Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB DS203NCC20APR30 is a 3P+N APR RCBO with 20 A rated current, C tripping characteristic, 30 mA residual-current sensitivity and 6 kA breaking capacity for high-immunity three-phase circuit protection.
£194.84
The ABB DS203NCC20APR30 is a compact 3P+N residual current circuit breaker with overcurrent protection (RCBO) designed to protect three-phase electrical circuits against overloads, short circuits and residual earth-fault currents. As part of the ABB DS203NC series, it combines residual-current and overcurrent protection in a single modular device for efficient commercial and industrial electrical distribution.
This RCBO features a 20 A rated current, C tripping characteristic and APR residual-current characteristic with 30 mA sensitivity. ABB APR devices provide enhanced resistance to unwanted tripping caused by transient disturbances while maintaining residual-current protection, making them particularly useful where continuity of service and immunity to nuisance tripping are important.
With a rated residual operating current of 30 mA and a rated short-circuit breaking capacity of 6 kA according to EN/IEC 61009, the DS203NCC20APR30 provides combined protection in a compact 3P+N four-module format. Its C characteristic accommodates moderate starting currents, supporting use with a wide range of commercial and industrial loads.
The ABB DS203NCC20APR30 combines the functions of a miniature circuit breaker and a residual-current protective device in one unit. It responds to overload and short-circuit conditions while monitoring residual current flowing to earth, providing coordinated protection for conductors, connected equipment and electrical installations.
Its APR characteristic is designed for increased immunity to transient disturbances that can cause unwanted operation of conventional residual-current devices. Combined with 30 mA residual-current sensitivity and a C tripping characteristic, the DS203NCC20APR30 is suited to installations requiring residual-current protection together with improved continuity of service.
| Series | DS203NC |
|---|---|
| SKU | DS203NCC20APR30 |
| ABB order code | 2CSR256440R1204 |
| Product group | DS200 / DSH200 RCBO |
| Product type | Residual current circuit breaker with overcurrent protection (RCBO) |
| Number of poles | 3P+N / 4 poles |
| Protected poles | 3 |
| Rated current | 20 A |
| Tripping characteristic | C |
| Residual-current characteristic | APR |
| Rated residual operating current | 30 mA |
| Rated voltage | 400–415 V AC |
| Frequency | 50/60 Hz |
| Rated short-circuit breaking capacity Icn | 6 kA |
| Rated ultimate short-circuit breaking capacity Icu | 10 kA |
| Rated insulation voltage Ui | 500 V |
| Rated impulse withstand voltage Uimp | 4 kV |
| Energy limiting class | 3 |
| Overvoltage category | III |
| Pollution degree | 2 |
| Operating temperature | -25 to +55 °C |
| Mounting type | DIN rail |
| Width | 4 modules / 71 mm |
| Built-in depth | 69 mm |
| Standards | IEC/EN 61009-1, IEC/EN 61009-2-1 |
The ABB DS203NCC20APR30 is a 3P+N RCBO designed to protect three-phase circuits against overloads, short circuits and residual earth-fault currents while providing enhanced immunity to unwanted tripping from transient disturbances.
The RCBO has a rated current of 20 A and uses a C tripping characteristic, making it suitable for circuits with moderate starting and inrush currents.
The DS203NCC20APR30 has a rated residual operating current of 30 mA and uses ABB's APR high-immunity residual-current characteristic.
ABB's APR characteristic provides increased resistance to unwanted residual-current tripping caused by transient disturbances, helping improve continuity of service in installations susceptible to nuisance tripping.
The device has a rated short-circuit breaking capacity Icn of 6 kA according to EN/IEC 61009 and an ultimate short-circuit breaking capacity of 10 kA according to IEC 60947-2.
ABB DS203NC RCBOs combine residual-current and overcurrent protection in a compact modular format, while APR versions provide enhanced immunity to transient disturbances for dependable protection and improved service continuity in three-phase installations.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.