Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB DDA202A250.03APR DDA202 A-25/0.03 AP-R is a 2-pole 25 A 30 mA Type A residual current device block with enhanced immunity to transient disturbances for use with compatible ABB miniature circuit breakers.
£97.20
The ABB DDA202A250.03APR, manufacturer type DDA202 A-25/0.03 AP-R, is a 2-pole Type A AP-R residual current device (RCD) block designed for combination with compatible ABB miniature circuit breakers. Part of the ABB DDA200 RCD series, it provides residual-current protection with enhanced resistance to unwanted tripping in installations where electrical disturbances can affect conventional instantaneous devices.
The DDA202 A-25/0.03 AP-R is designed to detect sinusoidal alternating and pulsating DC residual currents. ABB's AP-R characteristic provides increased immunity to transient disturbances while incorporating a short intentional delay, helping improve continuity of service without sacrificing the residual-current protection required by the circuit.
With a rated current of 25 A, a rated residual operating current of 30 mA and a 2-pole configuration, the DDA202A250.03APR is suited to electrical installations requiring sensitive Type A residual-current protection together with improved resistance to nuisance tripping. Its modular format allows it to be combined with compatible ABB miniature circuit breakers for coordinated residual-current and overcurrent protection.
Residual current protection operates by monitoring the balance of current flowing through the live conductors and disconnecting the circuit when earth leakage exceeds the specified threshold. The ABB DDA202 A-25/0.03 AP-R combines 30 mA sensitivity with Type A detection for both sinusoidal AC and pulsating DC residual currents.
The AP-R characteristic is particularly useful where switching operations, electronic equipment or transient disturbances could cause unwanted operation of conventional instantaneous RCDs. Its increased resistance to transient currents and short-delay behaviour help improve installation continuity while retaining dependable residual-current protection.
| Series | DDA200 |
|---|---|
| SKU | DDA202A250.03APR |
| ABB order code | 2CSB202401R1250 |
| Product type | Residual current device block / RCD block |
| Residual-current type | Type A |
| Operating characteristic | AP-R |
| Number of poles | 2 |
| Rated current | 25 A |
| Rated residual operating current | 30 mA |
| Rated voltage | 230/400 V AC |
| Rated frequency | 50–60 Hz |
| Rated insulation voltage | 500 V |
| Rated impulse withstand voltage | 4 kV |
| Protection rating | IP2X |
| Standard | IEC/EN 61009 Annex G |
The ABB DDA202A250.03APR is a Type A AP-R RCD block designed for combination with compatible ABB miniature circuit breakers to provide sensitive residual-current protection with enhanced immunity to unwanted tripping.
The ABB DDA202 A-25/0.03 AP-R has a rated current of 25 A.
The DDA202 A-25/0.03 AP-R has a rated residual operating current of 30 mA.
The AP-R characteristic identifies an ABB RCD design with enhanced immunity to transient disturbances and short-delay operation, helping reduce unwanted tripping compared with conventional instantaneous devices.
As a Type A device, it is designed to respond to sinusoidal alternating residual currents and pulsating DC residual currents.
ABB DDA200 AP-R residual current device blocks combine Type A earth-fault detection with enhanced resistance to transient disturbances, providing dependable circuit protection where continuity of service and reduced nuisance tripping are important.