ABB OVR T2 40-440s P TS QS is a single-pole pluggable Type 2 surge protective device with Safety Reserve technology, 20 kA nominal discharge current, 40 kA maximum discharge current, 440 V AC maximum continuous operating voltage and remote status signalling.
£115.49
The ABB OVR T2 40-440s P TS QS, order code 2CTB815704R2900, is a compact Type 2 surge protective device (SPD) designed to protect low-voltage electrical installations against transient overvoltages caused by indirect lightning effects and switching events. Its single-pole design is suitable for coordinated protection in TT, TN-C, TN-S and IT distribution systems.
Designed for 400 V AC applications and 400/690 V AC systems, the OVR T2 40-440s P TS QS has a maximum continuous operating voltage Uc of 440 V AC. It provides a nominal discharge current In of 20 kA and a maximum discharge current Imax of 40 kA using the 8/20 µs waveform, together with a voltage protection level Up of 1.8 kV.
The device combines ABB QuickSafe technology with a Safety Reserve preventive-maintenance function, pluggable construction and visual status indication. The TS remote-signalling contacts provide one normally open and one normally closed auxiliary contact for remote condition monitoring, while the compact 17.8 mm DIN-rail width makes the SPD easy to integrate into space-conscious switchboards.
Type 2 SPDs are designed to discharge transient currents associated with indirect lightning events and switching operations before damaging overvoltages reach connected equipment. The ABB OVR T2 40-440s P TS QS combines a 20 kA nominal discharge current, 40 kA maximum discharge current and 1.8 kV protection level with a 440 V AC continuous operating rating for higher-voltage distribution applications.
The Safety Reserve feature supports preventive maintenance and increased surge-protection availability, while the pluggable cartridge allows the protection module to be replaced without changing the complete base assembly. Visual indication provides local status information, and the TS auxiliary contacts allow the SPD condition to be incorporated into remote monitoring, alarm or building-management systems.
Tick the specs you need, then view products that match.
| Remote Signal | Yes | |
|---|---|---|
| SPD Type | Type 2 | |
| Poles | 1-pole | |
| Device Type | Surge protection device | |
| Impulse Current Iimp (kA) | 2 kA | |
| Series | OVR T2 QuickSafe | |
| ABB order code | 2CTB815704R2900 | |
| EAN / GTIN | 3660308525369 | |
| Product group | Surge Protection Devices | |
| Product type | Type 2 surge protective device | |
| SPD classification | Type 2 / Class II | |
| Standards | IEC 61643-11 / EN 61643-11 | |
| Protection technology | Varistor | |
| Low-voltage distribution systems | TT / TN-C / TN-S / IT | |
| Number of poles | 1 | |
| Number of protected poles | 1 | |
| Rated voltage | 400 V AC | |
| Nominal system voltage | 400 / 690 V AC | |
| Voltage rating DC | 560 V DC | |
| Frequency | 45–65 Hz | |
| Maximum continuous operating voltage Uc | 440 V AC | |
| Impulse current Iimp (10/350 µs) | 2 kA | |
| Nominal discharge current In (8/20 µs) | 20 kA | |
| Maximum discharge current Imax (8/20 µs) | 40 kA | |
| Voltage protection level Up | 1.8 kV | |
| Short-circuit withstand capability | 100 kA | |
| Rated service short-circuit breaking capacity Ics | 100 kA | |
| Maximum backup fuse or circuit breaker | 125 A | |
| Response time | ≤25 ns | |
| Preventive maintenance function | Yes | |
| Safety Reserve | Yes | |
| QuickSafe technology | Yes | |
| Status indicator | Yes | |
| Remote signalling | Yes | |
| Normally open auxiliary contacts | 1 | |
| Normally closed auxiliary contacts | 1 | |
| Minimum auxiliary contact load | 12 V DC / 10 mA | |
| Maximum auxiliary contact load | 250 V AC / 1 A | |
| Construction | Pluggable | |
| Replacement cartridge | OVR T2 40-440s C QS | |
| Replacement cartridge order code | 2CTB815704R5500 | |
| Degree of protection | IP20 | |
| Flammability rating | UL 94 V-0 | |
| Operating temperature | -40 to +80 °C | |
| Maximum operating altitude | 5000 m | |
| Mounting type | DIN rail | |
| Module width | 1 module | |
| Dimensions (H × W × D) | 95.8 × 17.8 × 76.7 mm | |
| Weight | 0.15 kg |
It is a Type 2 surge protective device designed to protect low-voltage electrical installations against transient overvoltages caused by indirect lightning effects and electrical switching events, particularly in higher-voltage AC distribution systems.
The device has a nominal discharge current In of 20 kA and a maximum discharge current Imax of 40 kA using the 8/20 µs waveform, together with a 2 kA impulse-current capability using the 10/350 µs waveform.
The “s” identifies the Safety Reserve version, which incorporates a preventive-maintenance function designed to increase protection availability and provide an indication when SPD maintenance or cartridge replacement is required.
The TS version includes remote signalling through one normally open and one normally closed auxiliary contact, allowing the SPD condition to be integrated with suitable monitoring, alarm or building-management systems.
Yes. The OVR T2 40-440s P TS QS has a pluggable protection cartridge. The compatible replacement is the ABB OVR T2 40-440s C QS, order code 2CTB815704R5500.
ABB OVR Type 2 surge protective devices combine high surge-current capability, QuickSafe technology and pluggable construction, with the OVR T2 40-440s P TS QS adding Safety Reserve functionality and remote status signalling for dependable surge protection in higher-voltage commercial and industrial electrical installations.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.