2CSR272001R1064 ABB DS202 M AC-C6/0.03 RCBO 2P 6 A 30 mA 10 kA

2CSR272001R1064 ABB DS202 M AC-C6/0.03 RCBO 2P 6 A 30 mA 10 kA

ABB DS202 M AC-C6/0.03 is a 6 A 2-pole Type AC 30 mA RCBO with C-curve overcurrent protection and 10 kA short-circuit breaking capacity for commercial and industrial electrical circuits.

SKU: 2CSR272001R1064Alt SKU: DS202MACC60.03MPN: 2CSR272001R1064
Price
List Price £243.36 ex VAT
Your Price (ex VAT) Save 35%
£158.18 35% OFF
You save £85.18 per unit
Manufacturer Lead Time Estimated Delivery 9 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £158.18
Trade pricing is personalised to your account

Manufacturer Lead Time

£158.18

Why Choose the ABB DS202 M AC-C6/0.03 RCBO?

The ABB DS202 M AC-C6/0.03, order code 2CSR272001R1064, is a high-performance 2-pole residual current circuit breaker with overcurrent protection (RCBO) designed to protect electrical circuits against overloads, short circuits and sinusoidal alternating earth fault currents. Part of the ABB DS200 / DSH200 RCBO product group, it combines residual-current and overcurrent protection in a factory-assembled device for commercial and industrial electrical installations.

This DS200 M series RCBO uses Type AC residual-current protection and a C tripping characteristic. It provides protection against indirect contact and, with its 30 mA rated residual operating current, additional protection against direct contact. The factory-assembled combination simplifies installation and wiring while retaining the protection characteristics required for demanding electrical distribution applications.

With a rated current of 6 A, 30 mA residual-current sensitivity and 10 kA rated short-circuit breaking capacity, the DS202 M AC-C6/0.03 provides robust protection for two-pole circuits. Its DIN rail format and compatibility with ABB System pro M compact accessories make it suitable for professional distribution-board and control-panel installations.

Key Advantages

  • Combined residual current, overload and short-circuit protection in one device.
  • 6 A rated current with C-curve overcurrent tripping characteristic.
  • 30 mA residual current sensitivity for additional protection against direct contact.
  • Type AC protection for sinusoidal alternating residual currents.
  • 2-pole configuration with both poles protected.
  • 10 kA rated short-circuit breaking capacity for demanding applications.
  • Factory-assembled RCBO construction simplifies installation and wiring.
  • Suitable for commercial and industrial electrical distribution systems.

Key Features

  • ABB DS200 M RCBO series.
  • 6 A rated current.
  • C tripping characteristic.
  • 30 mA rated residual current (IΔn).
  • Type AC residual-current protection.
  • 2-pole configuration.
  • 2 protected poles.
  • 10 kA rated short-circuit breaking capacity (Icn).
  • Protection against overload and short-circuit currents.
  • Protection against sinusoidal alternating earth fault currents.
  • Protection against indirect contact and additional protection against direct contact.
  • Suitable for command and isolation of resistive and inductive loads.
  • DIN rail mounting for integration into modular distribution systems.

Reliable 10 kA Combined Circuit Protection

An RCBO combines the functions of residual-current protection and overcurrent protection within a single assembly. The ABB DS202 M AC-C6/0.03 protects connected circuits against overload and short-circuit currents while also detecting sinusoidal alternating earth leakage currents that can create electrical hazards.

The DS200 M series is designed for demanding commercial and industrial applications and provides a 10 kA rated short-circuit breaking capacity. Its factory-assembled construction simplifies installation compared with assembling separate compatible protection components on site, while the 30 mA Type AC protection provides additional protection against direct contact where Type AC residual-current detection is appropriate for the installation.

Typical Applications

  • Commercial electrical distribution systems.
  • Industrial distribution boards and control panels.
  • Circuits requiring combined 6 A overcurrent and 30 mA residual-current protection.
  • Resistive and inductive electrical loads.
  • Two-pole circuits requiring Type AC residual-current protection.
  • Installations requiring a 10 kA rated short-circuit breaking capacity.

Technical Specifications

Product group DS200 / DSH200 RCBO
Series DS200 M
ABB order code 2CSR272001R1064
EAN 8012542851509
Product type Residual current circuit breaker with overcurrent protection (RCBO)
Number of poles 2
Protected poles 2
Rated current 6 A
Tripping characteristic C curve
Rated residual current (IΔn) 30 mA
Residual current type Type AC
Rated voltage 230 V AC
Rated short-circuit breaking capacity (Icn) 10 kA
Rated ultimate short-circuit breaking capacity (Icu) 15 kA at 400 V AC
Standards IEC/EN 61009-1; IEC/EN 61009-2-1
Application Commercial and industrial electrical installations
Mounting DIN rail
Weight approx. 0.44 kg

Frequently Asked Questions

What is the ABB DS202 M AC-C6/0.03 used for?

The ABB DS202 M AC-C6/0.03 is a 2-pole RCBO used to protect electrical circuits against overloads, short circuits and sinusoidal alternating earth fault currents in commercial and industrial installations.

What is the current rating of the DS202 M AC-C6/0.03?

The RCBO has a rated current of 6 A and uses a C-curve tripping characteristic.

What residual current sensitivity does this RCBO have?

The DS202 M AC-C6/0.03 has a rated residual operating current of 30 mA and uses Type AC residual-current protection.

What is the breaking capacity of the ABB DS202 M AC-C6/0.03?

The DS202 M AC-C6/0.03 has a rated short-circuit breaking capacity (Icn) of 10 kA.

What does Type AC mean on the ABB DS202 M AC-C6/0.03?

Type AC means the RCBO is designed to detect sinusoidal alternating residual currents, providing residual-current protection for applications where this type of earth leakage current is expected.

Trusted ABB Circuit Protection

ABB DS200 M RCBOs combine residual-current and overcurrent protection in factory-assembled devices designed for reliable commercial and industrial electrical distribution, with high short-circuit breaking capacity and straightforward integration into modular installations.