ABB MCCB 1sda054209r1-t4h 250 tmd 50-500 3 pole

ABB MCCB 1sda054209r1-t4h 250 tmd 50-500 3 pole

ABB 1SDA054209R1 SACE Tmax T4H 250 three-pole fixed moulded case circuit breaker with 50 A thermal magnetic TMD release and front terminals for industrial power distribution.

SKU: 1SDA054209R1Alt SKU: T4H 250 TMD 50-500 3p F FMPN: 1SDA054209R1
Price on application Contact us for pricing and availability.
Call 01708 343600

Why Choose the ABB 1SDA054209R1 Tmax T4H Moulded Case Circuit Breaker?

The ABB 1SDA054209R1 is a dependable Tmax T4H moulded case circuit breaker (MCCB) designed to protect low voltage electrical installations against overloads and short circuits. As part of the proven ABB SACE Tmax T series, it provides robust circuit protection for industrial switchboards, power distribution panels and OEM machinery applications.

This model features a 250 A frame size with a 50 A thermal magnetic TMD release, offering reliable protection for feeders, equipment and distribution circuits. Its fixed three-pole configuration with front terminal connections supports straightforward installation inside electrical panels and control cabinets.

With high short-circuit breaking performance, compact dimensions and ABB's recognised build quality, the ABB 1SDA054209R1 is suitable for demanding installations where safety, reliability and long service life are essential.

Key Advantages

  • Reliable ABB SACE Tmax T4H moulded case circuit breaker.
  • 50 A thermal magnetic TMD release within a 250 A frame.
  • Three-pole fixed MCCB for industrial power distribution.
  • High short-circuit breaking capacity for demanding installations.
  • Front terminal connections for practical panel installation.
  • Designed for overload and short-circuit protection.

Key Features

  • ABB SACE Tmax T series.
  • Model: T4H 250 TMD 50-500 3P F F.
  • Product ID: 1SDA054209R1.
  • 50 A rated current.
  • 250 A rated uninterrupted current.
  • Thermal magnetic TMD trip unit.
  • Fixed three-pole construction.
  • Front terminal connection type.
  • Rated operational voltage up to 690 V AC.
  • Suitable for switchboards, control panels and OEM machinery.

Reliable Protection for Industrial Power Distribution

The ABB Tmax T4H range is engineered to deliver consistent circuit protection in industrial and commercial electrical systems. It helps safeguard cables, equipment and connected loads by disconnecting circuits during overload or short-circuit conditions.

The thermal magnetic TMD release provides overload protection through its thermal element and rapid short-circuit response through its magnetic element. This makes the ABB 1SDA054209R1 a practical choice for panel builders and engineers requiring dependable protection in compact power distribution assemblies.

Typical Applications

  • Industrial switchboards and distribution panels.
  • Motor control centres.
  • OEM machinery and automation equipment.
  • Commercial power distribution systems.
  • Manufacturing and process control installations.
  • Electrical control cabinets and feeder circuits.

Technical Specifications

Tick the specs you need, then view products that match.

Current 50 A
Phase Three Phase
Poles 3-pole
Device Type MCCB
Breaking Capacity 100 kA
Trip Unit Thermal-magnetic
Manufacturer ABB
Series SACE Tmax T
Product ID 1SDA054209R1
Extended product type T4H 250 TMD 50-500 3P F F
Product type Moulded Case Circuit Breaker (MCCB)
Frame size T4H 250
Rated current (In) 50 A
Rated uninterrupted current (Iu) 250 A
Release type Thermal Magnetic (TMD)
Number of poles 3
Rated operational voltage Up to 690 V AC / 750 V DC
Rated insulation voltage (Ui) 1000 V
Rated impulse withstand voltage (Uimp) 8 kV
Rated ultimate short-circuit breaking capacity (Icu) Up to 100 kA at 230 V AC
Rated ultimate short-circuit breaking capacity at 415 V AC 70 kA
Terminal type Front terminals
Mounting Fixed
Electrical durability 8,000 cycles
Mechanical durability 20,000 cycles
Dimensions (H × W × D) Approx. 205 × 105 × 103.5 mm
Weight Approx. 2.35 kg
Standards IEC 60947

Frequently Asked Questions

What is the ABB 1SDA054209R1 used for?

The ABB 1SDA054209R1 is used to protect low voltage electrical circuits against overloads and short circuits in industrial and commercial distribution systems.

What current rating does this breaker provide?

This MCCB features a 50 A thermal magnetic TMD release within an ABB Tmax T4H 250 frame.

How many poles does the ABB 1SDA054209R1 have?

The breaker is supplied as a three-pole fixed moulded case circuit breaker.

What connection type does this MCCB use?

The ABB 1SDA054209R1 uses front terminal connections, making it suitable for installation in switchboards and control panels.

Where is this MCCB typically installed?

It is typically installed in industrial switchboards, motor control centres, distribution panels, OEM machinery and electrical control cabinets.

Trusted by Electrical Professionals Worldwide

ABB SACE Tmax moulded case circuit breakers are trusted by panel builders, electrical engineers and OEM manufacturers worldwide for robust protection, high breaking capacity and long-term reliability.