2CSF204123R3630 ABB F204 A-63/0.3-L RCCB 4P Type A 300mA 63A

2CSF204123R3630 ABB F204 A-63/0.3-L RCCB 4P Type A 300mA 63A

ABB F204 A-63/0.3-L is a 4-pole 63 A Type A RCCB with 300 mA residual current sensitivity, 230/400 V AC operation and a left-side neutral connection for residual current protection in three-phase electrical distribution systems.

SKU: 2CSF204123R3630Alt SKU: F204A630.3LMPN: 2CSF204123R3630
Price
List Price £276.20 ex VAT
Your Price (ex VAT) Save 35%
£179.53 35% OFF
You save £96.67 per unit
Manufacturer Lead Time Estimated Delivery 7 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £179.53
Trade pricing is personalised to your account

Manufacturer Lead Time

£179.53

Why Choose the ABB F204 A-63/0.3-L RCCB?

The ABB F204 A-63/0.3-L, order code 2CSF204123R3630, is a 4-pole Type A residual current circuit breaker (RCCB) designed to provide dependable residual current protection in three-phase electrical distribution systems. Part of the established ABB F200 / FH200 RCCB product group, this model features the neutral connection on the left and is suitable for residential, commercial and industrial applications.

This RCCB has a rated current of 63 A and a rated residual operating current of 300 mA. Its Type A characteristic provides detection of sinusoidal AC residual currents and pulsating DC residual currents, including pulsating residual currents with smooth DC components up to the limits specified for the F200 Type A range.

The 4-pole configuration is designed for three-phase electrical distribution, while its 230/400 V AC rating and four-module DIN rail format make it straightforward to integrate into compatible distribution boards. With a rated insulation voltage of 500 V and rated impulse withstand voltage of 4 kV, the F204 A-63/0.3-L provides robust ABB residual current protection for professional installations.

Key Advantages

  • Reliable ABB Type A residual current protection for modern electrical installations.
  • 63 A rated current for higher-current distribution circuits.
  • 300 mA residual current sensitivity for earth leakage and fault protection.
  • Detects sinusoidal AC and pulsating DC residual currents.
  • 4-pole configuration for three-phase electrical distribution.
  • Neutral connection on the left for installations requiring this terminal arrangement.
  • Compact four-module DIN rail format for modular distribution boards.

Key Features

  • ABB F200 series RCCB.
  • Type A residual current characteristic.
  • 4-pole configuration.
  • 63 A rated current.
  • 300 mA rated residual current.
  • 230/400 V AC rated operational voltage.
  • 50/60 Hz rated frequency.
  • Detection of sinusoidal AC and pulsating DC residual currents.
  • Left-side neutral arrangement.
  • DIN rail mounting for modular electrical installations.
  • Designed to meet IEC/EN 61008-1 and IEC/EN 61008-2-1.

Type A Residual Current Protection with Left-Side Neutral

Type A RCCBs are designed to respond to sinusoidal AC residual currents and pulsating DC residual currents. This makes the ABB F204 A-63/0.3-L suitable for electrical circuits containing equipment with electronic components that can produce pulsating DC earth leakage in addition to conventional AC residual currents.

The -L configuration provides the neutral connection on the left, making this version suitable where the distribution board layout or installation design requires this terminal arrangement. As an RCCB, the F204 A-63/0.3-L does not incorporate overload or short-circuit protection, so appropriate overcurrent protection must be provided separately. Its 300 mA sensitivity should also be distinguished from 30 mA devices typically specified where additional protection against electric shock is required.

Typical Applications

  • Commercial electrical distribution systems.
  • Industrial electrical installations.
  • Residential three-phase distribution boards.
  • Three-phase circuits requiring 4-pole residual current protection.
  • Installations requiring a left-side neutral connection.
  • Circuits supplying equipment capable of producing pulsating DC residual currents.
  • Building services and electrical distribution equipment.
  • Installations requiring 300 mA Type A residual current protection.

Technical Specifications

Series F200
Product group F200 / FH200 RCCB
Manufacturer part number F204A630.3L
ABB order code 2CSF204123R3630
EAN 8012542820901
Product type Residual current circuit breaker (RCCB)
Number of poles 4
Rated current 63 A
Rated residual current 300 mA
Residual current type Type A
Residual current detection Sinusoidal AC and pulsating DC
Rated operational voltage 230/400 V AC
Rated frequency 50/60 Hz
Rated insulation voltage 500 V
Rated impulse withstand voltage 4 kV
Rated short-time withstand current 1 kA
Surge current capacity 0.25 kA
Neutral position Left
Protection rating IP20
Pollution degree 2
Number of modules 4
Dimensions (H × W × D) 85 × 70 × 69 mm
Operating temperature -25 to +55 °C
Mounting type DIN rail
Standards IEC/EN 61008-1, IEC/EN 61008-2-1

Frequently Asked Questions

What is the ABB F204 A-63/0.3-L used for?

The ABB F204 A-63/0.3-L is a 4-pole Type A RCCB designed to provide 300 mA residual current protection in appropriately designed three-phase electrical distribution systems.

What are the current and residual current ratings of the F204 A-63/0.3-L?

The RCCB has a rated current of 63 A and a rated residual operating current of 300 mA.

What does Type A mean on the ABB F204 A-63/0.3-L?

Type A means the RCCB is designed to detect sinusoidal AC and pulsating DC residual currents, providing broader residual current detection than a Type AC RCCB.

What does the L mean in F204 A-63/0.3-L?

The L identifies this F204 configuration with the neutral connection positioned on the left, making it suitable for distribution systems and installation layouts requiring this terminal arrangement.

Does the ABB F204 A-63/0.3-L provide overload protection?

No. The F204 A-63/0.3-L is an RCCB providing residual current protection. Appropriate overcurrent protection must be provided separately where required for overload and short-circuit protection.

Trusted ABB Protection for Three-Phase Electrical Distribution

ABB F200 Type A residual current circuit breakers provide dependable protection against sinusoidal AC and pulsating DC residual currents, with the F204 A-63/0.3-L offering a practical left-side neutral configuration for compatible residential, commercial and industrial distribution systems.