2CSB204201R4630 ABB DDA204 A S-63/0.5 Selective RCD Block 4P 63A 500mA

2CSB204201R4630 ABB DDA204 A S-63/0.5 Selective RCD Block 4P 63A 500mA

ABB DDA204 A S-63/0.5 is a four-pole 63 A Type A selective RCD block with 500 mA residual-current sensitivity for coordinated protection against sinusoidal AC and pulsating DC residual currents.

SKU: 2CSB204201R4630Alt SKU: DDA204AS630.5MPN: 2CSB204201R4630
Price
List Price £226.55 ex VAT
Your Price (ex VAT) Save 35%
£147.26 35% OFF
You save £79.29 per unit
Manufacturer Lead Time Estimated Delivery 8 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £147.26
Trade pricing is personalised to your account

Manufacturer Lead Time

£147.26

Why Choose the ABB DDA204 A S-63/0.5 RCD Block?

The ABB DDA204 A S-63/0.5 is a four-pole Type A selective residual current device (RCD) block designed for assembly with compatible ABB miniature circuit breakers. Part of the ABB DDA200 RCD block series, it combines Type A residual-current detection with selective operation for coordinated protection in electrical distribution systems.

This RCD block detects sinusoidal alternating residual currents and pulsating DC residual currents. Its 500 mA rated residual operating current and selective S-type characteristic make it suitable for earth leakage and fault protection where coordination between upstream and downstream residual-current protective devices is required.

With a 63 A rated current and four-pole configuration, the DDA204 A S-63/0.5 is suited to commercial, industrial and building distribution systems requiring selective Type A residual-current protection. When combined with a compatible ABB miniature circuit breaker, the assembly provides residual-current protection alongside the MCB's overcurrent and short-circuit protection.

Key Advantages

  • Four-pole RCD block for multi-pole electrical distribution circuits.
  • 63 A rated current for higher-current protection applications.
  • 500 mA rated residual operating current.
  • Type A detection for sinusoidal AC and pulsating DC residual currents.
  • Selective S-type operation supports coordination with suitable downstream RCDs.
  • Designed for combination with compatible ABB miniature circuit breakers.

Key Features

  • ABB DDA200 RCD block series.
  • Four-pole configuration.
  • 63 A rated current.
  • 500 mA rated residual operating current.
  • Type A, selective S characteristic.
  • Detection of sinusoidal AC and pulsating DC residual currents.
  • Time-delayed selective operation for improved RCD coordination.
  • 50–60 Hz rated frequency.
  • Modular design for combination with compatible ABB MCBs.

Selective Type A Residual-Current Protection

Residual current devices monitor the balance of current flowing through the active conductors of an electrical circuit. If an insulation fault or leakage path causes current to flow to earth, the resulting imbalance can initiate disconnection when the RCD block is correctly combined with its compatible circuit breaker.

The selective S-type characteristic provides intentional time-delayed operation to support discrimination between upstream and suitable downstream residual-current protective devices. Combined with Type A sensitivity to sinusoidal AC and pulsating DC residual currents, the DDA204 A S-63/0.5 is suited to coordinated distribution systems where selective residual-current protection is required.

Typical Applications

  • Commercial electrical distribution boards.
  • Industrial power distribution systems.
  • Building-services electrical installations.
  • Upstream residual-current protection in coordinated installations.
  • Four-pole circuits requiring 500 mA selective residual-current protection.
  • Circuits requiring detection of sinusoidal AC and pulsating DC residual currents.

Technical Specifications

Series DDA200
ABB order code 2CSB204201R4630
Product type Residual current device (RCD) block
Residual-current type A
Operating characteristic Selective, S type
Number of poles 4
Rated current 63 A
Rated residual operating current 500 mA
Rated frequency 50–60 Hz
Rated insulation voltage 500 V
Rated impulse withstand voltage 4 kV
Applicable standard IEC/EN 61009 Annex G
Mounting DIN rail as part of a compatible modular circuit protection assembly

Frequently Asked Questions

What is the ABB DDA204 A S-63/0.5 used for?

It is a four-pole Type A selective RCD block designed to provide residual-current protection and support coordination with suitable downstream protective devices when combined with a compatible ABB miniature circuit breaker.

What is the rated current of the DDA204 A S-63/0.5?

The ABB DDA204 A S-63/0.5 has a rated current of 63 A.

What residual-current sensitivity does this RCD block provide?

It has a rated residual operating current of 500 mA.

What does the S characteristic mean on the DDA204 A S-63/0.5?

The S designation indicates selective, time-delayed operation, supporting coordination between an upstream RCD and suitable downstream residual-current protective devices.

What residual currents can this Type A RCD block detect?

Type A protection is designed to detect sinusoidal alternating residual currents and pulsating DC residual currents.

Trusted ABB Circuit Protection

ABB DDA200 residual current device blocks provide a modular solution for integrating residual-current protection with compatible miniature circuit breakers, with selective S-type variants supporting coordinated protection in commercial, industrial and building distribution systems.