2CSR256140R1104 ABB DS203NCC10A30 RCBO 3P+N C10 Type A 30mA 6kA

2CSR256140R1104 ABB DS203NCC10A30 RCBO 3P+N C10 Type A 30mA 6kA

ABB DS203NCC10A30 is a 10 A 3P+N Type C RCBO with 30 mA Type A residual-current protection, 400–415 V AC operation and a 6 kA rated short-circuit breaking capacity.

SKU: 2CSR256140R1104Alt SKU: DS203NCC10A30MPN: 2CSR256140R1104
Price
List Price £230.58 ex VAT
Your Price (ex VAT) Save 35%
£149.88 35% OFF
You save £80.70 per unit
Manufacturer Lead Time Estimated Delivery 4 - 5 Days
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £149.88
Trade pricing is personalised to your account

Manufacturer Lead Time

£149.88

Why Choose the ABB DS203NCC10A30 RCBO?

The ABB DS203NCC10A30 is a compact 3P+N residual current circuit breaker with overcurrent protection (RCBO) designed to protect three-phase electrical circuits against overloads, short circuits and residual earth-fault currents. Part of the ABB DS203NC series, it combines residual-current and overcurrent protection within a single four-module device for efficient commercial and industrial electrical distribution.

This RCBO has a rated current of 10 A, a Type C tripping characteristic and a rated residual operating current of 30 mA. Its Type A residual-current characteristic detects sinusoidal alternating and pulsating DC residual currents, making it suitable for modern electrical circuits where these residual-current waveforms may occur.

With a rated operational voltage of 400–415 V AC and a rated short-circuit breaking capacity of 6 kA, the DS203NC C10 A30 provides integrated protection for three-phase plus neutral circuits. Its 30 mA sensitivity provides additional protection against direct contact in suitable installations, while its compact four-module construction helps conserve distribution-board space.

Key Advantages

  • Combined residual-current, overload and short-circuit protection in one device.
  • 10 A rated current with Type C tripping characteristic.
  • 30 mA residual-current sensitivity for additional protection in suitable installations.
  • Type A residual-current detection for sinusoidal AC and pulsating DC residual currents.
  • 3P+N configuration with three protected poles.
  • 6 kA rated short-circuit breaking capacity according to IEC/EN 61009.

Key Features

  • ABB DS203NC RCBO series.
  • 10 A rated current.
  • Type C tripping curve.
  • 30 mA rated residual operating current.
  • Type A residual-current characteristic.
  • Detection of sinusoidal alternating and pulsating DC residual currents.
  • 3P+N four-pole configuration with three protected poles.
  • 400–415 V AC rated operational voltage.
  • 6 kA rated short-circuit breaking capacity (Icn).
  • 10 kA ultimate short-circuit breaking capacity (Icu).
  • 50/60 Hz rated frequency.
  • Compact four-module DIN-rail design.

Reliable Type A Protection for Three-Phase Circuits

The ABB DS203NCC10A30 combines overcurrent and residual-current protection within one modular device. Its overcurrent function protects against overload and short-circuit currents, while the Type A residual-current function responds to sinusoidal alternating and pulsating DC earth-fault currents that can occur in modern electrical installations.

With a residual-current sensitivity of 30 mA, the DS203NCC10A30 provides fault protection and additional protection against direct contact where applicable. Its Type C tripping characteristic is suitable for appropriate circuits with moderate inrush currents, while the compact four-module 3P+N construction helps minimise the panel space required for comprehensive circuit protection.

Typical Applications

  • Three-phase end-user electrical circuits.
  • Commercial electrical distribution boards.
  • Industrial electrical distribution systems.
  • Control panels and switchboards.
  • Circuits containing equipment capable of producing pulsating DC residual currents.
  • Three-phase circuits requiring combined Type C overcurrent and Type A residual-current protection.

Technical Specifications

Series DS203NC
SKU DS203NCC10A30
ABB order code 2CSR256140R1104
Product group DS200 / DSH200 RCBO
Product type Residual current circuit breaker with overcurrent protection (RCBO)
Rated current 10 A
Tripping characteristic C
Rated residual operating current 30 mA
Residual-current type A
Number of poles 4 (3P+N)
Number of protected poles 3
Rated operational voltage 400–415 V AC
Rated frequency 50/60 Hz
Rated short-circuit breaking capacity (Icn) 6 kA
Rated ultimate short-circuit breaking capacity (Icu) 10 kA
Rated conditional short-circuit current (Inc) 10 kA
Rated insulation voltage (Ui) 500 V
Rated impulse withstand voltage (Uimp) 4 kV
Energy limiting class 3
Operating characteristic Undelayed
Overvoltage category III
Pollution degree 2
Degree of protection IP2X
Neutral conductor Simultaneously switched
Maximum conductor cross-section 25 mm²
Operating temperature -25 to +55 °C
Mounting type DIN rail
Width 4 modules
Dimensions (W × H × D) 71 × 85 × 69 mm
Installation depth 69 mm
Power loss 5.6 W
Standards IEC 61009-1, IEC 61009-2-1, EN 61009-1, EN 61009-2-1
EAN 8012542896524

Frequently Asked Questions

What is the ABB DS203NCC10A30 used for?

The ABB DS203NCC10A30 is a 3P+N RCBO designed to protect three-phase electrical circuits against overloads, short circuits and residual earth-fault currents.

What is the rated current and tripping curve of the DS203NCC10A30?

The DS203NCC10A30 has a rated current of 10 A and uses a Type C tripping characteristic.

What residual-current protection does the DS203NCC10A30 provide?

The device has a rated residual operating current of 30 mA and uses Type A residual-current detection for sinusoidal alternating and pulsating DC residual currents.

What is the breaking capacity of the ABB DS203NCC10A30?

The DS203NCC10A30 has a rated short-circuit breaking capacity of 6 kA according to IEC/EN 61009 and an ultimate short-circuit breaking capacity of 10 kA.

How much panel space does the DS203NCC10A30 require?

The ABB DS203NCC10A30 occupies four DIN-rail modules and measures approximately 71 × 85 × 69 mm, integrating residual-current and overcurrent protection within a compact 3P+N device.

Trusted ABB Circuit Protection

ABB DS203NC Type A residual current circuit breakers with overcurrent protection combine compact three-phase circuit protection with detection of sinusoidal AC and pulsating DC residual currents, providing integrated protection for modern commercial and industrial electrical systems.