Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB OVR T2 3N 80-440s P TS QS 2CTB815708R3700 is a pluggable 3+N Type 2 surge protective device with an 80 kA maximum discharge current, 440 V AC maximum continuous operating voltage, Safety Reserve and remote signalling.
£491.17
The ABB OVR T2 3N 80-440s P TS QS is a high-performance Type 2 surge protective device (SPD) designed to protect three-phase low-voltage electrical installations against transient overvoltages caused by indirect lightning strikes and switching events. Identified by ABB order code 2CTB815708R3700, it forms part of the advanced ABB OVR QuickSafe surge protection range and is suitable for TN-S and TT electrical distribution systems.
This 3+N surge arrester combines a high discharge capability with ABB QuickSafe technology, a pluggable construction and an integrated Safety Reserve function. The reserve varistor provides continued basic surge protection when the primary protection element reaches the end of its service life, allowing maintenance personnel time to replace the cartridge while maintaining a degree of protection for the installation.
With a 400/690 V AC rated system voltage, 440 V AC maximum continuous operating voltage, 80 kA maximum discharge current and remote signalling contacts, the OVR T2 3N 80-440s P TS QS is well suited to industrial, commercial and infrastructure distribution boards. Its DIN-rail-mounted, four-line configuration provides coordinated L-N, L-PE and N-PE surge protection in a compact System pro M compatible format.
Type 2 surge protective devices are designed to discharge transient currents generated by indirect lightning strikes and switching events on low-voltage power distribution networks. The ABB OVR T2 3N 80-440s P TS QS provides coordinated protection across phase, neutral and protective-earth conductors, helping limit damaging transient voltages before they reach sensitive downstream electrical and electronic equipment.
Its QuickSafe architecture combines thermal disconnection, mechanical condition indication and ABB's Safety Reserve function with replaceable protection cartridges. The TS version additionally provides remote status signalling, making this model particularly suitable for installations where surge-protection condition needs to be monitored from a control panel, building management system or other supervisory circuit.
Tick the specs you need, then view products that match.
| Remote Signal | Yes | |
|---|---|---|
| Device Type | Surge protection device | |
| SPD Type | Type 2 | |
| Poles | 3-pole + N | |
| Earthing System | TN-S, TT | |
| Impulse Current Iimp (kA) | 6.25 kA | |
| Series | OVR QuickSafe | |
| ABB order code | 2CTB815708R3700 | |
| EAN | 3660308525581 | |
| Product group | Surge Protection Devices | |
| Product type | Type 2 surge protective device (SPD) | |
| Configuration | 3+N | |
| Number of protected lines | 4 | |
| Protection modes | L-N / L-PE / N-PE | |
| Test class | Class II / Type 2 | |
| Rated system voltage | 400 / 690 V AC | |
| Maximum continuous operating voltage (Uc) | 440 V AC | |
| Frequency | 47–63 Hz | |
| Nominal discharge current (In, 8/20 µs) | 20 kA | |
| Maximum discharge current (Imax, 8/20 µs) | 80 kA | |
| Impulse current (Iimp, 10/350 µs) | 6.25 kA | |
| Voltage protection level (Up L-N) | 1.8 kV | |
| Voltage protection level (Up L-PE) | 2.1 kV | |
| Voltage protection level (Up N-PE) | 2.0 kV | |
| Short-circuit withstand (ISCCR) | 100 kA | |
| Total current | 80 kA | |
| Response time | <25 ns | |
| Integrated thermal disconnector | Yes | |
| End-of-life indicator | Yes | |
| Safety Reserve | Yes | |
| Remote signalling | Yes, auxiliary changeover contact | |
| Maximum backup circuit breaker | 125 A, curve B or C | |
| Maximum backup fuse | 160 A gG / gL | |
| Mounting | 35 mm DIN rail | |
| Construction | Pluggable | |
| Solid conductor range | 2.5–35 mm² | |
| Stranded conductor range | 2.5–25 mm² | |
| Stripping length | 12.5 mm | |
| Dimensions (H × W × D) | approx. 95 × 71.2 × 69.4 mm | |
| Weight | approx. 600 g | |
| Maximum installation altitude | 2,000 m | |
| Fire resistance | UL 94 V-0 | |
| Standards | IEC 61643-11 / EN 61643-11 |
It is a Type 2 surge protective device designed to protect three-phase low-voltage electrical installations against transient overvoltages caused by indirect lightning strikes and switching events.
The device has a maximum discharge current Imax of 80 kA using an 8/20 µs waveform, providing high-capacity transient surge protection.
The TS version includes an auxiliary signalling contact that enables the operating condition of the surge protective device to be monitored remotely.
The Safety Reserve design uses an additional protection element to maintain basic surge protection after the primary protection stage reaches the end of its service life, providing additional time for planned replacement.
The device is designed for DIN-rail installation in three-phase main and sub-distribution boards and is suitable for applications including TN-S and TT electrical systems.
ABB OVR surge protective devices provide dependable protection for modern electrical distribution systems, combining high surge-discharge capability with QuickSafe technology, Safety Reserve functionality, remote signalling and convenient pluggable maintenance.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.