ABB OVR T2 4L 80-275s P QS is a four-pole pluggable Type 2 surge protective device for 230/400 V AC TN-S systems, with Safety Reserve technology, 20 kA nominal discharge current, 80 kA maximum discharge current and 275 V AC maximum continuous operating voltage.
£343.82
The ABB OVR T2 4L 80-275s P QS, order code 2CTB815708R2300, is a high-capacity Type 2 surge protective device (SPD) designed for three-phase plus neutral 230/400 V AC TN-S electrical systems. Its four protected lines provide coordinated surge protection for L1, L2, L3 and N conductors, helping protect distribution equipment and connected loads against transient overvoltages caused by indirect lightning effects and electrical switching events.
Designed for demanding low-voltage installations, the OVR T2 4L 80-275s P QS has a maximum continuous operating voltage Uc of 275 V AC. It provides a nominal discharge current In of 20 kA per protected line and a maximum discharge current Imax of 80 kA using the 8/20 µs waveform, together with an impulse-current capability Iimp of 6.25 kA using the 10/350 µs waveform and a voltage protection level Up of 1.4 kV.
ABB's Safety Reserve technology supports preventive maintenance and increased protection availability, while QuickSafe technology provides dependable thermal disconnection at end of life. The four-pole device uses pluggable protection cartridges with individual mechanical status indication, allowing straightforward inspection and cartridge replacement without replacing the complete SPD assembly.
Type 2 SPDs are designed to divert transient currents associated with indirect lightning effects and electrical switching before damaging overvoltages reach downstream equipment. The ABB OVR T2 4L 80-275s P QS combines four protected lines with an 80 kA maximum discharge-current rating and 1.4 kV voltage protection level, making it particularly suitable for demanding three-phase plus neutral TN-S distribution systems.
The Safety Reserve design supports preventive maintenance and continued protection availability, while ABB QuickSafe technology provides dependable thermal disconnection. Each protection module is pluggable and incorporates mechanical condition indication, allowing maintenance personnel to identify an affected module and replace its cartridge without unnecessarily replacing the complete four-pole SPD assembly.
Tick the specs you need, then view products that match.
| Remote Signal | No | |
|---|---|---|
| SPD Type | Type 2 | |
| Poles | 4-pole | |
| Earthing System | TN-S | |
| Device Type | Surge protection device | |
| Impulse Current Iimp (kA) | 6.25 kA | |
| Series | OVR T2 QuickSafe | |
| ABB order code | 2CTB815708R2300 | |
| EAN / GTIN | 3660308525529 | |
| Product group | Surge Protection Devices | |
| Product type | Type 2 surge protective device | |
| SPD classification | Type 2 / Class II | |
| Standards | IEC 61643-11 / EN 61643-11 | |
| Protection technology | Varistor | |
| Low-voltage distribution system | TN-S | |
| Number of poles | 4 | |
| Number of protected lines | 4 | |
| Rated system voltage | 230 / 400 V AC | |
| Maximum continuous operating voltage Uc | 275 V AC | |
| Impulse current Iimp (10/350 µs) | 6.25 kA | |
| Nominal discharge current In (8/20 µs) | 20 kA | |
| Maximum discharge current Imax (8/20 µs) | 80 kA | |
| Total maximum discharge-current capability | 320 kA | |
| Voltage protection level Up | 1.4 kV | |
| Rated service short-circuit breaking capacity Ics | 100 kA | |
| Safety Reserve | Yes | |
| Preventive maintenance function | Yes | |
| QuickSafe technology | Yes | |
| Status indication | Mechanical indicator on each protection module | |
| Remote signalling | No | |
| Construction | Pluggable | |
| Replacement cartridge | OVR T2 80-275s C QS | |
| Replacement cartridge order code | 2CTB815708R2600 | |
| Degree of protection | IP20 | |
| Operating temperature | -40 to +80 °C | |
| Mounting type | DIN rail | |
| Module width | 4 modules |
It is a Type 2 surge protective device designed for three-phase plus neutral 230/400 V AC TN-S systems, providing four-line protection against transient overvoltages caused by indirect lightning effects and electrical switching events.
The device provides a nominal discharge current In of 20 kA and a maximum discharge current Imax of 80 kA using the 8/20 µs waveform, together with a 6.25 kA impulse-current capability using the 10/350 µs waveform.
The “s” identifies ABB's Safety Reserve version. Safety Reserve technology supports preventive maintenance and helps maintain a level of surge protection when the primary protection stage reaches end of life.
No. ABB order code 2CTB815708R2300 is the P QS version without the TS auxiliary remote-signalling contact. Local condition information is provided by the mechanical status indicators on the protection modules.
Yes. The OVR T2 4L 80-275s P QS uses pluggable protection cartridges. The compatible ABB OVR T2 80-275s C QS replacement cartridge has order code 2CTB815708R2600.
ABB OVR Type 2 surge protective devices combine high surge-current capability, QuickSafe technology and pluggable construction, with the OVR T2 4L 80-275s P QS delivering four-line protection, Safety Reserve functionality and up to 80 kA maximum discharge current per protection path for demanding three-phase plus neutral TN-S installations.