2TAZ265114R1104 ABB DSN201EMC10A10 DSN201E M C10 A10 RCBO 1P+N 10A 10mA

2TAZ265114R1104 ABB DSN201EMC10A10 DSN201E M C10 A10 RCBO 1P+N 10A 10mA

ABB DSN201EMC10A10 is a compact DSN201E M 1P+N Type A electronic RCBO with a 10 A rated current, C tripping characteristic, 10 mA residual-current sensitivity and 10 kA breaking capacity.

SKU: 2TAZ265114R1104Alt SKU: DSN201EMC10A10MPN: 2TAZ265114R1104
Price
List Price £156.23 ex VAT
Your Price (ex VAT)
£156.23
Manufacturer Lead Time Estimated Delivery 7 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £156.23
Trade pricing is personalised to your account

Manufacturer Lead Time

£156.23

Why Choose the ABB DSN201EMC10A10 RCBO?

The ABB DSN201EMC10A10, type code DSN201E M C10 A10, is a compact 1P+N Type A electronic residual current circuit breaker with overcurrent protection (RCBO) designed to protect single-phase circuits against overloads, short circuits and earth fault currents. As part of the ABB DSN201E RCBO series, it combines residual-current and overcurrent protection in a space-saving single-module device for DIN-rail distribution boards.

This RCBO has a rated current of 10 A, a sensitive 10 mA rated residual operating current and a Type C tripping characteristic. Its Type A residual-current detection responds to sinusoidal alternating and pulsating DC earth fault currents, providing suitable protection for circuits supplying modern electrical and electronic equipment.

With a 10 kA breaking capacity and compact 17.8 mm width, the DSN201E M C10 A10 provides comprehensive circuit protection while using only one DIN-rail module. Its switched neutral and ability to accept supply connections from either the top or bottom support flexible installation in residential, commercial and industrial distribution systems.

Key Advantages

  • Combined residual-current, overload and short-circuit protection in one device.
  • 10 A rated current for low-current final circuits.
  • High-sensitivity 10 mA residual operating current.
  • Type A residual-current protection for AC and pulsating DC earth fault currents.
  • Type C tripping characteristic suitable for circuits with moderate inrush currents.
  • 10 kA breaking capacity for robust short-circuit protection.
  • Compact 1P+N single-module design helps conserve DIN-rail space.
  • Top or bottom supply connection provides flexible distribution-board wiring.

Key Features

  • ABB DSN201E M electronic RCBO series.
  • 1P+N configuration with switched neutral.
  • 10 A rated current.
  • 10 mA rated residual operating current (IΔn).
  • Type A residual-current characteristic.
  • C tripping characteristic.
  • 10 kA breaking capacity.
  • Compact 17.8 mm single-module width.
  • DIN-rail mounting for residential, commercial and industrial distribution boards.
  • Compatible with ABB DSCC series auxiliary accessories.

Reliable Combined Circuit and Residual-Current Protection

An RCBO combines miniature circuit breaker and residual-current protection functions in a single device. The ABB DSN201E M C10 A10 therefore protects its connected circuit against overload and short-circuit currents while also detecting earth leakage caused by insulation faults or unintended current paths.

The Type C characteristic makes this model suitable for circuits where moderate starting or inrush currents may occur, while its Type A residual-current characteristic provides detection of both sinusoidal AC and pulsating DC residual currents. The compact single-module construction helps installers maximise available DIN-rail space without sacrificing combined circuit protection.

Typical Applications

  • Residential electrical distribution boards.
  • Commercial building final circuits.
  • Industrial control and distribution panels.
  • Circuits supplying electrical and electronic equipment.
  • Loads with moderate starting or inrush currents.
  • Space-constrained DIN-rail installations requiring combined RCBO protection.

Technical Specifications

Series DSN201E RCBO
Model / type code DSN201E M C10 A10
SKU DSN201EMC10A10
ABB order code 2TAZ265114R1104
Product type Electronic residual current circuit breaker with overcurrent protection (RCBO)
Number of poles 1P+N
Rated current 10 A
Residual-current type Type A
Rated residual operating current (IΔn) 10 mA
Tripping characteristic C
Breaking capacity 10 kA
Neutral Switched
Mounting 35 mm DIN rail
Module width 1 module
Dimensions (H × D × W) 86 × 70 × 17.8 mm
Weight approx. 0.119 kg
Supply connection Top or bottom
Housing protection degree IP40
Terminal protection degree IP20
Operating ambient temperature -25 to +55 °C
Storage temperature -25 to +70 °C
Standards IEC 61009-1, IEC 61009-2-2

Frequently Asked Questions

What is the ABB DSN201EMC10A10 used for?

The ABB DSN201EMC10A10 provides combined overload, short-circuit and residual-current protection for single-phase final circuits in residential, commercial and industrial electrical installations.

What is the current rating of the DSN201E M C10 A10?

This RCBO has a rated current of 10 A and uses a Type C tripping characteristic.

What residual-current sensitivity does this RCBO provide?

The DSN201E M C10 A10 has a rated residual operating current of 10 mA, providing sensitive earth-leakage detection.

What type of residual current does the DSN201EMC10A10 detect?

It is a Type A RCBO, designed to respond to sinusoidal alternating residual currents and pulsating DC residual currents.

What is the breaking capacity of the ABB DSN201E M C10 A10?

The DSN201E M C10 A10 has a 10 kA breaking capacity and a compact 1P+N single-module format for DIN-rail distribution boards.

Trusted ABB Protection for Electrical Distribution

ABB DSN201E electronic RCBOs provide compact combined protection against overloads, short circuits and earth fault currents, helping installers create space-efficient and dependable residential, commercial and industrial distribution systems.