ABB OVR T2-T3 N 80-440 P QS is a pluggable combined Type 2 and Type 3 neutral surge protective device with 80 kA maximum discharge current, 30 kA nominal discharge current and 440 V AC maximum continuous operating voltage for neutral-to-earth surge protection.
£92.87
The ABB OVR T2-T3 N 80-440 P QS is a high-capacity combined Type 2 and Type 3 neutral surge protective device (SPD) designed for neutral-to-earth protection in low-voltage electrical installations. As part of the ABB OVR QuickSafe surge protection range, this single-pole neutral module is intended for use in coordinated surge protection arrangements where dependable discharge of transient overvoltages between neutral and protective earth is required.
The OVR T2-T3 N 80-440 P QS provides a substantial maximum discharge current of 80 kA and a nominal discharge current of 30 kA using the 8/20 µs waveform. It also has an impulse current rating of 2 kA using the 10/350 µs waveform, providing robust neutral-to-earth surge handling within compatible Type 2 and Type 3 protection arrangements.
With a nominal voltage of 400 V AC, maximum continuous operating voltage of 440 V AC and voltage protection level of 1.4 kV, the device is suitable for higher-voltage low-voltage distribution applications. Its pluggable construction and compact single-module DIN-rail format make installation and replacement straightforward in commercial and industrial distribution boards.
Neutral surge protective devices provide a controlled discharge path between neutral and protective earth during transient overvoltage events. The ABB OVR T2-T3 N 80-440 P QS is designed specifically for this role, providing an 80 kA maximum discharge capability to help prevent damaging voltage differences from developing between neutral and earth within coordinated surge protection systems.
Its combined Type 2 and Type 3 characteristics allow the device to support both distribution-level surge protection and protection closer to sensitive downstream equipment. The high discharge capability, 440 V AC Uc rating and pluggable construction make it suitable for demanding commercial and industrial electrical installations where reliable neutral-to-earth protection is required.
Tick the specs you need, then view products that match.
| Remote Signal | No | |
|---|---|---|
| Device Type | Surge protection device | |
| SPD Type | Type 2+3 | |
| Poles | 1-pole | |
| Impulse Current Iimp (kA) | 2 kA | |
| Series | OVR T2-T3 QuickSafe | |
| ABB order code | 2CTB803973R2000 | |
| EAN | 3660308519665 | |
| Product group | Surge Protection Devices | |
| Product type | Combined Type 2 + Type 3 neutral surge protective device | |
| SPD classification | Type 2 + Type 3 | |
| Standards | IEC 61643-11 / EN 61643-11 | |
| Protection function | Neutral-to-earth surge protection | |
| Number of poles | 1 | |
| Number of protected poles | 1 | |
| Nominal voltage Un | 400 V AC | |
| Maximum continuous operating voltage Uc | 440 V AC | |
| Maximum discharge current Imax (8/20 µs) | 80 kA | |
| Nominal discharge current In (8/20 µs) | 30 kA | |
| Impulse current Iimp (10/350 µs) | 2 kA | |
| Follow current interrupting rating Ifi | 0.1 kA | |
| Voltage protection level Up | 1.4 kV | |
| Short-circuit withstand capability | 100 kA | |
| Rated service short-circuit breaking capacity | 100 kA | |
| Cartridge type | Pluggable | |
| Replacement cartridge | OVR T2-T3 N 80-440 C QS | |
| Replacement cartridge order code | 2CTB803886R0100 | |
| Protection rating | IP20 | |
| Maximum operating altitude | 5000 m | |
| Mounting type | DIN rail | |
| Modular width | 1 module | |
| Dimensions (H × W × D) | 88 × 17.8 × 58 mm | |
| Weight | 0.12 kg |
It is a combined Type 2 and Type 3 neutral surge protective device designed to provide neutral-to-earth protection against transient overvoltages in compatible low-voltage electrical installations.
The OVR T2-T3 N 80-440 P QS has a maximum discharge current Imax of 80 kA using an 8/20 µs waveform.
The device has a nominal discharge current In of 30 kA using an 8/20 µs waveform and an impulse current Iimp of 2 kA using a 10/350 µs waveform.
The device has a nominal voltage of 400 V AC and a maximum continuous operating voltage Uc of 440 V AC.
Yes. The OVR T2-T3 N 80-440 P QS has a pluggable construction and uses the OVR T2-T3 N 80-440 C QS replacement cartridge, ABB order code 2CTB803886R0100.
ABB OVR surge protective devices combine high surge discharge capability, compact DIN-rail construction and replaceable protection cartridges to provide dependable surge protection for modern commercial and industrial low-voltage electrical installations.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.