Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB OVR T2-T3 20-275 C QS QuickSafe replacement phase surge protection cartridge for compatible Type 2 and Type 3 SPDs, with 275 V AC maximum continuous operating voltage, 20 kA maximum discharge current, 5 kA nominal discharge current and 0.9 kV voltage protection level.
£29.90
The ABB OVR T2-T3 20-275 C QS is a replacement phase cartridge for compatible ABB OVR QuickSafe combined Type 2 and Type 3 surge protective devices. Designed for the ABB OVR T2-T3 20-275 range, it enables a worn or end-of-life surge protection cartridge to be replaced without changing the complete SPD base.
The cartridge provides a maximum discharge current (Imax) of 20 kA and a nominal discharge current (In) of 5 kA using an 8/20 µs surge-current waveform. It is designed for 230 V AC nominal applications with a 275 V AC maximum continuous operating voltage (Uc) and provides a 0.9 kV voltage protection level (Up).
As a genuine ABB QuickSafe pluggable replacement cartridge, the OVR T2-T3 20-275 C QS provides a straightforward way to restore surge protection after a cartridge reaches end of life. Its integrated status indicator assists with visual condition checking, while the compact single-pole cartridge format is designed for direct installation into compatible ABB OVR T2-T3 pluggable bases.
Pluggable surge protective devices allow the protection element to be replaced independently of the permanently wired base. When a surge cartridge reaches the end of its service life, replacing only the cartridge can restore the SPD to its intended protection capability while reducing maintenance time and avoiding unnecessary rewiring of the installation.
The ABB OVR T2-T3 20-275 C QS provides the electrical characteristics required for compatible 275 V OVR T2-T3 QuickSafe devices, including a 20 kA maximum discharge current, 5 kA nominal discharge current and 0.9 kV voltage protection level. Its plug-in construction and visual status indication make it a practical spare component for maintaining ABB surge protection installations.
Tick the specs you need, then view products that match.
| Device Type | Replacement cartridge | |
|---|---|---|
| Impulse Current Iimp (kA) | 2 kA | |
| Series | OVR T2-T3 QuickSafe | |
| ABB order code | 2CTB803876R1200 | |
| Product group | Surge Protection Devices | |
| Product type | Replacement surge protection cartridge | |
| Cartridge type | Phase cartridge | |
| SPD classification | Type 2 + Type 3 / Class II + III | |
| Number of poles | 1 | |
| Number of protected poles | 1 | |
| Compatible network types | TT / TN-C / TN-S | |
| Nominal voltage | 230 V AC | |
| Nominal AC system voltage | 230/400 V | |
| Maximum continuous operating voltage (Uc) | 275 V AC | |
| Maximum discharge current (Imax, 8/20 µs) | 20 kA | |
| Nominal discharge current (In, 8/20 µs) | 5 kA | |
| Impulse current (Iimp, 10/350 µs) | 2 kA | |
| Voltage protection level (Up) | 0.9 kV | |
| Temporary overvoltage withstand | 337 V | |
| Short-circuit withstand capability | 100 kA | |
| Technology | QuickSafe | |
| Construction | Plug-in replacement cartridge | |
| Status indicator | Yes | |
| Protection rating | IP20 | |
| Maximum operating altitude | 5000 m | |
| Dimensions (H × W × D) | 57 × 17.6 × 55.6 mm | |
| Net weight | approx. 50 g | |
| Standards | IEC 61643-11 / EN 61643-11 |
It is a replacement phase surge protection cartridge for compatible ABB OVR T2-T3 20-275 QuickSafe pluggable surge protective devices.
The cartridge has a maximum discharge current (Imax) of 20 kA and a nominal discharge current (In) of 5 kA, using an 8/20 µs surge-current waveform.
The ABB OVR T2-T3 20-275 C QS has a maximum continuous operating voltage (Uc) of 275 V AC and is intended for compatible 230 V AC applications.
The cartridge provides a voltage protection level (Up) of 0.9 kV, supporting protection of sensitive downstream electrical and electronic equipment.
No. The OVR T2-T3 20-275 C QS is specifically designed as a plug-in replacement cartridge, allowing a compatible ABB OVR T2-T3 SPD to be serviced without replacing its complete wired base.
ABB OVR QuickSafe replacement cartridges provide a practical way to maintain compatible pluggable surge protective devices, restoring their surge protection capability without replacing the complete installed SPD base.
We use cookies