating, 1 kA rated residual making and breaking capacity and compact four-module format make it a practical protection device for specialised industrial and infrastructure distribution systems.
Residual current circuit breakers monitor the current flowing through the live conductors and disconnect the circuit when an earth-leakage imbalance reaches the device's operating threshold. The 30 mA sensitivity of the F404A-LF63/0.03 provides additional residual-current protection while its Type A characteristic responds to both sinusoidal AC and pulsating DC residual currents.
Unlike standard-frequency versions, the F404A-LF63/0.03 is specifically intended for 16⅔ Hz electrical systems. Combined with its four-pole arrangement and direct SMISSLINE TP integration, this specialised design makes it suitable for low-frequency three-phase distribution systems where reliable residual-current protection is required.
| Series | F404 LF |
|---|---|
| ABB order code | 2CCF544110E0631 |
| Product group | SMISSLINE Plug-in System |
| Product type | Residual current circuit breaker (RCCB) |
| Residual-current type | Type A |
| Rated current | 63 A |
| Rated residual operating current | 30 mA |
| Number of poles | 4 |
| Rated voltage | 400 V AC |
| Operational voltage range | 230–400 V AC |
| Frequency | 16⅔ Hz |
| Rated residual making and breaking capacity | 1 kA |
| Protection rating | IP20 |
| Operating temperature | -25 to +55 °C |
| Mounting type | SMISSLINE TP conductor bar / plug-in mounting |
| Standard | IEC/EN 61008 |
| Width | 72 mm |
| Height | 91 mm |
| Depth | 75 mm |
| Weight | 0.430 kg |
It is a specialised four-pole Type A RCCB designed to provide residual-current protection in 16⅔ Hz low-frequency ABB SMISSLINE TP electrical distribution systems.
The RCCB has a rated current of 63 A and a rated residual operating current of 30 mA.
The LF designation identifies the specialised low-frequency version of the F404 RCCB, designed for operation in 16⅔ Hz electrical systems.
The Type A characteristic is designed to detect sinusoidal AC and pulsating DC residual currents.
The ABB order code for this RCCB is 2CCF544110E0631.
ABB F404 LF residual current circuit breakers combine specialised 16⅔ Hz operation, Type A residual-current protection and direct SMISSLINE TP integration for dependable protection in low-frequency electrical distribution systems.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.