2CSB204892R3630 ABB DDA204 B S-63/0.3 RCD Block 4P 63A 300mA

2CSB204892R3630 ABB DDA204 B S-63/0.3 RCD Block 4P 63A 300mA

ABB DDA204 B S-63/0.3 is a four-pole 63 A Type B selective RCD block with 300 mA residual-current sensitivity for coordinated protection against sinusoidal AC, pulsating DC and smooth DC residual currents.

SKU: 2CSB204892R3630Alt SKU: DDA204BS630.3MPN: 2CSB204892R3630
Price
List Price £1,585.44 ex VAT
Your Price (ex VAT) Save 35%
£1,030.54 35% OFF
You save £554.90 per unit
Manufacturer Lead Time Estimated Delivery 10 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £1,030.54
Trade pricing is personalised to your account

Manufacturer Lead Time

£1,030.54

Why Choose the ABB DDA204 B S-63/0.3 RCD Block?

The ABB DDA204 B S-63/0.3 is a four-pole Type B selective residual current device (RCD) block from the ABB DDA200 range, designed for assembly with compatible ABB miniature circuit breakers. Its selective S-type operating characteristic supports coordinated residual-current protection in multi-level electrical distribution systems.

As a Type B device, the DDA204 B S-63/0.3 is designed to respond to sinusoidal AC, pulsating DC and smooth DC residual currents. Its 300 mA rated residual operating current is intended for earth-leakage and fault protection at this sensitivity, while the selective characteristic makes it suitable for applications where coordination with downstream residual-current devices is required.

With a 63 A rated current and four-pole configuration, this DDA200 RCD block is suited to commercial and industrial distribution systems containing modern power-electronic equipment. When correctly combined with a compatible ABB miniature circuit breaker, the assembly provides residual-current protection alongside the MCB's overcurrent and short-circuit protection.

Key Advantages

  • Four-pole RCD block for multi-pole electrical distribution circuits.
  • 63 A rated current for higher-current circuit protection applications.
  • 300 mA rated residual operating current for earth-leakage and fault protection.
  • Type B residual-current detection for sinusoidal AC, pulsating DC and smooth DC residual currents.
  • Selective S-type operation supports residual-current protection coordination with downstream devices.
  • Designed for modular combination with compatible ABB miniature circuit breakers.

Key Features

  • ABB DDA200 RCD block series.
  • DDA204 B S-63/0.3 model.
  • Four-pole configuration.
  • 63 A rated current.
  • 300 mA rated residual operating current.
  • Type B residual-current characteristic.
  • Selective S-type operating characteristic.
  • Detection of sinusoidal AC, pulsating DC and smooth DC residual currents.
  • Modular design for combination with compatible ABB MCBs.

Selective Type B Residual-Current Protection

Type B residual-current protection is designed for circuits where power-electronic equipment can produce residual-current waveforms containing AC, pulsating DC or smooth DC components. This broader detection capability makes the DDA204 B S-63/0.3 suitable for installations where conventional Type AC or Type A residual-current detection may not cover the expected fault-current waveform.

The selective S-type characteristic provides time-delayed operation intended to support discrimination between residual-current protective devices installed at different levels of a distribution system. Combined with its 300 mA sensitivity, the DDA204 B S-63/0.3 is suited to upstream earth-leakage and fault protection where Type B detection and selective coordination are required.

Typical Applications

  • Commercial and industrial electrical distribution systems.
  • Upstream circuits requiring selective residual-current protection.
  • Four-pole circuits requiring 300 mA Type B protection.
  • Installations incorporating variable-speed drives, converters and inverter-based equipment.
  • Applications where smooth DC residual currents may occur.
  • ABB modular protection assemblies requiring coordination with downstream residual-current devices.

Technical Specifications

Series DDA200
ABB order code 2CSB204892R3630
Product type Residual current device (RCD) block
Residual-current type B
Operating characteristic Selective, S type
Number of poles 4
Rated current 63 A
Rated residual operating current 300 mA
Residual-current detection Sinusoidal AC, pulsating DC and smooth DC
Applicable standard IEC/EN 61009 Annex G
Mounting DIN rail as part of a compatible modular circuit protection assembly

Frequently Asked Questions

What is the ABB DDA204 B S-63/0.3 used for?

It is a four-pole Type B selective RCD block designed for 300 mA residual-current protection and coordination with downstream residual-current devices when correctly combined with a compatible ABB miniature circuit breaker.

What is the rated current of the DDA204 B S-63/0.3?

The ABB DDA204 B S-63/0.3 has a rated current of 63 A.

What residual-current sensitivity does this RCD block provide?

It has a rated residual operating current of 300 mA, intended for applications requiring earth-leakage and fault protection at this sensitivity.

What does the S characteristic mean on this ABB RCD block?

The S characteristic identifies selective, time-delayed operation, supporting coordination with downstream residual-current protective devices so that the device closest to a fault can operate first when the protection system is correctly designed.

What residual currents can this Type B RCD block detect?

Type B residual-current protection is designed to respond to sinusoidal AC, pulsating DC and smooth DC residual currents, making it suitable for circuits containing equipment capable of producing complex residual-current waveforms.

Trusted ABB Circuit Protection

ABB DDA200 Type B selective residual current device blocks combine broad residual-current detection with selective operation, supporting coordinated protection in modern commercial and industrial electrical distribution systems.