OT1600E12CP ABB 1600 A 3-Pole Manual Change-Over Switch

OT1600E12CP ABB 1600 A 3-Pole Manual Change-Over Switch

ABB OT1600E12CP is a 1600 A three-pole manual change-over switch with open-transition I-O-II operation, a mechanism between the poles and an included IP65 pistol handle for high-current three-phase power-source selection.

SKU: OT1600E12CPMPN: OT1600E12CP
Price
List Price £7,675.73 ex VAT
Your Price (ex VAT) Save 35%
£4,989.22 35% OFF
You save £2,686.51 per unit
Manufacturer Lead Time Estimated Delivery 6 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £4,989.22
Trade pricing is personalised to your account

Manufacturer Lead Time

£4,989.22

Why Choose the ABB OT1600E12CP Manual Change-Over Switch?

The ABB OT1600E12CP is a heavy-duty 1600 A three-pole manual change-over switch designed for controlled switching between two electrical power sources. Identified by ABB order code 1SCA103293R1001, it belongs to the ABB OT1600_C range and provides dependable manual source selection for high-current industrial and commercial power-distribution systems.

The OT1600E12CP provides I-O-II open-transition operation, with a defined OFF position between the two source positions. Its three-pole configuration is designed for three-phase applications, while the operating mechanism is positioned between the poles for a compact and practical switchboard arrangement.

Engineered for demanding electrical duties, the OT1600E12CP has a rated operational voltage of 1000 V, a conventional free-air thermal current of 1600 A and a rated short-time withstand current of 50 kA rms for 1 second. It is supplied with a black plastic IP65 I-O-II pistol-type handle, operating shaft and bolt set for cable connection.

Key Advantages

  • Heavy-duty 1600 A manual change-over switch for high-current applications.
  • Three-pole configuration for three-phase source-selection systems.
  • I-O-II open-transition operation provides a defined OFF position between sources.
  • Operating mechanism positioned between the poles.
  • Rated operational voltage of 1000 V.
  • 1600 A AC-21A and AC-22A operational ratings from 380–690 V.
  • High 50 kA for 1 s short-time withstand capability.
  • Supplied with an IP65 operating handle, shaft and cable-connection bolt set.

Key Features

  • ABB OT1600_C manual change-over switch.
  • 1600 A conventional free-air thermal current.
  • Three poles.
  • Manual I-O-II operation.
  • Open-transition source switching.
  • Front operated with mechanism between the poles.
  • Base mounting.
  • 1000 V rated operational voltage.
  • 1000 V rated insulation voltage.
  • 1600 A AC-23A at 380–500 V.
  • 1250 A AC-23A at 690 V.
  • 50 kA rms short-time withstand current for 1 s.
  • IP65 black plastic pistol-type operating handle included.
  • Handle padlockable in the OFF position.
  • Door interlocking in I and II positions and when padlocked.

Heavy-Duty Three-Pole Manual Source Change-Over

The ABB OT1600E12CP provides controlled manual source selection through an I-O-II open-transition sequence. The defined OFF position separates the two connected-source positions so that the active source is disconnected before the alternative source is connected, making the switch suitable for mains, generator and other alternative-source arrangements.

Its 1600 A three-pole construction, mechanism-between-poles configuration and 50 kA for 1 s short-time withstand capability make the OT1600E12CP suitable for substantial three-phase distribution systems. The supplied IP65 pistol handle, shaft and cable-connection hardware provide a coordinated ABB solution for professional switchboard integration.

Typical Applications

  • Manual mains and generator change-over systems.
  • Three-phase power-source selection.
  • High-current industrial switchboards.
  • Standby and alternative power systems.
  • Commercial building power distribution.
  • Infrastructure and critical-power installations.
  • Manufacturing and process-industry facilities.
  • OEM change-over and power-control panels.

Technical Specifications

Tick the specs you need, then view products that match.

Mounting Type Base mounting
Device Type Manual changeover switch
Operation Manual
Series OT1600_C
ABB order code 1SCA103293R1001
Product type Manual change-over switch
Rated current 1600 A
Number of poles 3
Switch positions I-O-II
Transition type Open transition
Operation Manual front operation
Operating mechanism Mechanism between the poles
Mounting Base mounting
Rated operational voltage 1000 V
Rated insulation voltage 1000 V
Conventional free-air thermal current 1600 A at 40 °C
Rated operational current AC-21A 1600 A at 380–415 V, 500 V and 690 V
Rated operational current AC-22A 1600 A at 380–415 V, 500 V and 690 V
Rated operational current AC-23A 1600 A at 380–415 V and 500 V; 1250 A at 690 V
Rated operational power AC-23A 400 kW at 220–240 V; 560 kW at 400–415 V; 900 kW at 500 V; 1200 kW at 690 V
Rated short-time withstand current 50 kA rms for 1 s
Power loss 48 W per pole
Terminal width 50 mm
Terminal tightening torque 50–75 Nm
Terminal arrangement Top-in/bottom-out or bottom-in/top-out
Front protection IP20
Operating handle Black plastic I-O-II pistol-type handle
Handle protection rating IP65
Padlocking OFF position
Included components Operating handle, shaft and bolt set for cable connection
Product net width 400 mm
Product net height 372 mm
Product net depth 309 mm
Product net weight approx. 51 kg
Standards IEC/EN 60947-1, IEC/EN 60947-3 and IEC/EN 60947-6-1
Product group OT Change over Switches

Frequently Asked Questions

What is the ABB OT1600E12CP?

The OT1600E12CP is an ABB 1600 A three-pole manual change-over switch designed for controlled manual selection between two electrical power sources.

What is the ABB order code for the OT1600E12CP?

The ABB order code for the OT1600E12CP is 1SCA103293R1001.

How many poles does the ABB OT1600E12CP have?

The OT1600E12CP has three poles and is designed for high-current three-phase source change-over applications.

What type of transition does the OT1600E12CP use?

The OT1600E12CP uses I-O-II open-transition switching, providing a defined OFF position between Source I and Source II.

Where is the operating mechanism positioned on the OT1600E12CP?

The OT1600E12CP has its operating mechanism positioned between the poles and is manually front operated.

What is the AC-23A rating of the ABB OT1600E12CP?

The switch is rated at 1600 A AC-23A at 380–500 V and 1250 A AC-23A at 690 V, with an AC-23A operational power rating of 560 kW at 400–415 V.

What is the short-time withstand current of the OT1600E12CP?

The ABB OT1600E12CP has a rated short-time withstand current of 50 kA rms for 1 second.

Is an operating handle supplied with the ABB OT1600E12CP?

Yes. The switch includes a black plastic IP65 I-O-II pistol-type handle, operating shaft and bolt set for cable connection. The handle is padlockable in the OFF position.