2CSB203201R3630 ABB DDA203 A S-63/0.3 RCD 3P AS 300mA 63A

2CSB203201R3630 ABB DDA203 A S-63/0.3 RCD 3P AS 300mA 63A

ABB DDA203 A S-63/0.3 is a 3-pole Type A selective RCD block rated at 63 A with a 300 mA residual operating current for coordinated residual current protection in three-phase electrical distribution systems.

SKU: 2CSB203201R3630Alt SKU: DDA203AS630.3MPN: 2CSB203201R3630
Price
List Price £215.19 ex VAT
Your Price (ex VAT) Save 35%
£139.87 35% OFF
You save £75.32 per unit
Manufacturer Lead Time Estimated Delivery 8 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £139.87
Trade pricing is personalised to your account

Manufacturer Lead Time

£139.87

Why Choose the ABB DDA203 A S-63/0.3 RCD Block?

The ABB DDA203 A S-63/0.3 is a selective 3-pole Type A residual current device (RCD) block designed to provide residual current protection when assembled with compatible ABB miniature circuit breakers. As part of the established ABB DDA200 RCD series, it provides protection against sinusoidal alternating and pulsating DC residual currents while incorporating a selective time delay for coordinated protection in electrical distribution systems.

Designed for combination with compatible ABB modular circuit breakers, the DDA203 A S-63/0.3 enables residual current protection to be combined with the overcurrent and short-circuit protection provided by the associated circuit breaker. Its Type A selective characteristic makes it particularly suitable for installations where discrimination between upstream and downstream residual current protection devices is required.

With a rated current of 63 A, a rated residual operating current of 300 mA and a 3-pole configuration, the DDA203 A S-63/0.3 is suited to commercial and industrial three-phase distribution systems requiring dependable selective earth leakage protection.

Key Advantages

  • Selective Type A residual current protection for three-phase electrical circuits.
  • 63 A rated current for commercial and industrial distribution applications.
  • 300 mA rated residual operating current.
  • Type A detection for sinusoidal alternating and pulsating DC residual currents.
  • Selective (S) operating characteristic supports coordinated residual current protection.
  • Designed for combination with compatible ABB modular circuit breakers.

Key Features

  • ABB DDA200 RCD series.
  • 3-pole selective RCD block for three-phase applications.
  • 63 A rated current.
  • 300 mA rated residual current.
  • Type A selective (S) residual current characteristic.
  • Detection of sinusoidal AC and pulsating DC residual currents.
  • Selective time-delay operation for improved discrimination.
  • Modular design for use with compatible ABB circuit breakers.

Selective Type A Residual Current Protection

The ABB DDA203 A S-63/0.3 combines Type A residual current detection with selective time-delay operation. It responds to sinusoidal alternating and pulsating direct residual currents, while the selective characteristic helps coordinate operation with suitable downstream residual current devices in correctly designed electrical protection systems.

The ABB DDA200 range is designed to combine residual current protection with compatible ABB circuit breakers. This modular arrangement allows the residual current block to work alongside the overcurrent and short-circuit protection of the associated breaker, providing a coordinated protection solution for electrical distribution systems.

Typical Applications

  • Three-phase electrical distribution systems.
  • Commercial electrical distribution boards.
  • Industrial electrical panels and switchboards.
  • Distribution systems requiring selective RCD coordination.
  • Machinery and industrial equipment supply circuits.
  • Circuits requiring 300 mA Type A selective residual current protection.

Technical Specifications

Series DDA200 RCD
ABB order code 2CSB203201R3630
Product type Selective residual current device (RCD) block
Residual current type Type A selective (S)
Number of poles 3
Rated current 63 A
Rated residual current 300 mA
Operating characteristic Selective / time-delayed
Mounting arrangement Coupled with compatible ABB modular circuit breaker

Frequently Asked Questions

What is the ABB DDA203 A S-63/0.3 used for?

The DDA203 A S-63/0.3 is a 3-pole selective residual current device block designed to provide Type A residual current protection when combined with a compatible ABB circuit breaker in three-phase electrical distribution systems.

What is the rated current of the DDA203 A S-63/0.3?

The ABB DDA203 A S-63/0.3 has a rated current of 63 A.

What is the residual current rating?

The DDA203 A S-63/0.3 has a rated residual operating current of 300 mA.

What does Type A S mean on this RCD block?

Type A means the device responds to sinusoidal alternating and pulsating direct residual currents, while the S selective characteristic introduces a time delay to support coordination with suitable downstream residual current devices.

Why use a selective RCD block?

A selective RCD block is used where coordinated residual current protection is required. Its delayed operating characteristic can help a suitable downstream device clear a fault first, reducing unnecessary disconnection of upstream circuits.