Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB F-ARI4Test A-25/0.3 is a four-pole Type A residual current circuit breaker rated at 25 A and 300 mA with automatic testing, self-diagnostics and automatic reset functionality for three-phase electrical installations.
£818.61
The ABB F-ARI4Test A-25/0.3 is a four-pole Type A residual current circuit breaker (RCCB) with automatic testing and automatic reset functionality, designed to combine residual-current protection with improved continuity of service. Part of ABB’s F-ARI range, this 3P+N device is intended for three-phase electrical systems where automated testing and restoration of supply can reduce routine maintenance and unnecessary downtime.
The F-ARI system automatically verifies the RCCB protection function and incorporates an automatic reset mechanism for suitable operating conditions. This makes it particularly useful for unattended, remotely located and continuity-critical installations where manual testing and resetting of conventional residual-current devices would otherwise require regular maintenance visits.
With a rated current of 25 A, a rated residual operating current of 300 mA and a 3P+N / four-pole configuration, the F-ARI4Test A-25/0.3 provides Type A residual-current protection for three-phase systems with neutral. It operates at 400 V AC, is suitable for DIN-rail installation and incorporates automatic testing, automatic resetting and an auxiliary contact within the device assembly.
Residual current circuit breakers require periodic functional verification to ensure that their protective mechanism remains operational. In installations containing numerous RCCBs, manual testing and resetting can require substantial maintenance effort, particularly where distribution boards are remote or difficult to access.
The ABB F-ARI range combines automatic functional testing with automatic reset technology. The F-ARI4Test A-25/0.3 therefore combines 25 A, 300 mA Type A residual-current protection with integrated self-diagnostics, automatic testing and reset functionality, helping reduce maintenance intervention and improve electrical system availability in suitable three-phase applications.
| Series | F-ARI Test |
|---|---|
| Product group | F200 / FH200 RCCB |
| ABB order code | 2CSF304131R3250 |
| EAN | 8012542290254 |
| Product type | RCCB with automatic test and reset function |
| Residual-current type | Type A |
| Number of poles | 3P+N / 4P |
| Rated current (In) | 25 A |
| Rated residual current (IΔn) | 300 mA |
| Rated voltage (Ue) | 400 V AC |
| Rated frequency | 50 Hz |
| Rated conditional short-circuit current | 10 kA |
| Rated switching capacity | 0.63 kA |
| Surge-current withstand | 3 kA |
| Automatic test | Yes |
| Automatic reset | Yes |
| Integrated functions | Self-diagnostics, automatic reset and auxiliary contact |
| Auxiliary contact rated current | 0.1 A |
| Auxiliary contact voltage | 5–230 V AC/DC |
| Module width | 7 modules |
| Overall width | 124.8 mm |
| Overall height | 106 mm |
| Installation depth | 73.5 mm |
| Mounting type | DIN rail |
| Weight | approx. 0.9 kg |
| Reference standards | EN 61008-1, VDE V 0664-120 Annex M |
The ABB F-ARI4Test A-25/0.3 provides 25 A, 300 mA Type A residual-current protection with automatic testing and reset functionality for three-phase electrical systems with neutral, helping reduce manual maintenance and improve continuity of service.
The F-ARI4Test A-25/0.3 has a rated current of 25 A and a rated residual operating current of 300 mA.
The automatic test function verifies operation of the RCCB automatically, reducing the routine manual testing requirements associated with conventional residual-current protection devices.
Yes. The F-ARI4Test A-25/0.3 incorporates an automatic reset function together with self-diagnostics and an auxiliary contact, supporting improved continuity of service in suitable electrical installations.
The ABB order code for the F-ARI4Test A-25/0.3 is 2CSF304131R3250.
ABB F-ARI automatic-test RCCBs combine Type A residual-current protection with automatic functional testing, self-diagnostics and automatic reset technology, helping reduce routine maintenance requirements while supporting continuity of service in commercial, industrial and infrastructure electrical installations.