ABB OVR T2 3N 40-440 P QS is a four-pole Type 2 surge protective device with 40 kA maximum discharge current per protected pole, 20 kA nominal discharge current and 440 V AC maximum continuous operating voltage for three-phase plus neutral electrical installations.
£285.77
The ABB OVR T2 3N 40-440 P QS is a high-performance Type 2 surge protective device (SPD) designed to protect three-phase plus neutral low-voltage electrical installations against transient overvoltages caused by indirect lightning effects and electrical switching events. As part of the ABB OVR QuickSafe surge protection range, it provides dependable protection for electrical distribution systems and sensitive equipment in commercial and industrial applications.
Designed with a 3+N four-pole configuration, the OVR T2 3N 40-440 P QS provides a nominal discharge current of 20 kA and a maximum discharge current of 40 kA per protected pole using the standard 8/20 µs surge waveform. Its pluggable construction allows individual protection cartridges to be replaced, simplifying maintenance while retaining the DIN-rail base assembly.
With a maximum continuous operating voltage of 440 V AC and compatibility with 400/690 V AC systems, this Type 2 SPD is suitable for higher-voltage three-phase distribution networks. Its compact four-module DIN-rail format, IP20 protection and visual status indication make it suitable for integration into distribution boards, switchgear and industrial electrical control panels.
Type 2 surge protective devices are installed in low-voltage distribution systems to limit transient overvoltages before they can damage connected electrical and electronic equipment. The ABB OVR T2 3N 40-440 P QS safely diverts surge currents away from protected circuits, helping safeguard switchgear, automation equipment, drives, control systems and other sensitive loads.
Its four-pole 3+N configuration provides surge protection across all three phases and neutral, while the 440 V AC Uc rating makes it suitable for installations requiring a higher continuous operating voltage than conventional 275 V SPDs. Pluggable construction and visual status indication help simplify inspection and maintenance throughout the installation's service life.
Tick the specs you need, then view products that match.
| Remote Signal | No | |
|---|---|---|
| Device Type | Surge protection device | |
| SPD Type | Type 2 | |
| Poles | 3-pole + N | |
| Earthing System | TN-S, TT | |
| Impulse Current Iimp (kA) | 2 kA | |
| Series | OVR T2 QuickSafe | |
| ABB order code | 2CTB803973R1400 | |
| EAN | 3660308519993 | |
| Product group | Surge Protection Devices | |
| Product type | Type 2 surge protective device | |
| SPD classification | Type 2 / Class II | |
| Standard | IEC 61643-11 / EN 61643-11 | |
| Number of poles | 4 | |
| Number of protected poles | 4 | |
| Configuration | 3 phases + neutral | |
| Nominal system voltage | 400 / 690 V AC | |
| Maximum continuous operating voltage Uc (L-PE) | 440 V AC | |
| Maximum continuous operating voltage Uc (L-N) | 440 V AC | |
| Maximum continuous operating voltage Uc (N-PE) | 440 V AC | |
| Maximum continuous operating voltage Uc (L-L) | 760 V AC | |
| Maximum discharge current Imax (8/20 µs) | 40 kA per protected pole | |
| Nominal discharge current In (8/20 µs) | 20 kA per protected pole | |
| Total maximum discharge current | 160 kA | |
| Impulse current Iimp (10/350 µs) | 2 kA | |
| Rated service short-circuit breaking capacity | 100 kA | |
| Cartridge type | Pluggable | |
| Remote auxiliary contact | No | |
| Status indication | Visual | |
| Protection rating | IP20 | |
| Operating temperature | -40 to +80 °C | |
| Mounting type | 35 mm DIN rail | |
| Width | 71.2 mm | |
| Dimensions (H × W × D) | 88 × 71.2 × 58 mm | |
| Weight | approx. 0.48 kg |
It is a Type 2 surge protective device designed to protect three-phase plus neutral low-voltage electrical installations and connected equipment against transient overvoltages.
The OVR T2 3N 40-440 P QS has a maximum discharge current Imax of 40 kA per protected pole using an 8/20 µs waveform.
The device has a nominal discharge current In of 20 kA per protected pole using an 8/20 µs waveform.
The device is suitable for nominal system voltages of 400/690 V AC and has a maximum continuous operating voltage Uc of 440 V AC from line to neutral, line to earth and neutral to earth.