2CSF202006R3630 ABB FH202 AC-63/0.3 RCCB 2P Type AC 300 mA 63 A

2CSF202006R3630 ABB FH202 AC-63/0.3 RCCB 2P Type AC 300 mA 63 A

ABB FH202 AC-63/0.3 is a 2-pole Type AC FH200 residual current circuit breaker rated at 63 A with 300 mA residual-current sensitivity for compatible low-voltage electrical installations.

SKU: 2CSF202006R3630Alt SKU: FH202AC630.3MPN: 2CSF202006R3630
Price
List Price £130.64 ex VAT
Your Price (ex VAT) Save 35%
£84.92 35% OFF
You save £45.72 per unit
Manufacturer Lead Time Estimated Delivery 7 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £84.92
Trade pricing is personalised to your account

Manufacturer Lead Time

£84.92

Why Choose the ABB FH202 AC-63/0.3 RCCB?

The ABB FH202 AC-63/0.3 is a 2-pole residual current circuit breaker (RCCB) from the ABB FH200 family, designed to provide residual-current protection in compatible low-voltage electrical installations. Supplied under ABB order code 2CSF202006R3630, it combines a rated current of 63 A with a rated residual operating current of 300 mA.

As a Type AC RCCB, the FH202 AC-63/0.3 is designed to respond to sinusoidal alternating residual currents. Its 300 mA residual-current rating makes it suitable for appropriate earth-leakage and fault-protection applications where this sensitivity is specified by the circuit design and applicable installation requirements.

The two-pole configuration is intended for compatible single-phase circuits, while its modular construction enables straightforward DIN-rail installation in distribution boards and electrical panels. As an RCCB without integral overcurrent protection, the FH202 AC-63/0.3 must be coordinated with appropriately selected overload and short-circuit protection.

Key Advantages

  • 63 A rated current for compatible low-voltage circuits.
  • 300 mA rated residual current for appropriate earth-leakage and fault-protection applications.
  • 2-pole configuration for compatible single-phase installations.
  • Type AC residual-current detection for sinusoidal alternating residual currents.
  • DIN-rail format for straightforward integration into modular distribution equipment.
  • Part of ABB's established FH200 RCCB family.
  • Suitable for residential, commercial and industrial low-voltage distribution applications where its ratings are appropriate.

Key Features

  • ABB FH202 AC-63/0.3 RCCB.
  • 2 poles.
  • 63 A rated current.
  • 300 mA rated residual current.
  • Type AC residual-current characteristic.
  • Designed for compatible single-phase circuits.
  • DIN-rail mounting.
  • Residual-current protection without integral overcurrent protection.
  • Suitable for modular low-voltage distribution equipment.
  • ABB order code 2CSF202006R3630.

300 mA Residual-Current Protection for Electrical Installations

An RCCB monitors the current flowing through the live conductors of a circuit and operates when an imbalance indicates current leakage to earth. The ABB FH202 AC-63/0.3 combines a substantial 63 A rated current with a 300 mA rated residual operating current for compatible residual-current protection applications.

A 300 mA RCCB is generally selected for installation and earth-fault protection applications rather than the 30 mA additional personal protection commonly specified for certain final circuits. The FH202 AC-63/0.3 is an RCCB rather than an RCBO, so it does not provide integral overload or short-circuit protection; suitable overcurrent protection must therefore be provided separately.

Typical Applications

  • Low-voltage electrical distribution boards.
  • Commercial electrical installations.
  • Industrial electrical distribution systems.
  • Compatible single-phase circuits.
  • Earth-leakage and residual-current protection.
  • Distribution and control panels.
  • DIN-rail modular electrical assemblies.

Technical Specifications

Product group F200 / FH200 RCCB
Series FH200
Order code 2CSF202006R3630
Product type Residual Current Circuit Breaker (RCCB)
Number of poles 2
Rated current (In) 63 A
Rated residual current (IΔn) 300 mA
Residual current type Type AC
Rated operational voltage 230 V AC
Rated insulation voltage (Ui) 500 V
Rated impulse withstand voltage (Uimp) 4 kV
Frequency 50/60 Hz
Mounting DIN rail
Overcurrent protection Not incorporated; separate protection required

Frequently Asked Questions

What is the ABB FH202 AC-63/0.3?

The ABB FH202 AC-63/0.3 is a 2-pole Type AC residual current circuit breaker from the FH200 family, rated at 63 A with a 300 mA rated residual current.

What does the 300 mA rating of the FH202 AC-63/0.3 mean?

The 300 mA figure is the RCCB's rated residual operating current. The device is designed to operate when qualifying residual current reaches its operating threshold, subject to the specified operating characteristics.

What type of residual current does the FH202 AC-63/0.3 detect?

The FH202 AC-63/0.3 is a Type AC RCCB, designed to respond to sinusoidal alternating residual currents.

Does the ABB FH202 AC-63/0.3 provide overload and short-circuit protection?

No. The FH202 AC-63/0.3 is an RCCB without integral overcurrent protection, so appropriate circuit-breaker or fuse protection must be provided separately.

What is the ABB order code for the FH202 AC-63/0.3?

The ABB order code for the FH202 AC-63/0.3 RCCB is 2CSF202006R3630.

ABB FH200 Residual Current Protection

ABB FH200 RCCBs provide residual-current protection for compatible low-voltage electrical installations, with variants covering different rated currents, residual-current sensitivities and residual-current characteristics.